According to 645.(D)(2) Branch-circuit supply conductors installed in rigid metal conduit, PVC conduit, intermediate metal conduit, electrical metallic tubing, electrical nonmetallic tubing, metal wireway, nonmetallic wireway, surface metal raceway with metal cover, surface nonmetallic raceway, flexible metal conduit, liquidtight flexible metal conduit, liquidtight flexible nonmetallic conduit, MI cable, MC cable, or AC cable are permitted in the raised floor space.
And the branch-circuit wiring methods must be securely fastened in place in accordance with 300.11.
However, power, communications, connecting, and interconnecting cables part of listed information technology equipment aren’t required to be secured in place [645.5(E). Mike Holt
|