Conductors for General Wiring

310.15 Conductor Ampacity

Text added to clarify how each current-carrying conductor of a parallel conductor set is to be treated when applying the ampacity adjustment factors of Table 310.15(B)(2)(a). Additional text clarifies that the reduced size feeder conductors permitted in Table 310.15(B)(6) only applies for individual dwelling units of one-family, two-family and multifamily dwellings.

(B) Ampacity Table. The allowable conductor ampacities listed in Table 310.16 are based on conditions where the ambient temperature isn’t over 86°F and no more than three current-carrying conductors are bundled together. Figure 310-3

Author’s Comment: When conductors are installed in an ambient temperature other than 78–86°F, ampacities listed in Table 310.16 must be corrected in accordance with the multipliers listed in Table 310.16.

(2) Ampacity Adjustment
(a) Conductor Bundle.
Where the number of current-carrying conductors in a raceway or cable exceeds three, or where single conductors or multiconductor cables are stacked or bundled in lengths exceeding 24 in., the allowable ampacity of each conductor, as listed in Table 310.16, must be adjusted in accordance with the adjustment factors contained in Table 310.15(B)(2)(a).

Each current-carrying conductor of a paralleled set of conductors must be counted as a current-carrying conductor.
Figure 310-4

Table 310.15(B)(2)(a) Conductor Adjustment Factors for Conductors in a Raceway or Cable
Current–Carrying Ampacity Multiplier
1–3 Conductors     1.00
4–6 Conductors     0.80
7–9 Conductors     0.70, Figure 310-5
10–20 Conductors 0.50


Figure 310-3
(Click on image to enlarge)


Figure 310-4
(Click on image to enlarge)


Figure 310-5
(Click on image to enlarge)

 
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • Can Table 310.15(B)used for a sub-panel in a single family dwelling?

    Romeo Ethier

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter