Article 210 Branch Circuits 210.5
 

 
Subject - Article 210 Branch Circuits 210.5

October 27, 2006  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 210   Hi Res - Cable/DSL [9415Kb]
VIEWING Video FILE requires
Real Alternative Player [ FREE ]
Branch Circuits

210.5 Identification for Branch Circuits

The requirement for branch-circuit identification was relocated from 210.4(D) to 210.5(C) and the text expanded to require circuit identification for all circuits, not just those that are multiwire.
(C) Ungrounded Conductors. Where the premises wiring system contains branch circuits supplied from more than one voltage system, each ungrounded conductor, where accessible, must be identified by system. Identification can be by color-coding, marking tape, tagging, or other means approved by the authority having jurisdiction. Such identification must be permanently posted at each branch-circuit panelboard or branch-circuit distribution equipment. Figure 210-3

Author’s Comment: Electricians often use the following color system for power and lighting conductor identification:
  • 120/240V single-phase: black, red and white
  • 120/208V three-phase: black, red, blue and white
  • 120/240V three-phase: black, orange, blue and white
  • 277/480V three-phase: brown, orange, yellow and gray, or brown, purple, yellow and gray





Figure 210-3
(Click on image to enlarge)

       

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • Time and time again we see voltages improperly stated. Please amend your documents to coincide with the NEC and IEEE stds.

    208Y/120V is 3 ph, 4 wire, 480Y/277V is 3 ph 4 wire,

    120/208Y is a 1 ph, 3 wire, open wye system.

    240/120V is a 3 ph, 4 wire high leg delta.

    B King

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter