This article was posted 08/17/2007 and is most likely outdated.

Article 501 Class I Locations - 501.15
 

 
Subject - Article 501 Class I Locations - 501.15
Based on - NEC - 2005 Edition

August 17, 2007
This newsletter was sent to 26572 newsletter subscribers
 

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 501   Hi Res - Cable/DSL [11637Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
Class I Locations

501.15 Sealing and Drainage

Part II. Wiring

Text revisions clarify that when a conduit leaves a Class I, Division 2 location to an unclassified location, the required boundary seal isn’t required to be explosionproof, but it must be identified for the purpose.

(B) Conduit Seals, Class I, Division 2.
(2) Conduit Boundary Seal at Unclassified Location. A conduit seal fitting must be installed in each conduit that passes from a Class I, Division 2 location into an unclassified location within 10 ft of the Class I, Division 2 area on either side of the boundary. Rigid metal conduit or threaded steel intermediate metal conduit shall be used between the sealing fitting and the point at which the conduit leaves the Division 2 location, and a threaded connection shall be used at the sealing fitting. Except for listed reducers at the conduit seal, there shall be no union, coupling, box, or fitting between the conduit seal and the point at which the conduit leaves the Division 2 location.
Figure 501-1

Author’s Comment: The conduit boundary seal at unclassified locations is to prevent the passage of gases or vapors; it is not to contain explosions in the conduit system.


Figure 501-1
(Click on image to enlarge)

       
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • I will recommend from my experience both ends of explosion proof conduit to be earthed.

    Constantin

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter