This article was posted 05/09/2007 and is most likely outdated.

Article 225: Outside Branch Circuits
 

 
Topic - NEC
Subject
- Article 225: Outside Branch Circuits

May 9, 2007
This newsletter was sent to 25277 newsletter subscribers
 

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 225: Outside Branch Circuits

 

By Mike Holt for EC&M Magazine

 

Get the inside dope on outside branch circuits.

 

Article 225 provides the installation requirements for outside branch circuits and feeders that run on (or between) structures or poles. The NEC differentiates between buildings and structures, but for convenience we’ll refer to both of them as structures.

 

Other articles also pertain to outside branch circuits (see Sidebar); most of these are application-specific. Lighting is the most common application. Make sure you don’t place 277V luminaires within 3 ft of platforms, fire escapes, or windows that open [225.7(C)]. See 210.6(C) for the types of luminaires permitted on 277V or 480V branch circuits.

 

Festoon lighting is a string of outdoor lights suspended between two points [Article 100]. It’s commonly used at carnivals and similar functions [525.20(C)]. Festoon lighting conductors must be at least 12 AWG, unless messenger wires support them. Overhead festoon lighting conductors must be supported by messenger wire (with strain insulators) when spans exceed 40 ft. [225.6(B)].

 

Conductor size and support

 

For overhead spans up to 50 ft, the minimum conductor size for outside branch circuits is 10 AWG. For longer spans, it’s 8 AWG [225.6(A)].

 

When these spans are installed over a building, they must be securely supported by substantial structures [225.15]. Where practicable, supports must be independent of the building [230.29]. If you use a mast for support, it must have adequate mechanical strength, braces, or guy wires to withstand the strain caused by the conductors [225.17]. Don’t use trees or other vegetation for conductor support [225.26].

 

Attachments

 

The points of attachment for overhead conductors must be at least 10 ft above finished grade. Maintain the minimum conductor clearance required by 225.18, even if that means raising the points of attachment.

 

When attaching open conductors, use fittings identified for use with conductors. Alternatively, you can use noncombustible, nonabsorbent insulators securely attached to the structure. You can attach branch conductors to the service mast, but don’t attach aerial communications cables or antennas to it [810.12].

 

Vertical clearances

 

For overhead conductors of 600V or less, maintain the following clearances: [225.18]:

  • 10 ft above finished grade, sidewalks, platforms, or projections from which they might be accessible to pedestrians if circuits are 150V to ground or less. Article 225 doesn’t provide a clearance for over 150V.
  • 12 ft above residential property and driveways, and commercial areas not subject to truck traffic if circuits of 300V to ground or less. It’s 15 ft for circuits over 300V to ground.
  • 18 ft over public trafficways, parking areas subject to truck traffic, driveways on other than residential property, and other areas traversed by vehicles (e.g., those used for cultivation, grazing, or forestry.

Observe the clearance requirements in 680.8 for any conductor that runs above pools, outdoor spas, outdoor hot tubs, diving structures, observation stands, towers, or platforms.

 

Overhead clearances

 

Conductors must maintain a vertical clearance of 8 ft above the surface of a roof, for least 3 ft from the edge of the roof. Four exceptions exist, and they’re listed in 225.19(A).

 

Conductors must maintain a vertical, diagonal, and horizontal clearance of at least 3 ft from signs, chimneys, radio and television antennas, tanks, and other structures (buildings and bridges are excluded) [225.19(B)].

 

Final span clearance

 

Remember earlier we said you have to keep luminaires at least 3 ft from platforms and similar locations? The same thing applies to overhead conductors. But conductors that run above a window aren’t required to maintain the 3 ft distance.

 

Conductors must maintain a vertical clearance of at least 10 ft above platforms, projections, or surfaces from which they might be reached. This vertical clearance must be maintained for 3 ft, measured horizontally from those surfaces.

 

Don’t install conductors under an opening through which materials might pass, or where conductors will obstruct building openings [225.19(D)(3)]. Arrange raceways on exterior surfaces so they drain. In wet locations, they must be raintight [225.22].

 

Multiple structures

 

Where more than one structure is on the same property, each must be served by no more than one feeder or branch circuit [225.30]. As you might expect, the NEC provides several exceptions.

The first one is “Special Conditions.” You can provide additional circuits for

  • Fire pumps
  • Emergency systems
  • Legally required standby systems
  • Optional standby systems
  • Parallel power production systems
  • Systems designed for connection to multiple sources of supply for the purpose of enhanced reliability.

You can also, by special permission, provide additional feeders for:

  • Multiple-occupancy buildings where there’s no available space for supply equipment accessible to all occupants
  • A structure so large that two or more feeder supplies are necessary.

The three other exceptions are:

  1. The capacity requirements exceed 2,000A.
  2. Different voltages, frequencies, or uses. For example, control of outside lighting from multiple locations.
  3. Documented safe switching procedures are established and maintained for disconnection.

Disconnects

 

Provide a disconnecting means for all conductors that enter a structure [225.31]. Install it at a readily accessible location nearest the point of entrance of the conductors [225.32]. You can locate it elsewhere:

  • Where documented safe switching procedures are established and maintained. But it must be monitored by qualified persons (see Article 100).

Also:

  • A disconnecting means isn’t required within sight of poles that support luminaires.
  • The disconnecting means for a sign doesn’t need to be readily accessible if installed per the requirements for signs. Each sign must be controlled by an externally operable switch or circuit breaker that opens all ungrounded conductors to the sign. The sign disconnecting means must be within sight of the sign, or the disconnecting means must be capable of being locked in the open position [600.6(A)].

The structure disconnecting means can consist of no more than six switches (or circuit breakers) in a single enclosure, or separate enclosures for each supply permitted by 225.30. Group all disconnects in one location [225.34] and mark each one to indicate the loads served [110.22].

 

To minimize accidental interruption of the critical power systems, 225.30(A) requires the disconnecting means for a fire pump [695.4(B)(2)] or standby power [701.11(E)] to be located remotely from the normal power disconnect. First responders to a fire can shut down power to the facility without shutting off the fire pump.

 

In a multiple-occupancy building, each occupant must have access to the disconnecting means for their occupancy [225.35]. The occupant disconnect can be accessible to building management, if management provides electrical maintenance under continuous supervision.

 

You can use a snap switch (or a set of 3-way or 4-way snap switches) as the disconnecting means for garages and outbuildings on residential property, without having a “service equipment” rating.

 

Where more than one feeder supplies a structure, a permanent plaque or directory must be installed at each feeder disconnect location. It must denote all other feeders supplying that structure and the area served by each [225.37].

 

The structure disconnecting means can consist of either a manually operated switch (or circuit breaker) or a power-operated one that’s capable of being operated manually [225.38]. If you use a shunt-trip pushbutton as the means of opening a power-operated circuit breaker, the breaker is the disconnecting means and the pushbutton is not.

 

The feeder or branch-circuit disconnecting means for a structure must have an ampere rating not less than the calculated load determined per Article 220 [225.39]. But observe the following:

  • One-circuit installation. The disconnecting means must have a rating at least 15A.
  • Two-circuit installation. The feeder disconnecting means must be rated at least 30A.
  • One-family dwelling. The feeder disconnecting means must be rated at least 100A, 3-wire.

For all other installations, the feeder or branch-circuit disconnecting means must be rated at least 60A.

 

You may have noticed that Article 225 primarily concerns itself with clearances, support, and disconnects. If you address those issues before starting your outside branch circuit installations, you should have no problem complying with Article 225. Be sure to review Table 225.2 for other applicable Articles and comply accordingly.

 

Sidebar. Other Articles

 

•   Branch Circuits, Article 210

•   Class 1, Class 2, and Class 3 Remote-Control, Signaling and Power-Limited Circuits, Article 725

•   Communications Circuits, Article 800

•   Community Antenna Television and Radio Distribution Systems, Article 820

•   Conductors for General Wiring, Article 310

•   Electric Signs and Outline Lighting, Article 600

•   Feeders, Article 215

•   Floating Buildings, Article 553

•   Grounding (Earthing) and Bonding, Article 250

•   Marinas and Boatyards, Article 555

•   Radio and Television Equipment, Article 810

•   Services, Article 230

•   Solar Photovoltaic Systems, Article 690

•   Swimming Pools, Fountains, and Similar Installations, Article 680

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • Often In Pensacola, FL we would service older homes with the garage detached and to the rear of the home. We would often install or replace the circuit to the garage using this article of the code. We had to use the #10 conductors, or #8 if the distance was longer. We often used the ceramic "screw knobs" on the home and the garage, with a 'gooseneck' weather head on the cirucit feeding the garage and on the garege end. That has been some 30 years. Before PVC conduit - it was overhead or ridgid conduit underground.

    Thanks for a look into the (not so distant) past

    Lynn Adams

    Lynn Adams

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter