Article 695 Fire Pumps - 695.6
 

 
Subject - Article 695 Fire Pumps - 695.6
Based on - NEC - 2005 Edition

November 2, 2007
This newsletter was sent to 27335 newsletter subscribers
 

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 695   Hi Res - Cable/DSL [14455Kb]

VIEWING Video FILE requires
Real Media Player [ FREE ]

     Page 4 of 5
Fire Pumps

695.6 Power Wiring

The text was revised to alert the Code user that the branch circuit conductors for a fire pump motor are sized in accordance with 430.22. In addition, branch circuit conductors must be sized to accommodate the voltage drop requirements of 695.7.

(C) Conductor Size.
(1) Fire Pump Motors and Other Equipment. Conductors supplying fire pump motors and accessory equipment must be sized no less than 125 percent of the sum of the motor full-load currents as listed in Table 430.248 or 430.250, plus 100 percent of the ampere rating of the fire pumps accessory equipment.

(2) Fire Pump Motors Only. Conductors supplying a single fire pump motor must be sized in accordance with the requirements of 430.22.


Author’s Comment: This means that the branch circuit conductors to a single fire pump motor must have a an ampere rating of not less than 125 percent of the fire pump motor full-load current (FLC) as listed in Table 430.248 or 430.250.
Question: What size conductor is required for a 25 hp, 208V three-phase fire pump motor? Figure 695-1
(a) 4 AWG (b) 3 AWG (c) 2 AWG    (d) 1 AWG

Answer: (b) 3 AWG

Conductors sized at 125 percent of the motor’s FLC as listed in Table 430.250
FLC of 25 hp = 74.8A, Table 430.250
Conductor = 74.8A x 1.25
Conductor = 93.5A
3 AWG at 75°C is rated 100A

Note: Fire pump motor circuit protective device size must be set to carry indefinitely the sum of the locked-rotor current of the fire pump motor. According to Table 430.151(B), the locked-rotor current of a 25 hp, 208V three-phase motor is 404A.

In addition, branch circuit conductors for a fire pump motor must be sized to accommodate the voltage drop requirements of 695.7.



Figure 695-1
(Click on image to enlarge)

       
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • Mike,In your example,75 degree rated cable was chosen.Why not 60 degree rated cable?Thanks.

    T.M.Haja Sahib

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter