Why are we seeing so many GFCI receptacle failures?
 

 
Subject - Why are we seeing so many GFCI receptacle failures?

March 28, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Why are we seeing so many GFCI receptacle failures?

 

 

By: Scott A. Hightower

 

Image 1I am an electrical engineer (University of Kentucky BSEE 1979) with about five years of experience working as an electrician.  I work closely with a Master Electrician with nearly 40 years of experience as an electrician and electrical contractor, another Master Electrician with approximately 30 years of experience and another electrician with approximately 20 years of experience.

 

Background: We install mostly 15A, 125V GFCI receptacles in residential and some light commercial settings, with about an equal mixture of new construction and remodeling of existing structures.

 

We have noticed what appears to be an increased failure rate for installed GFCI receptacles over the last several years.  We have not kept records of failures; therefore this problem description is mostly anecdotal.

 

The electrical contractor believes that he began seeing a noticeable increase in failures roughly five years ago.  Many of the failures are discovered by homeowners within our one year warranty.  In some cases we have replaced GFCI receptacles as many as three times within that first year.  It is not unusual for us to replace at least one before final inspection of the job.

 

In some cases, we suspect damage due to surges (recent thunderstorms before the failure is discovered) or moisture (outdoor locations).

However, this does not account for most of the failures.

 

Definition of failure: I count a failure only where the GFCI receptacle does not operate correctly after confirming that it has been properly wired.  Sometimes, of course, we find installation problems (e.g. line and load reversal or ground wire contact with load neutral), but I don't consider these to be failures so long as the GFCI receptacle operates correctly after fixing the installation problem.

 

Failures we have seen include the following: Cannot reset after tripping (most common), cannot trip with test button, cannot trip with other test, no voltage across hot and neutral outlets after reset, and voltage across hot and neutral outlets after tripping (one uncertain instance).

 

Testing GFCI receptacles: The inspectors use a pluggable test device that indicates presence of voltage, reversal of hot and neutral or missing ground or neutral.  GFCI operation is tested with a button on this device.

 

Most of us use a similar device most of the time.  The electrical contractor has always used a 60W incandescent bulb in a drop socket to test receptacles, and tests GFCI operation by attaching it to the hot outlet and ground.  The rest of us will test the same way if our receptacle tester is not readily at hand.

 

Recent extreme example: We have just finished a new church building (light commercial, all wiring in conduit--mostly MC, some PVC and EMT).  At project completion, there were 9 GFCI receptacles installed in 5 restrooms, a break area and outdoors.  We have performed 7 replacements due to failure.  In one location, the GFCI receptacle was replaced twice.  (In another location, the GFCI receptacle was also replaced twice, due to an "out of the box" failure--the first replacement never worked correctly.)  The single outdoor GFCI receptacle was installed just before final inspection, so it hasn't had time to fail.

 

The indoor GFCI receptacles are distributed between three branch circuits, two fed from a remote subpanel and the other (break area) fed from a subpanel close to the main distribution panel.  All three branch circuits are wired in MC.  GFCI receptacles have failed on all three branch circuits.

 

The break area branch circuit has two GFCI receptacles with no load side attachments and two unprotected receptacles outside the sink area.  The first GFCI receptacle has been replaced once (twice if we count the "out of box" failure.)

 

The upstairs restroom branch circuit has four GFCI receptacles, one protected receptacle attached to the third GFCI receptacle and no unprotected receptacles.  The first and last receptacles have each been replaced once.  This branch circuit was initially wired improperly: The second GFCI receptacle fed a protected receptacle, which was then connected to the third GFCI receptacle and its attached protected receptacle.  In addition, the second GFCI receptacle had reversed line and load attachments.  The reversal was eliminated by changing to a line-side connection only and another GFCI receptacle replaced its attached protected receptacle.  The last GFCI receptacle was discovered to have failed when the improper wiring was corrected.

 

The downstairs restroom branch circuit has two GFCI receptacles, with a protected receptacle attached to the second, one unprotected receptacle split off ahead of the first and one unprotected receptacle between the first and second GFCI receptacles.  This branch circuit has been in operation longer than the others.  The first GFCI receptacle has been replaced twice and the second has been replaced once.

 

Experience of others: From time to time we have asked other electricians if they have seen similar failure rates and have asked at the supply stores if they are seeing a lot of returns due to failed GFCI receptacles.  Until recently, the answer has always been "No."  This has made us wonder if we are doing something to cause the high rate of failures, or if other electricians are unaware that they can return the failed GFCI receptacles.

 

Recently I asked again at the supply house and they said yes, they were suddenly seeing a lot of returns.

 

Thoughts on possible causes: We test frequently and thoroughly, especially just before final inspection.  We are now wondering if the 60W incandescent bulb load between hot and ground could cause some failures.

 

It is not unusual for construction equipment (saws, air compressors, drills, etc.) to be plugged into whatever receptacles we happen to have powered up.  I'm wondering if this might expose the GFCI receptacles to an unusually high amount of electrical "noise."

 

Scott A. Hightower

 

NEMA GROUND FAULT PERSONNEL PROTECTION (GFCI) SECTION ACTION

 Image 2

In 1999, members of the NEMA GFCI Section received reports of non-operational Ground Fault Circuit Interrupters (GFCI) whereby, afterthe GFCI had been installed, the GFCI could not perform its intended function or later became non-operational. In response to these reports, the members of the NEMAGFCI Section, at its meeting on September 8, 1999, passed a resolution that read:

 

“NEMA 5PP Section supports the conduct of an impartial and comprehensive investigation of field performance of GFCIs. The investigation objective is to obtain statistically valid data to identify, define, and quantify long term operation of GFCIs in the installed infrastructure. For suspected field failures, both the installation and the product must be analyzed and data compiled to enable clear definition of the cause of failure (including condition of use andenvironment) and mode failure (e.g., SCR failure, test button failure) sufficient to define remedial action(s) if required”

 

The GFCI Section formed the Field Test Survey Task Force at that meeting to define the study and how it would be conducted. The study examined 2,680 GFCIs installed in 1,090 residences in ten locations within the United States. The task force completed the study and this is the report of the findings. The task force has not attempted to draw conclusions on the results of the study but rather to report the results of the findings.

 

Click here to review the GFCI Field Test Survey Report.

 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • I seem to have touched a raw nerve with this article.

    Several interesting points have been made. For some reason, I am unable to view the comments and replies on the website. Mike very kindly set me up to receive them by e-mail, but most of the short replies cannot be related to a comment by content alone.

    I will respond to one question that has been asked more than once. We use Leviton almost exclusively. In the extreme example of the church, we used Leviton 20A GFCI receptacles. At the start, they were all SmartLok, but toward the end, the replacements were all SmarkLok Pro. We rarely buy anything from the "big box" stores or through discount outlets.

    I had not considered that the devices might be counterfeit. We usually return them to our supplier, but I don't know if they ship them to the manufacturer or just dump them and apply for credit. That's an interesting question to ask the boys at the counter the next time I'm there.

    I had not really thought about high failure rates due to offshore manufacturing or early in a new design cycle. Both are quite plausible, and I do have some experience with both, from a former life. "Shrinking the die" is also plausible as a cause, although I was under the impression that it would not apply to GFCI receptacles. Perhaps the newer designs need specifically designed components, rather than off the shelf stuff. In that case, yes, the chip manufacturer will look for ways to increase yield.

    I was interested in the assertion that nothing you do on the load side of a GFCI should affect its operation. I did not see any responses to that (that I could recognize as such). I will certainly agree that is a desirable design point. But is it in fact a required design point? I understand that GFCI receptacles are not intended to act as overload interruptors, and it is also my understanding (and experience) that an overload can fry one. I think I remember that the Task Force report mentioned the delicacy of the components and their susceptibility to surges--that, too, agrees with my experience. Therefore, I have doubts about the assertion (that load side actions have no effect). Applying a 60W incandescent load between hot and ground is not a normal occurrence. I am not convinced that this method of testing has caused a lot of failures, but neither am I yet convinced that it cannot.

    I was under the impression that shorting the neutral to ground would trip the GFCI only if there was a load. I don't have an AFCI tester, so I apply a load before shorting neutral to ground. I thought that's what I would have to do for GFCI, as well.

    As a side note, I am not just testing the operation of the GFCI (or AFCI). When I test, I go through the same motions that our inspectors will go through--assuring that every receptacle is in fact protected, and not "bootlegged" off of the nearest power source. During peak periods, we often have more work than the four of us can handle, so we'll subcontract or we'll hire temporary help. These people are always fully licensed, and should not need close supervision, but we have almost always found miswirings and (rarely) outright bootleg work. Even among ourselves, misunderstandings of what has already been done or what was intended have resulted in accidental miswirings when we help each other get caught up on a job. On a few occasions, the carpenters will have to change out a stud or make other changes that affect wiring, and will "help" us by doing it themselves. And of course, there are always boxes covered by the drywallers and forgotten. For all these reasons, I am in the habit of thorough testing. I hate it when the inspector finds something I should have caught.

    I am also interested in the one comment about proper torque to the side screws. I don't much like the way GFCI receptacles force me to connect the wires. I'd really rather have plain old side screws. Many times I have had to chase down a failure that was nothing more than a wire slipped out of the clamps. Therefore, after running the screws down, I apply an extra twist to make sure it is tight. Can overtorquing damage a GFCI receptacle?

    On using GFCI breakers instead of receptacles: My understanding and experience with GFCI is that nuisance tripping increases with distance between the GFCI and the load, due to brief current imbalances induced by stray noise. I think this has been more of a problem in commercial settings, with their higher population of electronics and the longer home runs to the panels.

    Nuisance tripping due to electronic loads on the GFCI protected system itself is another can of worms that I don't want to get into right now.

    In summary, while the comments (and the volume) have been interesting, I have not yet seen anything that says that we are or are not doing anything ourselves to cause the failures. However, the trend seems to say that we are not; that the failures are common.

    Scott A. Hightower

    Scott A. Hightower