By Mike Holt for
EC&M Magazine
Here's the follow up
to yesterday's newsletter. This includes all of the answers to the questions
sent, so you can see how you did.
Note: These questions are based on the 2014 NEC®.
Any underlined
text indicates a
change to the Code rule for the 2014 NEC.
Q1. What are the grounding and bonding
requirements for Class I locations?
A1. Because of
the explosive conditions associated with electrical installations in hazardous
(classified) locations [500.5], electrical continuity of metal parts of
equipment and raceways must be ensured regardless of the voltage of the
circuit.
(A)
Bonding. Locknuts aren't suitable for bonding purposes in hazardous
(classified) locations, therefore bonding jumpers or other approved means of
bonding must be used. Such means of bonding apply to all intervening raceways,
fittings, boxes, enclosures, and so forth between Class I locations and service
equipment [501.30].
Author's
Comment:
Regardless of the circuit voltage, electrical continuity
of metal parts of equipment and raceways in hazardous (classified) locations
must be ensured by bonding-type locknuts, bushings,
wedges, or bushings with bonding jumpers [250.92(B)(4)]; whether or not
equipment grounding conductors of the wire type are installed in the raceway
[250.100].
A separate equipment grounding conductor
isnt required if a metal raceway is used for equipment grounding. Threaded
couplings and hubs made up wrenchtight provide a
suitable low impedance path [250.100].
(B)
BondingFlexible Raceway. Flexible metal conduit and liquidtight
flexible metal conduit must have an equipment bonding jumper of the wire type
installed in accordance with 250.102.
Author's
Comment:
Bonding jumpers are sized in accordance with Table
250.122, based on the rating of the overcurrent device [250.102(D)], and where
installed outside of a raceway, the length of bonding jumpers must not exceed 6
ft and they must be routed with the raceway
[250.102(E)(2)].
Q2. What does the Code define as an
Emergency System?
A2.
Emergency Systems. Emergency power systems are those systems legally required
and classed as emergency by a governmental agency having jurisdiction. These
systems are intended to automatically supply illumination and/or power essential
for safety to human life [700.2].
Note:
Emergency power systems may also provide power to maintain life, fire detection
and alarm systems, elevators, fire pumps, public safety communications systems,
industrial processes where current interruption would produce serious life
safety or health hazards, and similar functions.
Q3. What are the Code requirements for
transfer equipment of Emergency Systems?
A3.
Emergency System Capacity [700.4]
(A) Capacity and Rating. An emergency power
system must have adequate capacity to carry all emergency loads expected to
operate simultaneously.
(B)
Load Shedding. If an alternate power supply has adequate capacity, its
permitted to supply emergency loads [Article 700], legally required standby
loads [Article 701], and optional standby system loads [Article 702]. If the
alternate power supply doesnt have adequate capacity to carry the entire load,
it must have automatic selective load pickup and load shedding to ensure
adequate power in the following order of priority:
(1) The emergency circuits,
(2) The legally required standby circuits, and
(3) The optional standby circuits.
A temporary
alternate source of power must be available whenever the emergency generator is
out of service for more than a few hours for maintenance or repair.
Transfer
Equipment [700.5]
(A) General. Transfer equipment must be
automatic, identified for emergency use, and approved by the authority having
jurisdiction.
(C)
Automatic Transfer Switches. Automatic transfer switches must be electrically
operated, mechanically held, and listed for emergency power system use.
(D)
Use. Transfer equipment must supply only emergency loads.
Author's
Comment:
Multiple transfer switches are required
where a single generator is used to supply both emergency loads and other
loads.
Q4. What locations are acceptable for
the installation of overcurrent devices according to the NEC?
A4. Location of Overcurrent
Devices [240.24]
(A) Readily
Accessible. Circuit breakers and fuses must be readily accessible, and they
must be installed so the center of the grip of the operating handle of the fuse
switch or circuit breaker, when in its highest position, isnt more than 6 ft 7 in. above the floor or working platform, unless the
installation is for:
(1) Busways, as provided in 368.17(C).
(2) Supplementary overcurrent devices arent
required to be readily accessible [240.10].
(3) For overcurrent devices, as described in 225.40
and 230.92.
(4) Overcurrent devices located next to equipment
can be mounted above 6 ft 7 in., if accessible by
portable means [404.8(A) Ex 2].
(C) Not Exposed to Physical Damage. Overcurrent devices
must not be exposed to physical damage.
Note: Electrical equipment must be suitable for the
environment, and consideration must be given to the presence of corrosive
gases, fumes, vapors, liquids, or chemicals that have a deteriorating effect on
conductors or equipment [110.11].
(D) Not in Vicinity
of Easily Ignitible Material. Overcurrent devices
must not be located near easily ignitible material,
such as in clothes closets.
(E) Not in
Bathrooms. Overcurrent devices arent permitted to be located in the bathrooms
of dwelling units, dormitories, or guest rooms or guest suites of hotels or
motels.
Author's Comment:
The service
disconnecting means must not be located in a bathroom, even in commercial or
industrial facilities [230.70(A)(2)].
(F) Over Steps.
Overcurrent devices must not be located over the steps of a stairway.
Authors Comment:
Clearly, its
difficult for electricians to safely work on electrical equipment thats
located on uneven surfaces such as over stairways.
Q5. What are the Code rules for sizing
transformer secondary conductors?
A5. (C) Transformer
Secondary Conductors. A set of conductors supplying single or separate loads is
permitted to be connected to a transformer secondary without overcurrent
protection in accordance with 240.21(C)(1) through
(6).
The permission of the next size up protection rule
when the conductor ampacity doesnt correspond with the standard size
overcurrent protection device of 240.4(B) doesnt apply to transformer
secondary conductors.
(1) Protection by
Primary Overcurrent Device. The primary overcurrent device sized in accordance
with 450.3(B) is considered suitable to protect the secondary conductors of a
2-wire (single-voltage) system, provided the primary overcurrent device doesnt
exceed the value determined by multiplying the secondary conductor ampacity by
the secondary-to-primary transformer voltage ratio.
Question: Whats the minimum size secondary conductor
required for a 2-wire, 480V to 120V transformer rated 1.50 kVA with 60ºC
terminals?
(a) 16 AWG (b) 14 AWG (c)
12 AWG (d) 10 AWG
Answer: (c) 12 AWG
Primary Current = VA/E
VA = 1,500 VA
E = 480V
Primary Current = 1,500 VA/480V
Primary Current = 3.13A
Primary Protection [450.3(B)] = 3.13A x 1.67
Primary Protection [450.3(B)] = 5.22A or 5A Fuse
Secondary Current = 1,500 VA/120V
Secondary Current = 12.50A
Secondary Conductor = 12 AWG, rated 20A at 60ºC,
[Table 310.15(B)(16)]
The 5A primary overcurrent device can be used to protect
12 AWG secondary conductors because it doesnt exceed the value determined by
multiplying the secondary conductor ampacity by the secondary-to-primary
transformer voltage ratio.
20A secondary conductor ampacity x 120V/480V ratio = 5A
which is equal to or less than the primary protection
(2) 10 Ft Secondary Conductors. Secondary conductors can
be run up to 10 ft without overcurrent protection if
installed as follows:
(1) The ampacity of the secondary conductor must
not be less than:
a. The calculated load in accordance with Article
220, and
b. The rating of the overcurrent device at the
termination of the secondary conductors
Ex: Listed equipment, such as a surge protection device,
can have their conductors sized in accordance with the manufacturers
instructions.
(2) The secondary conductors
must not extend beyond the switchboard, switchgear,
panelboard, disconnecting means, or control devices they supply.
(3) The secondary conductors are enclosed in a
raceway.
(4) Not less than 10 percent of the rating of the
overcurrent device protecting the primary of the transformer, multiplied by the
primary-
to-secondary transformer voltage
ratio.
(4) Outside Secondary Conductors of Unlimited Length.
Outside secondary conductors can be of unlimited length, without overcurrent
protection at the point they receive their supply, if theyre installed as
follows:
(1) The conductors are suitably protected from
physical damage in a raceway or manner approved by the authority having
jurisdiction.
(2) The conductors must terminate at a single
circuit breaker or a single set of fuses that limit the load to the ampacity of
the conductors.
(3) The overcurrent
device for the ungrounded conductors is an integral part of a disconnecting
means or its located immediately adjacent thereto.
(4) The disconnecting means is located at a readily
accessible location that complies with one of the following:
a. Outside of a building.
b. Inside, nearest the point of entrance of the
conductors.
c. If installed in accordance with 230.6, nearest
the point of entrance of the conductors.
(5) Secondary Conductors from a Feeder Tapped
Transformer. Transformer secondary conductors must be installed in accordance
with 240.21(B)(3).
(6) 25-Foot Secondary Conductor. Secondary conductors
can be run up to 25 ft without overcurrent protection
if they comply with all of the following:
(1) The secondary conductors have an ampacity not
less than the value of the primary-to-secondary voltage ratio multiplied by
one-third of the rating of the overcurrent device that protects the primary of
the transformer.
(2) Secondary conductors terminate in a single
circuit breaker or set of fuses rated no more than the tap conductor ampacity
in accordance with 310.15 [Table 310.15(B)(16)].
(3) The secondary conductors are protected from
physical damage by being enclosed in a manner approved by the authority having
jurisdiction, such as within a raceway.
(D) Service Conductors. Service conductors must be
protected against overload in accordance with 230.90 and 91.
(H) Battery Conductors.
Overcurrent protection is installed as close as practicable to the storage
battery terminals.