Reply from: Mike Holt I've done the math, the impedance of the Ufer ground does not have any impact on the fault current to the source and it has no effective impact if the service neutral is open. So to close this topic, the purpose of the Grounding Electrode System is not to assist in clearing a ground, it's purpose is to ground metal parts to the earth to reduce transient overvoltage... but this is another topic. Reply to Mike Holt Reply from: James Wilson The UFER ground is in parallel with the grounded conductor back to the source. In case of a ground fault a portion of that fault, although a small amount, will flow thru the UFER electrode back to the grounded source. If the UFER ground is increased in length, say from 20ft to 40ft, the resistance of the earth connection is reduced by 26%. That's using a formula from IEEE Std 142 "The Green Book" on grounding. This reduction would result in a slight increase in the return current thru the UFER. As I stated I see no advantage in increasing the capacity of the UFER path. There is nothing in the previous comments that implied that the grounding electrode, be it a UFER or any other approved type, is used to assist in clearing a ground fault. The NEC doesn't require that it be sized to guard against a neutral being open, which, if that occurred would be influenced by a lower UFER resistance. Reply to James Wilson |