Article 210 Branch Circuits 210.4
 

 
Subject - Article 210 Branch Circuits 210.4

October 20, 2006  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 210   Hi Res - Cable/DSL [6477Kb]
VIEWING Video FILE requires
Real Alternative Player [ FREE ]
    
Branch Circuits

210.4 Multiwire Branch Circuits

Part I. General Provisions

New FPN alerts the Code user to ensure that the continuity of the grounded neutral conductor of a multiwire circuit isn’t interrupted (open), because doing so can result in a fire and/or destruction of electrical equipment because of under- or over-voltage.
(C) Line-to-Neutral Loads. Multiwire branch circuits must supply only line-to-neutral loads.
Ex 1: A multiwire branch circuit is permitted to supply line-to-line utilization equipment, such as a range or dryer.

Ex 2: A multiwire branch circuit is permitted to supply both line-to-line and line-to-neutral loads if the circuit protection device opens all ungrounded conductors of the multiwire branch circuit simultaneously under a fault condition (multipole circuit breaker with common internal trip). Figure 210-1

FPN: See 300.13(B) for the requirements relating to the continuity of grounded neutral conductor on multiwire circuits.

CAUTION: If the continuity of the grounded neutral conductor of a multiwire circuit is interrupted (open), the resultant over- or undervoltage could cause a fire and/or destruction to electrical equipment. Figure 210-2



Figure 210-1
(Click on image to enlarge)


Figure 210-2
(Click on image to enlarge)

     

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • Resistive and capacitive loads are in relation to whether the current or voltage is leading or lagging in the phase angle. Tnis can affect the power factor and play a part in harmonic distortion. The nuetral does not care what type of load you have when it is being shared as long as the ungrounded conductors are on opposing phases.

    Benjamin Brown

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter