This article was posted 05/04/2007 and is most likely outdated.

Article 406 Receptacles, Cord Connectors, and Attachment Plugs - 406.8
 

 
Subject - Article 406 Receptacles, Cord Connectors, and Attachment Plugs - 406.8

May 4, 2007
This newsletter was sent to 25843 newsletter subscribers
 

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 406   Hi Res - Cable/DSL [20350Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
Receptacles, Cord Connectors, and Attachment Plugs (Caps)

406.8 Receptacles in Damp or Wet Locations

The word “outdoors” was deleted from this rule. The effect? All 15 and 20A 125V and 250V receptacles installed in a wet location (indoor or outdoor) must be within an enclosure that is weatherproof when an attachment plug is inserted.
(B) Receptacles in Wet Locations.
(1) 15 and 20A Receptacles. All 15 and 20A 125V and 250V receptacles installed in a wet location must be within an enclosure that is weatherproof even when an attachment plug is inserted. Figure 406-2
(2) Other Receptacles. Receptacles rated other than 15 or 20A or having a voltage rating of 208V installed in a wet location must comply with (a) or (b): Figure 406-3
(a) Wet Location Cover. A receptacle installed in a wet location, where the load isn’t attended while in use, must have an enclosure that is weatherproof with the attachment plug cap inserted or removed.
(b) Damp Location Cover. A receptacle installed in a wet location for use with portable tools can have an enclosure that is weatherproof when the attachment plug is removed.



Figure 406-2
(Click on image to enlarge)


Figure 406-3
(Click on image to enlarge)

     
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • Why would you use a "weatherproof" box rather than a "waterproof" box in a wet location?

    Charles Sanders

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter