Grounding vs Bonding: 250.66 Grounding Electrode Conductor—Size

February 10, 2006  

  View Comments | Add Comments  

PART III. GROUNDING ELECTRODE SYSTEM AND GROUNDING ELECTRODE CONDUCTOR  

Hi Res - Cable/DSL [7953Kb]
VIEWING Video FILE requires Real Media Player [ FREE ]

       Page 12 of 14
Sections

250.66 Grounding Electrode Conductor—Size.

Except for a ground rod electrode [250.66(A)], a concrete-encased electrode [250.66(B)], or a ground ring electrode [250.66(C)], the grounding electrode conductor must be sized based on the largest service-entrance conductor or equivalent area for parallel conductors in accordance with Table 250.66

Question: What size grounding electrode conductor is required for a 1,200A service that is supplied with three parallel sets of 600 kcmil conductors per phase? Figure 250–116

(a) 1 AWG     (b) 1/0 AWG    (c) 2/0 AWG     (d) 3/0 AWG

Answer: (d) 3/0 AWG

The equivalent area of three parallel 600 kcmil conductors is 1,800 kcmil per phase [Table 250.66].

FPN: Because the grounded neutral service conductor is required to serve as the low-impedance ground-fault current path back to the source, it must be sized no smaller than that shown in Table 250.66 [250.24(C)(1)]. Of course, it must be sized to carry the maximum unbalanced load as calculated by 220.61.
(A) Ground Rod. Where the grounding electrode conductor is connected to a ground rod, that portion of the grounding electrode conductor that is the sole connection to the ground rod isn’t required to be larger than 6 AWG copper. Figure 250–117

Author’s Comment: See 250.52(A)(5) for the installation requirements of a ground rod electrode.
(B) Concrete-Encased Grounding Electrode (Ufer Ground). Where the grounding electrode conductor is connected to a concrete-encased electrode, that portion of the grounding electrode conductor that is the sole connection to the concrete-encased electrode isn’t required to be larger than 4 AWG copper. Figure 250–118

Author’s Comment: See 250.52(A)(3) for the installation requirements of a concrete-encased electrode.
(C) Ground Ring. Where the grounding electrode conductor is connected to a ground ring, that portion of the conductor that is the sole connection to the ground ring isn’t required to be larger than the conductor used for the ground ring.

Author’s Comment: A ground ring encircling the building or structure in direct contact with earth must consist of not less than 20 ft of bare copper conductor not smaller than 2 AWG [250.52(A)(4)].



Figure 250–116
(Click on image to enlarge)


Figure 250–117
(Click on image to enlarge)


Figure 250–118
(Click on image to enlarge)

   

Grounding versus Bonding Library - DVDs
Grounding and bonding problems are at epidemic levels. Surveys repeatedly show a high percentage of power quality problems are due to poor grounding and bonding. Electrical theory has been applied to this difficult to understand Article, making it easier for students to grasp the concepts of grounding and bonding. Additionally, Mike has color coded the graphics so you can easily differentiate between grounding and bonding. For a limited time, you can order the Entire Grounding versus Bonding Library including the textbook, 2 videos, MP3 Audio CD and the Online Program for this great price. You save over $200!

Product Code: 05GBDVD
ISBN: N/A
MultiMedia: Tape & CDROM & DVD

DVD/CD Return Policy: Unopened sealed DVD's or CD's may be returned within 10 days and we will credit your credit card or issue a refund for the price of the item(s). Opened items may not be returned unless they arrive defective.

Table of Contents
Sample Pages
Sample Graphic

Copyright © 2005 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments
  • The article was about the Grounding Electrode Conductor to the grounding electrode. This we use 250.66 for sizing. You are asking about the Equipment Grounding Conductor, which is another topic. The Equipment Grounding Conductor is sized in accordance with Table 250.122.



Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter