Article 250 Grounding and Bonding 250.4
 

 
Subject - Article 250 Grounding and Bonding 250.4

December 22, 2006  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 250   Hi Res - Cable/DSL [19012Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
   
Grounding and Bonding

250.4 General Requirements for Grounding and Bonding

Change clarifies that swift operation of an overcurrent protection device in the presence of a ground-fault depends upon the existence of an effective ground fault current path from the point of the fault to the power-supply neutral.

The last sentence was revised to make it clear that the earth cannot be used as the effective ground-fault current path. It will not facilitate the opening of the circuit protection device from a ground fault.


(A) Solidly-Grounded Systems.
(5) Effective Ground-Fault Current Path. Electrical raceways, cables, enclosures and equipment, as well as other electrically conductive material that are “likely to become energized,” must be installed in a manner that creates a permanent, low-impedance path that facilitates the operation of the circuit overcurrent device or ground-fault detector for high-impedance grounded systems. Figure 250-3

The effective ground-fault current path must be capable of safely carrying the maximum fault current likely to be imposed on it from any point on the wiring system where a ground fault may occur to the electrical supply source neutral [110.10].


Author’s Comment: Clearing ground faults (line-to-case faults) is accomplished by bonding all metal parts of electrical equipment and conductive material likely to become energized to the power-supply grounded neutral terminal.

Author’s Comment: Another factor necessary to help ensure an effective ground-fault current path is that all circuit conductors (ungrounded, grounded and the equipment grounding (bonding) conductor) must be grouped together in the same raceway, cable, or trench [300.3(B), 300.5(I), and 300.20(A)]. Figure 250-4

The earth is not considered an effective ground-fault current path. Figure 250-5



Figure 250-3
(Click on image to enlarge)


Figure 250-4
(Click on image to enlarge)


Figure 250-5
(Click on image to enlarge)

   
 

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • I understand the importance of the wires being grouped together but in a system preexisting with no ground wire in it wouldn't an external ground wire be better than nothing? If properly installed.

    tom glastra

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter