Article 600: Electric Signs and Outline Lighting
 

 

Topic - NEC
Subject - Article 600: Electric Signs and Outline Lighting

February 18, 2008
This newsletter was sent to 28300 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 600: Electric Signs and Outline Lighting

By Mike Holt for EC&M Magazine

 

How to light up electric signs, not people

 

Every commercial occupancy needs a form of identification, and the standard method is the electric sign. This is one reason why you’ll be working with Article 600 if you do much commercial work. Many industrial sites also use electric signs.

 

Article 600 covers the installation of conductors and equipment for electric signs and outline lighting (see Sidebar). It also covers installations and equipment that use neon tubing for signs, decorative elements, skeleton tubing, or art forms [600.1].

 

Electric signs, section signs, and outline lighting—fixed, mobile, or portable—must be listed and installed per the listing instructions. Field-installed skeleton tubing and outline lighting needn’t be listed, if you wire it per Chapter 3 [600.3].

 

Branch Circuits

 

If a tenant location is accessible to pedestrians, install at least one sign outlet at each entrance (service hallways and corridors don’t count as entrances) [600.5]. Dedicate an individual branch circuit, rated at least 20A, for this purpose. The circuit can serve multiple sign outlets, but no other load.

 

Terminate sign wiring at the enclosure, box, or conduit body of the sign (same applies to outline lighting). Poles used for sign support can contain the sign circuit conductors, if the installation complies with 410.30(B) [600.5(C)(3)].

 

Each circuit that supplies a sign (or outline lighting system) must be controlled by an externally operable switch or circuit breaker that opens all ungrounded conductors [600.6].

 

The “within sight” (see Article 100) rule applies to parts of the sign that you can energize. That rule requires the disconnecting means to be within sight of a sign unless the disconnecting means can be locked in the open position [600.6]. The provision for locking (or adding a lock to) the disconnecting means must be on the switch or circuit breaker whether the lock is there or not. A portable locking means doesn’t meet this requirement.

 

If you install signs (or outline lighting systems) operated by electronic or electromechanical controllers external to the sign (or outline lighting system), install the disconnecting means so it is:

 

  1. Within sight of, or in the same enclosure with, the controller.
  2. Capable of disconnecting the sign (or outline lighting) and the controller from all ungrounded supply conductors.
  3. Capable of being locked in the open position. The locking provision requirements are the same as for the disconnect.

Grounding and Bonding

 

Connect signs (and metal equipment of outline lighting systems) to the equipment grounding conductor of the supply circuit, using an equipment grounding conductor (EGC) specified in 250.118 [600.7(A)(1)]. Size the EGC per 250.122, based on the rating of the overcurrent device protecting the conductors that supply the sign.

 

Terminate each EGC using one of the following methods [250.8]:

  • Listed pressure connectors.
  • Terminal bars.
  • Pressure connectors listed for direct burial or concrete encasement [250.70].
  • Exothermic welding.
  • Machine screws that engage at least two threads or are secured with a nut.
  • Self-tapping machine screws that engage at least two threads.
  • Connections that are part of a listed assembly.
  • Other listed means.

Auxiliary grounding electrodes are not required for signs, but they are permitted [600.7(A)(4)]. If you install any, they must comply with 250.54. Some facts about auxiliary electrodes:

 

  • You don’t have to bond them to the building or structure grounding electrode system,
  • The grounding conductor to the electrode need not be sized per 250.66, and
  • The contact resistance of the electrode to the earth does not have to comply with the 25 ohm requirement of 250.56.

Don’t try to use the earth as your effective ground-fault current path. It doesn’t qualify as such a path for meeting the requirements of 250.4(A)(3). Because the contact resistance of a grounding electrode to the earth is high, very little ground-fault current returns to the electrical supply source via the earth. Consequently, the circuit overcurrent device will not open and clear the ground fault. This means metal parts will become and remain energized with dangerous potential.

 

Location

 

Locate a sign (or outline lighting system) at least 14 ft above areas accessible to vehicles, unless you mechanically protect it from physical damage [600.9(A)]. Section 225.18(4) requires a minimum of 18 ft overhead conductor clearance above public streets, alleys, roads, parking areas subject to truck traffic, and driveways on other than residential property. This may be an important consideration if you feed a sign with overhead conductors.

 

Protect neon tubing from physical damage, if you use it for signs, decorative elements, skeleton tubing, or art forms in locations that are readily accessible to pedestrians [600.9(B)].

 

Install signs and outline lighting systems in such a way that adjacent combustible materials aren’t subjected to temperatures over 194°F. An incandescent or HID lamp or lampholder must have at least 2 in. of spacing from wood or other combustible materials [600.9(C)].

 

If you install signs or outline lighting systems in wet locations, ensure that they are weatherproof and have drain holes [600.9(D)].

 

Portable or Mobile Signs

 

Portable or mobile signs must be adequately supported and readily movable without the use of tools [600.10]. Each portable or mobile sign must have an attachment plug. Remember that 400.8(2) and (5) prohibit flexible cords from being run through, or above, a suspended ceiling.

 

The cords for portable or mobile signs in wet or damp locations must be junior hard service or hard-service types with an EGC. Also, the signs themselves must have a factory-installed GFCI-protection. If that’s not the case with a particular sign, don’t install it in a wet or damp location.

 

The cords for portable or mobile signs in dry locations (as defined in Article 100) must be SP-2, SPE-2, SPT-2, or heavier (see Table 400.4). These cords can’t be longer than 15 ft [600.10(D)].

 

Ballasts, Transformers, and Electronic Power Supplies

 

Ballasts, transformers, and electronic power supplies must be accessible. They must be securely fastened in place, and their secondary conductors must be as short as possible [600.21].

 

If ballasts, transformers, and electronic power supplies are installed outside of the sign (e.g., in a separate enclosure rather than in the sign), maintain a working space of at least 3 ft high by 3 ft wide by 3 ft deep [600.21(E)].

 

You can install ballasts, transformers, and/or electronic power supplies in attics and soffits, if the point of entry for each component has:

 

  • An access door,
  • A passageway not less than 3 ft high by 22½ in. wide, and
  • A suitable permanent walkway at least 1 ft wide.

At least one lighting outlet that contains a switch (or is controlled by a wall switch) must be installed at the usual point of entry to these spaces. The lighting outlet must be at or near the equipment requiring servicing.

 

Ballasts, transformers, and electronic power supplies can be above a suspended ceiling, if the enclosures are securely fastened in place and don’t use the suspended-ceiling grid for support [600.21(F)]. You cannot connect these to the branch-circuit wiring by a flexible cord. Once again, remember that 400.8(2) and (5) prohibit flexible cords from being run through, or above, a suspended ceiling.

 

Define the sign

 

Article 100 defines an electric sign as any “fixed, stationary, or portable self-contained, electrically illuminated utilization equipment with words or symbols designed to convey information or attract attention.”

 

Outline lighting is an arrangement of incandescent lamps or electric-discharge lighting to outline (call attention to) certain features, such as the shape of a building or the decoration of a window.

 

Article 600 adds definitions in 600.2. Two important ones are:

 

  1. Section Sign. A sign or outline lighting system, shipped as subassemblies that require field-installed wiring between the subassemblies to complete the overall sign. The subassemblies are either physically joined to form a single sign unit, or are installed as separate remote parts of an overall sign.
  2. Skeleton Tubing. Neon tubing sign or outline lighting not attached to an enclosure.
Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • Excellent posting. I've just been asked to wire up a sign for a gas station. It's being moved on the property for better visability. This was just what I needed to zero in on my requirments. Thanks much!

    Dave

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter