This article was posted 01/11/2006 and is most likely outdated.

Most Common Installation Deficiencies - 2005 (Part 1 of 3)
 

 
Topic - NEC
Subject - Most Common Installation Deficiencies - 2005 (Part 1 of 3)

January 11, 2006 

| Ask a Question |  Code Graphic Code Quiz Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
  Web Page Version [Printer-Friendly]    

Most Common Installation Deficiencies

State of New Hampshire 2005

Credit: http://www.nh.gov/electrician/concerns_2005.html

The Electricians' Licensing Board in conjunction with the State Electrical Inspectors, municipal electrical and building inspectors and other representatives of the electrical industry in the State of New Hampshire have put together this list of common installation deficiencies and problems encountered by the Board's office staff. The Board welcomes any input from instructors, inspectors, licensees and other concerned parties relative to this list or any other items of concern.

The Board would like to remind all concerned parties that the 2005 NEC becomes effective July 1, 2005 as part of the Board's administrative rules.

The following is a list of the most common deficiencies found with electrical installations in the State of New Hampshire. The list is in random order and it has been formatted to the 2005 edition of the National Electrical Code (NFPA 70-2005). To view the deficiencies and examples for each deficiency, please ‘control/click’ on the light bulb for the appropriate deficiency.

light bulb 1.) A grounding electrode conductor that is attached to the grounded conductor or equipment grounding terminal bar of a remote panelboard.
light bulb 2.) The bonding of metal water piping in the vicinity of separately derived systems.
light bulb 3.) The non-use of expansion fittings in Rigid Non-Metallic (PVC) conduits that are subject to thermal expansion and contraction.
light bulb 4.) The non-use of expansion fittings on conduits emerging from the earth where attached to fixed equipment and are installed in locations that are subject to ground movement.
light bulb 5.) The improper installation and securing of expansion fittings in runs of Rigid Non-Metallic (PVC) Conduit.
light bulb 6.) Use of electrical equipment without following the manufacturer's instructions.
light bulb 7.) The non-bonding of service raceways and equipment.
light bulb 8.) The non-use of a locking type disconnect for submersible well pump motors.
light bulb 9.) The improper connection of septic pumps.
light bulb 10.) Clearances working clearances, headroom, dedicated space.
light bulb 11.) Failure to re-identify the white conductor in cables installed for the purpose of switching, employing the white conductor as an ungrounded conductor.
light bulb 12.) The terminating of more than one grounded conductor under a single terminal.
light bulb 13.) The failure to support luminaires to the ceiling grid in suspended ceilings.
light bulb 14.) The flexible connection to emergency system equipment in hospitals.
light bulb 15.) The mechanical protection of fire pump wiring and control wiring.
light bulb 16.) The location of the disconnecting means for Emergency Systems.
light bulb 17.) The separation of Emergency System Conductors from other conductors.
light bulb 18.) Emergency, Legally Required and Optional Standby Signs
light bulb 19.) The sealing of underground raceways or raceways that are exposed to different temperatures.

 

Mike Holt’s Comment: What an outstanding service by the State of New Hampshire. These guys really have it together. Be sure to ‘control/click’ each of the light bulbs for the technical details.

[ View More Newsletters ] [ Please Reply With Your Comments | View Comments ]

Understanding Volume 1 & 2 together - SAVINGS!
Save $10 when you purchase the Understanding the NEC, Volume 1 and Volume 2 together.

Product Code: 05UND12
Pages:
Illustrations:
Price:
$98.00

 
[ Please Reply With Your Comments | View Comments ] [ View More Newsletters ]

F o r w a r d   t h i s   N e w s l e t t e r   t o   a   F r i e n d !
Do you have a friend, relative, or colleague who you think would be interested in receiving this free newsletter? If so, we encourage you to forward this message along to them. If you received this email from someone else, and wish to receive your own free issues of our newsletter, sign up today!

C o n t a c t    I n f o r m a t i o n
   
 

Copyright © 2002, 2003, 2004, 2005 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Comments
  • Please have the webmaster review the lightbulb for item #17. When used it refers you back to item #16.

    Doug Decherd

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter