Grounding vs Bonding: 250.122 Sizing Equipment Grounding (Bonding) Conductor
 

 
Subject - Grounding vs Bonding: 250.122 Sizing Equipment Grounding (Bonding) Conductor

July 14, 2006  

| Ask a Question |  Code Graphic Code Quiz - All New! |  Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
[ image1 Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    
PART VI.   Hi Res - Cable/DSL [2990Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]

Sections

250.122 Sizing Equipment Grounding (Bonding) Conductor.

(A) General. The equipment grounding (bonding) conductor must be sized in accordance with Table 250.122, based on the ampere rating of the circuit-protection device, but in no case is it required to be larger than the circuit conductors. Figure 250–169

Author’s Comment: Equipment grounding (bonding) conductors must be capable of safely conducting any ground-fault current likely to be imposed on them [110.10]. If the equipment grounding (bonding) conductor isn’t sized to withstand the ground-fault current, the conductor may burn clear before the protective device responds.

Table 250.122—Minimum Size Equipment Grounding (Bonding) Conductor

Protection Rating.......CopperConductor
15A..........................14 AWG
20A...........................12 AWG
30—60A..................10 AWG
70—100A..................8 AWG
110—200A................6 AWG
225—300A................4 AWG
350—400A................3 AWG
450—500A................2 AWG
600A...........................1 AWG
700—800A.............1/0 AWG
1,000A.....................2/0 AWG
1,200A.....................3/0 AWG

imageSend to a Friend


Figure 250–169
(Click on image to enlarge)

       
[ View More Newsletters ] [ Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ]

F o r w a r d   t h i s   N e w s l e t t e r   t o   a   F r i e n d !
Do you have a friend, relative, or colleague who you think would be interested in receiving this free newsletter? If so, we encourage you to forward this message along to them. If you received this email from someone else, and wish to receive your own free issues of our newsletter, sign up today!

C o n t a c t    I n f o r m a t i o n
 

Copyright © 2002, 2003, 2004, 2005, 2006 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Comments
  • Please stop sending me comments. If not possible then please unsubscribe me. Thank you.

    Siddique Patel
  • Reply from: Tara Moffitt   
    You will no longer be notified when comments are posted to this newsletter. You can select: Stop notifying me when comments are posted to this newsletter at the bottom of each newsletter by simply entering in your e-mail address and clicking "Stop Notifying me". That is what I did for you so this will be the last e-mail you receive about this newsletter. I did not unsubscribe you from receiving our newsletters altogether. If you wish to do so you can click here: http://www.mikeholt.com/newslettersRegister.php?action=modify&email= This option is also always included in the header of all of our newsletters. You should not have been receiving comments to this newsletter unless you at some point elected to: "notify me when comments are posted".


Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter