Grounding versus Bonding, Part 11 of 12
 

 
Topic - Grounding versus Bonding, Part 11 of 12
Subject - Pools, fountains, and similar installations

September 8, 2005 

| Ask a Question |  Code Graphic Code Quiz Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
  Web Page Version [Printer-Friendly]    
Grounding versus Bonding, Part 11 of 12

Pools, fountains, and similar installations

Mike Holt for EC&M Magazine

The bonding and grounding requirements of pools can make you feel like you're in over your head.

What comes to mind when you think of pools, spas, hot tubs, and similar installations? Most people would say fun and relaxation. But the person trying to properly ground and bond these is more likely to say confusion and frustration. Why? Because of a wrinkle to what we've covered thus far in this series. To help us iron out that wrinkle, let's recap three basic concepts:

  1. When you ground, you connect something to the earth. Think of this as earthing .
  2. When you bond, you create a conductive path between metallic objects.
  3. Bonding is the method by which you create a low-impedance path for fault current.

But with pools and other such installations, the NEC throws a new bit of lingo at us: equipotential bonding . The purpose of equipotential bonding is to bring metallic objects to the same potential. This reduces the shock hazard, which is obviously an important consideration for people immersed in a container of water.

The intention of equipotential bonding is to reduce earth voltage gradients in the area around a permanently installed pool or similar installation by the use of a common bonding grid per 680.26(B) and (C).

Equipotential bonding is not intended to provide a low-impedance ground-fault current path to the source (which would assist in clearing a ground fault) as required by 250.4(A)(3). It has nothing to do with creating a path for fault current. Therefore, the 8 AWG or larger solid copper equipotential bonding conductor required by 680.26(C) isn't required to extend to (or attach to) any panelboard, service equipment, or electrode.

In addition, to equipotential bonding is the requirement that any wiring method used for equipment associated with the pool, spa, or hot tub is to include an insulated copper equipment grounding (bonding) conductor. You must size this conductor per 250.122, but in no case can it be smaller than 12 AWG copper (Figure 680-7). Various other requirements apply, depending on the type of raceway used. These requirements all work toward providing an effective ground-fault current path.

Pool lights

We can all agree that the goal when wiring luminaires in a pool is to light up the pool, not its occupants. This is why branch-circuit conductors for an underwater luminaire must contain an insulated copper equipment grounding (bonding) conductor sized per Table 250.122. In no case can this conductor be smaller than 12 AWG (Figure 680-19).

The equipment grounding (bonding) conductor for the underwater luminaire must not be spliced [680.23(F)(2)], unless one of two conditions exists (Figure 680-20):

  1. More than one underwater luminaire is supplied by the same branch circuit. If so, the equipment grounding (bonding) conductor can terminate at a listed pool junction box that meets the requirements of 680.24(A).
  2. The equipment grounding (bonding) conductor terminates at the grounding terminal of a listed pool transformer, GFCI, clock switch, or manual snap switch that is located between the panelboard and a junction box connected to the conduit that extends directly to the underwater luminaire.

The branch-circuit conductors for the underwater luminaire must not occupy raceways, boxes, or enclosures containing other conductors on the load side of a GFCI or transformer-unless one of the following conditions exists:

  1. The other conductors are GFCI protected.
  2. The other conductors are grounding (bonding) conductors.
  3. The other conductors supply a feed-through type GFCI.
  4. The other conductors are in a panelboard.

Junction Boxes

The junction box (deck box) that connects directly to an underwater permanently installed pool, outdoor spa, or outdoor hot tub luminaire forming shell must be listed as a swimming pool junction box and equipped with threaded entries or a nonmetallic hub [680.24] (Figure 680-21). It also must be constructed of copper, brass, or corrosion-resistant material approved by the authority having jurisdiction. You must provide electrical continuity between all metal conduit and the grounding (bonding) terminals within the junction box.

Also, you must ensure the junction box has at least one more grounding (bonding) terminal than the number of conduit entries [680.24(D)]. Typically, there are four grounding (bonding) terminals in the junction box and three conduit entries. Finally, you must provide a strain relief at the enclosure where you terminate the flexible cord of an underwater luminaire [680.24(E)].

Bonding Metal Parts to the Equipotential Bonding Grid

Ensure the following parts of a permanently installed pool, outdoor spa, or outdoor hot tub are bonded together and to the equipotential bonding grid.

(1) All metallic parts of reinforcing metal not encapsulated with a nonconductive compound. The usual steel tie-wires that secure rebar together are considered suitable for bonding the reinforcing steel together (Figure 680-22). Where conductive reinforcing steel of the permanently installed pool, outdoor spa, or outdoor hot tub shell and deck is not available, provide-per 680.26(C)-for an alternative means to eliminate voltage gradients that would otherwise be provided by unencapsulated, bonded reinforcing steel.

(2) All metal forming shells for underwater wet-niche luminaire.

(3) Metal fittings within or attached to the permanently installed pool, outdoor spa, or outdoor hot tub structure, such as ladders and handrails.

(4) Metal parts of electrical equipment associated with the circulating system (water heaters and pump motors) and metal parts of equipment associated with pool covers.

(5) Metal cables, metal raceways, metal piping, and all fixed metal parts of electrical equipment-except those separated from the pool by a permanent barrier located within:

  • 5 ft horizontally of the inside walls of the permanently installed pool, outdoor spa, or outdoor hot tub.
  • 12 ft above the maximum water level of the permanently installed pool, outdoor spa, or outdoor hot tub; or any observation stands, towers, platforms, or diving structures.

The Equipotential Bonding Grid

All metal parts specified in 680.26(B) must be bonded to an equipotential bonding grid with a solid copper conductor not smaller than 8 AWG. The termination of the bonding conductor must be made by exothermic welding, listed pressure connectors, or listed clamps that are labeled as suitable for the purpose. An equipotential bonding grid must extend under paved walking surfaces for 3 ft horizontally from the water.

The equipotential bonding grid must be formed from either or both of:

(1) The structural reinforcing steel of a concrete permanently installed pool, outdoor spa, or outdoor hot tub, tied together by the usual steel tie wires.

(2) The metal walls of a permanently installed pool, outdoor spa, or outdoor hot tub.

But, what if neither of these is available? Where structural reinforcing steel or the walls of bolted or welded metal permanently installed pool, outdoor spa, or outdoor hot tub structures are not available, you must construct an equipotential bonding grid as follows:

(a) The equipotential grid can be constructed with 8 AWG bare solid copper conductors that are bonded to each other at all points of crossing by exothermic welding, listed pressure connectors of the set screw or compression type, listed clamps, or other listed fittings [250.8].

(b) The equipotential bonding grid must cover the contour of the permanently installed pool, outdoor spa, or outdoor hot tub, and deck extending 3 ft horizontally from the water. The equipotential bonding grid must be arranged in a 1 ft x 1 ft network of 8 AWG conductors, with a tolerance of 4 in.

All equipotential bonding terminations must be by exothermic welding, listed pressure connectors of the set screw or compression type, listed clamps, or other listed fittings [250.8].

Let's go back for a moment to a frequently misapplied term: grounding. One of the myths about grounding (earthing) is that it reduces shock hazards by bringing everything to ground potential. Because the earth is not of uniform conductivity, that can hardly be the case. Another myth is that grounding (earthing) provides a common reference point. This, also, defies logic.

What about that common reference? If ground (earth) is not it, what is? You can establish a common reference by constructing a bonding grid, not an earthing connection . Connect your bonding path to the grounding grid, and all of the objects are at an equal potential.

When you have equal potential, then by definition you do not have a voltage difference. Without a voltage difference, there can be no current flow. Thus, you use an equipotential bonding system-not a grounding system-to reduce shock hazards.

This is the final article in this series. If you've read them all, you now understand the difference between grounding and bonding-and the purpose of one vs. the other. By not confusing the two, you can eliminate some common causes of unsafe installations.

[ View More Newsletters ] [ Please Add Your Comments ]
2 0 0 5   G r o u n d i n g   v e r s u s   B o n d i n g   S e m i n a r s
 TOPIC  LOCATION  SPONSOR  INFORMATION
October 11st thru
October 12nd
Mike Holt, EC&M & Leviton: Grounding versus Bonding
Boston, MA
Boston Convention & Exhibition Center
415 Summer Street
(617) 954-2000
Mike Holt Enterprises, EC&M Magazine & Leviton
Email Donna Brown
Phone: (866) 632-2633
[ Download Brochure ]
[ Preview Video ] Download Quicktime Player [FREE]
[ Register Both Days ]
October 17th thru
October 18th
Mike Holt, EC&M & Leviton: Grounding versus Bonding
Philadelphia, PA
Pennsylvania Convention Center
1101 Arch St.
(215) 418-4700
Mike Holt Enterprises, EC&M magazine & Leviton
Email Donna Brown
Phone: (866) 632-2633
[ Download Brochure ]
[ Preview Video ] Download Quicktime Player [FREE]
[ Register Both Days ]
November 9th thru
November 10th
Mike Holt, EC&M & Leviton: Grounding versus Bonding
Seattle, WA
Meydenbauer Center
11100 NE 6th Street
(425) 637-1020
Mike Holt Enterprises, EC&M magazine & Leviton
Email Donna Brown
Phone: (866) 632-2633
[ Download Brochure ]
[ Preview Video ] Download Quicktime Player [FREE]
[ Register Both Days ]
November 16th thru
November 17th
Mike Holt, EC&M & Leviton: Grounding versus Bonding
Chicago, IL
Midwest Conference Center
401 W Lake St
Northlake, IL
(708) 409-2828
Outside Chicago - 7 Miles from Ohare

Mike Holt Enterprises, EC&M magazine & Leviton
Email Donna Brown
Phone: (866) 632-2633
[ Download Brochure ]
[ Preview Video ] Download Quicktime Player [FREE]
[ Register Both Days ]
[ Please Add Your Comments ] [ View More Newsletters ]

F o r w a r d   t h i s   N e w s l e t t e r   t o   a   F r i e n d !
Do you have a friend, relative, or colleague who you think would be interested in receiving this free newsletter? If so, we encourage you to forward this message along to them. If you received this email from someone else, and wish to receive your own free issues of our newsletter, sign up today!

C o n t a c t    I n f o r m a t i o n
   
 

Copyright © 2002, 2003, 2004, 2005 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Comments
  • Mike,

    In Canada (Ontario)the ESA requires (not each municipality) that the water pipes for the pools are bonded even if they are PVC. So the common practice is to insert a metallic tube inside the PVC and bond the metalic tube That way the water is bonded even if the level of the water inside the pool is insignificantly low. Is there a practice similar like this one in USA.

    Thanks, Filip



Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter