Mike Holt Enterprises Electrical News Source

Understanding Raceways


Figure 01


For EC&M Magazine

By Mike Holt, NEC®Consultant

Looking at four types of raceway helps you understand raceways in general.

Chapter 3 of the NEC contains a series of articles (342 - 376) that provide raceway requirements. What is raceway? "An enclosed channel designed expressly for holding wires, cables, or busbars, with additional functions as permitted in this Code [100]."

Common rules
These rules apply to all types of raceway:

  • The total amount of bends (including offsets) between pull points can't exceed 360 degrees.
  • Remove burrs and rough edges after cutting.
  • Install as a complete system.
  • Securely fasten and support.
  • Metallic raceway can serve as an equipment grounding conductor (EGC) providing it meets the requirements of 250.118, but nonmetallic raceway must include a separate EGC (wire type) [362.60] when an EGC is required.
  • Conductors 4 AWG and larger entering an enclosure must be protected from abrasion, during and after installation, by a fitting that provides a smooth, rounded, insulating surface (e.g., insulating bushing), unless the design of the box, fitting, or enclosure provides equivalent protection per 300.4(G). Figure 01

What follows is an overview of two types of tubing, then two types of conduit.

Two tubing types
EMT is lightweight and relatively easy to bend and cut. Because it isn't threaded, all connectors and couplings are threadless and provide quick, easy, and inexpensive installation when compared to conduit.

Electrical nonmetallic tubing (ENT) is a pliable, corrugated, circular raceway made of PVC. It's available in many colors. It's sold in fixed lengths and on reels.

EMT
You can use EMT exposed or concealed in [358.10(A)]:

  • Concrete in direct contact with the earth per 358.10(B).
  • Dry, damp, or wet locations.
  • Any hazardous (classified) location as permitted by other articles in this Code.

You can use galvanized steel and stainless steel EMT, elbows, and fittings in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences if protected by corrosion protection and approved as suitable for the condition [300.6(A)].

You can't use EMT [358.12]:

  1. Where subject to severe physical damage.
  2. To support luminaires or other equipment (like boxes), except conduit bodies no larger than the largest trade size of the tubing the raceway can support.

Couplings and connectors
Couplings and connectors must be made-up tight to maintain an effective ground-fault current path to safely conduct fault current per 250.4(A)(5), 250.96(A), and 300.10 [358.42].

If buried in masonry or concrete, EMT fittings must be of the concrete-tight type. If installed in wet locations, fittings must be listed for use in wet locations and prevent moisture or water from entering or accumulating within the enclosure per 314.15.

ENT
You can use ENT [362.10]:

  1. In buildings not exceeding three floors:
    a. Exposed, where not prohibited by 362.12.
    b. Concealed within walls, floors, and ceilings.
  2. In buildings exceeding three floors: concealed in walls, floors, or ceilings that provide a thermal barrier having a 15-minute finish rating, as identified in listings of fire-rated assemblies. If a fire sprinkler system is on all floors, per NFPA 13, you can use ENT in buildings of any height.
  3. In severe corrosive and chemical locations, when identified for this use.
  4. In dry and damp concealed locations, if not prohibited by 362.12.
  5. Above a suspended ceiling, if that ceiling provides a thermal barrier with a 15-minute finish rating, as identified in listings of fire-rated assemblies. If a fire sprinkler system is on all floors, per NFPA 13, you can use ENT above a suspended ceiling that doesn't have a 15-minute finish rated thermal barrier.
  6. Where encased or embedded in a concrete slab, if using fittings identified for the purpose.
  7. In wet locations indoors, or in a concrete slab on or below grade, with fittings listed for the purpose.

You can't use ENT [362.12]:

  1. In any hazardous location, except as permitted by 504.20 and 505.15(A)(1).
  2. For the support of luminaires or equipment. See 314.23.
  3. If the ambient temperature exceeds 50 DegrC (122 DegrF).
  4. For direct earth burial. But ENT can be encased in concrete [362.10(6)].
  5. Exposed in buildings over three floors, except as permitted by 362.10(1) and (5) Ex.
  6. In assembly occupancies or theaters, except as permitted by 518.4 and 520.5.
  7. Exposed to the direct rays of the sun for an extended period, unless listed as sunlight resistant.
  8. If subject to physical damage.

And you can't use ENT in ducts, plenum spaces [300.22(C)], or patient care space circuits in health care facilities [517.13(A)].

Joints
Make joints (e.g., couplings and connectors) in a manner approved by the Authority Having Jurisdiction (AHJ) [362.48]. Follow the manufacturers' instructions for the raceway, fittings, and glue.

Compare these conduits
Rigid metal conduit (RMC) is a standard choice for protection from physical impact and difficult environments.

Rigid PVC conduit provides many of the advantages of RMC, while allowing installation in areas that are wet or corrosive. It's inexpensive, easily installed, lightweight, easily cut and glued together, and relatively strong. However, conduits manufactured from PVC are brittle when cold, and they sag when hot. It's commonly used underground because of its low cost, ease of installation, and resistance to corrosion and decay.

RMC
You can use:

  • Galvanized steel and stainless steel RMC in all atmospheric conditions and occupancies [344.10(A)(1)].
  • Red brass RMC for direct burial and swimming pool applications [344.10(A)(2)].
  • Aluminum RMC if approved for the environment [344.10(A)(3)].

In corrosive environments [344.10(B)]:

  1. Galvanized steel, stainless steel, and red brass RMC fittings, elbows, and couplings can be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences if approved for the condition.
  2. Aluminum RMC must have supplementary corrosion protection approved by the AHJ if encased in concrete or in direct contact with the earth.

In wet locations, support fittings such as screws and straps must be made of corrosion resistant material or protected by corrosion resistant coatings per 300.6 [344.10(D)].

Thermal expansion
RMC must have expansion fittings if it's necessary to compensate for thermal expansion and contraction [300.7(B)]. Determine the expansion characteristics for:

  • Steel raceways by multiplying the values from Table 352.44 by 0.20.
  • Aluminum raceways by multiplying the values from Table 352.44 by 0.40 [300.7 Note].

Couplings and connectors
Couplings and connectors must be made-up tight to maintain an effective ground-fault current path to safely conduct fault current per 250.4(A)(5), 250.96(A), and 300.10. When installed in a wet location, they must comply with 314.15. [344.42(A)].

Threadless couplings and connectors cannot be used on threaded conduit, unless listed for the purpose.

PVC conduit
You can conceal PVC conduit within walls, floors, or ceilings, directly buried or embedded in concrete, in buildings of any height [352.10(A)].

You can use PVC conduit in:

  • Areas subject to severe corrosion for which the material is specifically approved by the AHJ [352.10(B)].
  • Wet or outdoor locations. The support fittings must be made of corrosion-resistant materials, or must be protected with a corrosion-resistant coating, per 300.6(A).
  • Dry and damp locations, except where limited in 352.12.
  • Exposed locations where not subject to physical damage. If exposed to physical damage, schedule 80 PVC is identified for the application.
  • Underground installations, but it must comply with the burial requirements of 300.5.

PVC conduit can support nonmetallic conduit bodies that aren't larger than the largest trade size of an entering raceway. These conduit bodies can't support luminaires or other equipment, and cannot contain devices other than splicing devices permitted by 110.14(B) and 314.16(C)(2).

You can't use PVC conduit [352.12]:

  • In hazardous locations except as permitted by 501.10(A)(1)(a) Ex, 503.10(A), 504.20, 514.8 Ex 2, and 515.8.
  • In Class I, Division 2 locations, except as permitted in 501.10(B)(7).
  • For the support of luminaires or other equipment not described in 352.10(H).

Expansion fittings
If installing PVC conduit in a straight run between securely mounted items (e.g, boxes) provide expansion fittings if the expansion or contraction length change (per Table 352.44) is expected to be ΒΌ in. or greater [352.44].

When determining the number and setting of expansion fittings, read the manufacturer's documentation.

Raceway expertise
Chapter 3 provides the requirements for many different types of raceways, wireways, and cable systems. Selecting the right one for a given application makes a big difference in project cost, but also in system performance, safety, and reliability.

It's worth setting aside some time to compare some of these to learn the specific ways in which they differ.

Post a Comment View Comments Subscribe Unsubscribe

Exam Preparation | Continuing Education | Code Products | more..
888.NEC.CODE (632.2633) www.MikeHolt.com
Mike Holt Enterprises, 3604 Parkway Boulevard, Ste 3, Leesburg, FL 34748
"... as for me and my house, we will serve the Lord" [Joshua 24:15]

Comments
  • I really appreciate the network and I will continue to build and mastermind with the organization.Thank you all fellow tradesmen for your skills knowledge and expertise.

    William Lamey  December 8 2017, 6:39 am EST

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter