This article was posted 09/05/2006 and is most likely outdated.

NEC Questions and Answers - August 2006
 

 
Topic - NEC Questions
Subject - NEC Questions and Answers - August 2006

September 5, 2006  

| Ask a Question |  Code Graphic Code Quiz - All New! |  Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
[ image1 Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

NEC Questions and Answers August 2006

 

By Mike Holt for EC&M Magazine

 

Q1. Can the sum of the ampere rating of circuit breakers in a panel exceed the rating of the panelboard?

A1. Yes, because each lighting and appliance branch-circuit panelboard [408.34(A)] must have overcurrent protection not greater than that of the panelboard [408.36(A)].

 

Q2. Can I use a different manufacturer’s breaker in my panel as long as it fits?

A2. Only if the circuit breaker is listed or classified to be used in the specific panelboard [110.3(B)].

 

Q3. If an outdoor generator has a disconnect, do I need an additional disconnect where the conductors enter the building?

A3. Where an outdoor-housed generator is equipped with a readily accessible disconnecting means located within sight (Article 100 - within 50 ft) of the building or structure, an additional disconnecting means isn’t required on or at the building or structure for the generator feeder conductors that serve the building or structure [700.12(B)(6), 701.11(B)(5) and 702.11].

 

Q4.  Can I use 12-3 NM cable to wire the bathroom and laundry circuits in a dwelling?

A4. Yes, however continuity of the grounded (neutral) conductor of a multiwire branch circuit must not be interrupted by the removal of a wiring device [300.13(B)]. Therefore, the grounded neutral conductors must be spliced together, and a pigtail must be provided for the wiring device.

 

Q5 How far away must a receptacle outlet be from a shower or bathtub?

Q6. Receptacles must not be installed within or directly over a bathtub or shower stall [406.8(C)], but they can be installed next to a bathtub or shower. Hydromassage bathtubs are treated like bathtubs [680.70].

 

Q6. Can Table 310.15(B)(6) (reduced size wire for dwelling unit service) be used to size the service neutral conductor for a single family dwelling?

A6. Yes this table can be used to size the grounded neutral conductor of a 3-wire single-phase 120/240V service or feeder that serves as the main power feeder, based on the feeder calculated load in accordance with 220.61.

 

Q7. Can an AFCI type receptacle be used to meet the AFCI requirements of the NEC?

A7. Yes, if the AFCI is located within 6 ft of the branch-circuit overcurrent device as measured along the branch-circuit conductors, if the circuit conductors are installed in a metal raceway or a cable with a metallic sheath [210.12(B) exception]. But no manufacture makes an AFCI receptacle…

 

Q8. Do I need to bond the metal parts of a diving board and ladder of a fiberglass swimming pool pump motor?

A8. Yes, all metal fittings within or attached to a permanently installed pool, outdoor spa, or outdoor hot tub structure, such as ladders, diving boards and handrails must be bonded together, even if the pool is of fiberglass construction [680.26(B)(3)].

 

Q9.  I have two receptacles on two different circuits in the same outlet box. Am I required to use a two pole breaker for these circuits?

A9. No. A two pole breaker or two single breakers with handle ties identified for the purpose is only required if the two circuits are on the same receptacle [210.4(B) and 210.7(B)].

 

Q10. How many 12 AWG conductors can I install in 4 x 4 x 1½” box if the box has a plaster ring listed for 3.3 cubic inches and there are no cable clamps or fixture support fittings in the enclosure.

A10. According to Table 314.16(A), the box has a capacity of 21.0 cubic inches.  Table 314.16(B) tells us that each 12 AWG conductor is considered as 2.25 cubic inches, so:

Step 1. Determine the total volume of the box assembly [314.16(A)].
Box 21 cu in. + 3.3 cu in. plaster ring = 28.3 cu in.

 

Step 2. Determine the number of 12 AWG conductors permitted in the box.

24.3 cu in. /2.25 cu in. = 10 conductors

 

[ View More Newsletters ] [ Send to a Friend ] [ Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © 2002, 2003, 2004, 2005, 2006 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

To suggest a topic or submit content for a newsletter: nlsuggest@mikeholt.com
Experiencing a Problem? Contact our Webmaster

Comments
  • Hi Mike, Just wanted to say I love these newsletters. They are very informative and timely. I enjoy reading them. I use them as study guides and references at my fingertips. Keep up the good work. Thank you.

    Michael

    Michael

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter