By Mike Holt for EC&M Magazine
Here's the follow up to yesterday's newsletter. This includes all of the answers to the questions sent, so you can see how you did.
Note: These questions are based on the 2014 NEC®. Any underlined text indicates a change to the Code rule for the 2014 NEC®.
Q1. What are the NEC requirements for sizing
raceways?
A1. Raceways must be large enough to permit the installation and removal
of conductors without damaging the conductor’s insulation [300.17]
Example
1: When all conductors in a raceway
are the same size and of the same insulation type, the number of conductors
permitted can be determined by Annex C.
Question: How many 12 THHN conductors can be installed in trade size
¾ electrical metallic tubing?
(a) 12 (b) 13 c) 14 (d)
16
Answer: (d) 16 conductors [Annex
C, Table C1]
Example 2: When different size conductors are installed in a raceway, conductor fill
is limited to the percentages in Table 1 of Chapter 9.
Table 1, Chapter 9
|
Number
|
Percent Fill
|
1 Conductor
|
53%
|
2 Conductors
|
31%
|
3 or more
|
40%
|
Author's Comment: The above percentages are based
on conditions where the length of the conductor and number of raceway bends are
within reasonable limits [Chapter 9, Table 1, Note 1].
Step 1: When sizing a raceway, first
determine the total area of conductors (Chapter 9, Table 5 for insulated
conductors and Chapter 9, Table 8 for bare conductors).
Step 2: Select
the raceway from Chapter 9, Table 4, in accordance with the percent fill listed
in Chapter 9, Table 1.
Question: What trade size Schedule 40 PVC conduit is required for the following
conductors?
3—500 THHN
1—250 THHN
1—3 THHN
(a) 2 (b) 3 (c)
4 (d)
6
Answer: (b) 3
Step 1: Determine the total area of
conductors [Chapter 9, Table 5]:
500 THHN 0.7073
x 3 = 2.1219 in.2
250 THHN 0.3970
x 1 = 0.3970 in.2
3 THHN 0.0973
x 1 = + 0.0973 in.2
Total Area = 2.6162 in.2
Step 2: Select the raceway at 40
percent fill [Chapter 9, Table 4]:
Trade size 3 Schedule 40 PVC =
2.907 sq in. of conductor fill at 40%.
Q2. What are the NEC requirements for sizing boxes
for conductor fill?
A2. Boxes containing 6 AWG and smaller conductors must be sized in an
approved manner to provide free space for all conductors, devices, and
fittings. In no case can the volume of the box, as calculated in 314.16(A), be
less than the volume requirement as calculated in 314.16(B) [314.16].
Conduit bodies must be sized in accordance with 314.16(C).
Author’s Comment:
The
requirements for sizing boxes and conduit bodies containing conductors 4 AWG
and larger are contained in 314.28. The requirements for sizing handhole
enclosures are contained in 314.30(A).
(A) Box Volume Calculations. The volume of a box includes the total
volume of its assembled parts, including plaster rings, extension rings, and
domed covers that are either marked with their volume in cubic inches (cu in.),
or are made from boxes listed in Table 314.16(A).
(B) Box Fill Calculations. The calculated conductor volume determined by
314.16(B)(1) through (5) and Table 314.16(B) are added
together to determine the total volume of the conductors, devices, and
fittings. Raceway and cable fittings, including locknuts and bushings,
aren’t counted for box fill calculations.
Table 314.16(B) Volume Allowance Required per Conductor
|
Conductor AWG
|
Volume cu
in.
|
18
|
1.50
|
16
|
1.75
|
14
|
2.00
|
12
|
2.25
|
10
|
2.50
|
8
|
3.00
|
6
|
5.00
|
(1) Conductor Volume. Each unbroken conductor that
runs through a box, and each conductor that terminates in a box, is counted as
a single conductor volume in accordance with Table 314.16(B).
Each loop or coil of unbroken conductor having a length of at least twice
the minimum length required for free conductors in 300.14 must be counted as
two conductor volumes. Conductors that originate and terminate within the box,
such as pigtails, aren’t counted at all.
Author’s Comment:
According to
300.14, at least 6 in. of free conductor, measured from the point in the box
where the conductors enter the enclosure, must be left at each outlet,
junction, and switch point for splices or terminations of luminaires or
devices.
Ex: Equipment grounding conductors, and up to four 16 AWG and smaller
fixture wires, can be omitted from box fill calculations if they enter the box
from a domed luminaire or similar canopy, such as a ceiling paddle fan canopy.
(2) Cable Clamp Volume. One or more internal cable clamps
count as a single conductor volume in accordance with Table 314.16(B), based on
the largest conductor that enters the box. Cable connectors that have their
clamping mechanism outside of the box aren’t counted.
(3) Support Fitting Volume. Each luminaire stud or luminaire
hickey counts as a single conductor volume in accordance with Table 314.16(B),
based on the largest conductor that enters the box.
Author’s Comment:
Luminaire stems
don’t need to be counted as a conductor volume.
(4) Device Yoke Volume. Each single-gang device yoke
(regardless of the ampere rating of the device) counts as two conductor
volumes, based on the largest conductor that terminates on the device in
accordance with Table 314.16(B).
Each multigang-device yoke counts as two conductor volumes for each gang,
based on the largest conductor that terminates on the device in accordance with
Table 314.16(B).
(5) Equipment Grounding Conductor
Volume. All
equipment grounding conductors in a box count as a single conductor volume in
accordance with Table 314.16(B), based on the largest equipment grounding
conductor that enters the box. Insulated equipment grounding conductors for
receptacles having insulated grounding terminals (isolated ground receptacles)
[250.146(D)], count as a single conductor volume in accordance with Table
314.16(B).
Author’s Comment:
Conductor
insulation isn’t a factor that’s considered when determining box
volume calculations.
Question: How many 14 AWG conductors can be
pulled through a 4 in. square x 2½ in. deep box with a plaster ring with
a marking of 3.60 cu in.? The box contains two receptacles, five 12 AWG
conductors, and two 12 AWG equipment grounding conductors.
(a) 3 (b) 5 (c)
7 (d)
9
Answer: (b) 5
Step 1: Determine the volume of the
box assembly [314.16(A)]:
Box 30.30 cu in. + 3.60 cu in.
plaster ring = 33.90 cu in.
A 4 x 4 x 21⁄8 in. box has an interior volume is 30.30 cu in., as listed in
Table 314.16(A).
Author's Comment: The gross volume
of a box base on Table 314.16(A) dimension (4 in. x 4 in. x 21⁄8 in. = 34 cu in.) doesn't take into account the actual volume of
the material used to make the box. This why the interior volumes on this table
are smaller than the overall volumes.
Step 2: Determine the volume of the
devices and conductors in the box:
Two—receptacles 4—12
AWG
Five—12 AWG 5—12
AWG
Two—12 AWG Grounds 1—12
AWG
Total 10—12 AWG x 2.25 cu
in. = 22.50 cu in.
Step 3: Determine the remaining
volume permitted for the 14 AWG conductors:
33.90 cu in. – 22.50 cu in.
= 11.40 cu in.
Step 4: Determine the number of 14
AWG conductors permitted in the remaining volume:
14 AWG = 2.00 cu in. each [Table
314.16(B)]
11.40 cu in./2.00
cu in. = 5 conductors
Q3. What are the Code’s installation
requirements for raceway seals in Class I locations?
A3. Raceway and
cable seals must comply with 501.15.
501.15 Note
1: Raceway and cable seals must be installed to:
• Minimize the passage of gases and vapors from one
portion of electrical equipment to another through the raceway or cable.
• Minimize the passage of flames from one portion of
electrical equipment to another through the raceway or cable.
• Limit internal explosions to within the explosionproof
enclosure.
(A) Raceway Seal—Class I,
Division 1. In Class I, Division 1 locations, raceway seals must be located as
follows:
(1) Entering Enclosures. A raceway
seal is required in each raceway that enters an explosionproof enclosure if
either (1) or (2) apply:
(1) A
raceway seal fitting must be installed in each raceway that enters an
explosionproof enclosure that contains make-and-break contacts. A seal must also be provided where the enclosure
contains equipment that operates at over 80 percent of the autoignition temperature of the gas or vapor in the area.
Ex: A raceway seal isn’t
required if the make-and-break contacts are:
a. Within a hermetically sealed chamber
b. Immersed in oil in accordance with 501.115(B)(1)(2)
c. Enclosed within a factory-sealed explosionproof chamber
(2) A
raceway seal fitting isn’t required for trade size ½, ¾, 1,
1¼, or 1½ raceways that enter an explosionproof enclosure that
doesn’t contain any make-and-break contacts
(junction and splice boxes). An example is an enclosure that only contains terminals,
splices, or taps. However, a trade size 2 or larger raceway that enters any
explosionproof enclosure must have a raceway seal fitting installed within 18
in. of the explosionproof enclosure.
Author’s
Comment:
When a raceway enters an
enclosure that doesn’t contain make-and-break contacts, the raceways only require a seal if they’re trade size 2 or
larger.
The raceway
seal fitting must be installed within 18 in. of the explosionproof enclosure.
Only
explosionproof unions, couplings, reducers, elbows, capped elbows, and conduit
bodies are permitted between the raceway seal and the explosionproof enclosure.
(2) Pressurized Enclosures. A raceway
seal fitting must be installed in each raceway that isn’t pressurized
where the raceway enters a pressurized enclosure. The raceway seal fitting must be installed within 18 in. of each
raceway that terminates to the pressurized enclosure.
(3) Between Explosionproof Enclosures. A single
raceway seal is permitted between two explosionproof enclosures containing make-and-break contacts if the raceway seal fitting is
located not more than 18 in. from either explosionproof enclosure.
(4) Class I, Division 1,
Boundary Seal. A raceway
seal fitting must be installed in each raceway that leaves a Class I, Division
1 location within 10 ft of the Class I, Division 1 location
on either side of the boundary.
There must
be no fitting, except for a listed explosionproof reducer
installed at the raceway seal fitting, between the raceway seal fitting and the
point at which the raceway leaves the Class I, Division 1 location.
Ex 1: A raceway boundary seal fitting isn’t required for a raceway that passes completely through the Class I, Division 1 area unbroken
with no fittings installed within 1 ft of either side of the boundary.
Ex 2: If
the raceway boundary is below grade, the raceway seal can be located above
grade, after the raceway emerges from below grade.
(B) Raceway Seal—Class I,
Division 2. In Class I, Division 2 locations, raceway seals must be located as
follows:
(1) Enclosures with Make-and-Break Contacts. A raceway seal fitting must be installed in each raceway that enters an
enclosure that must be explosionproof and that contains make-and-break contacts. The seal fitting must be installed within 18 in. of the
explosionproof enclosure.
(2) Boundary Seal at Unclassified Location. A raceway seal fitting must be installed in each
raceway leaving a Class I, Division 2
location. It can be installed on either
side of the boundary within 10 ft of
the Class I, Division 2 area.
Except for listed explosionproof reducers installed at the raceway seal
fitting, there must be no union, coupling, box, or fitting between the raceway seal fitting and the point at
which the raceway leaves the Division 2 location.
Raceway
boundary seals aren’t required to be explosionproof, but must be
identified for the purpose of minimizing the passage of gases permitted under normal operating conditions, and they must
be accessible.
Author’s
Comment:
See the definition of
“Accessible” as it relates to wiring methods in Article 100.
The raceway boundary seal at
unclassified locations is used to minimize the passage of gases or vapors, not
to contain explosions in the raceway system.
Ex 1: A
raceway boundary seal fitting isn’t required for a raceway that passes
completely through the Class I, Division 2 area unbroken with no fittings
installed within 1 ft of either side of the boundary.
Ex 2: A
raceway boundary seal fitting isn’t required for raceways that terminate in an
unclassified location where the metal conduit transitions to cable trays, cablebus, ventilated
busways, MI cable, or open wiring if:
(1) The unclassified location
is located outdoors or the unclassified location is indoors and the conduit
system is entirely in one room.
(2) The
raceways must not terminate at an enclosure containing an ignition source in
normal operation.
Ex 3: A
boundary seal fitting isn’t required for a raceway that passes from an
enclosure or a room
that’s unclassified, as a result of pressurization, into a Class I,
Division 2 location.
(C) Raceway
Seals—Installation Requirements. If explosionproof sealing fittings are
required in Class I, Division 1 and 2 locations, they must comply with the
following:
Ex:
Boundary seals for Class 1 Division 2 locations that aren’t required to be
explosionproof [501.15(B)(2)] aren’t required to
comply with 501.15(C).
(1) Fittings. Raceway seal fittings must be
listed for the specific sealing compounds and Class I location, and must be
accessible.
(2) Compound. The raceway seal compound
must be mixed and installed in accordance with manufacturer’s
instructions so it minimizes the passage of gases and/or vapors through the sealing fitting.
Author’s
Comment:
The sealing compound must be
from the same manufacturer as the raceway seal.
(3) Thickness of Compounds. Except
for listed cable sealing fittings, the thickness of the raceway seal compound installed in completed seals, other than listed cable sealing fittings, must not
be less than the trade size of the seal fitting, but in no case less than 5⁄8 in.
(4) Splices and Taps. Splices
and taps must not be made within a raceway seal fitting.
(6) Number of Conductors or Optical
Fiber Cables. The
conductor or optical fiber tube cross-sectional area must not exceed 25 percent of the cross-sectional area of rigid metal conduit (RMC) of the
same trade size, unless the seal is
specifically identified for a higher percentage fill.
Author’s
Comment:
The cross-sectional area of intermediate metal conduit (IMC) is approximately 7 percent greater
than that of RMC because the wall thickness of IMC is less than RMC. If the cross-sectional area of IMC is used for conductor fill
calculations, the 25 percent of “RMC conductor fill” can be
exceeded.
(D) Cable Seal—Class I,
Division 1. In Class I, Division 1 locations, cable seals must be located as
follows:
(1) Terminations. Type MC-HL cable is
inherently gas/vaportight by the construction of the cable, but the termination
fittings must permit the sealing compound to surround each individual insulated
conductor to minimize the passage of gases or vapors.
Ex: The
removal of shielding material or the separation of the twisted pairs
isn’t required within the raceway seal fitting.
(2) Cables Capable of Transmitting Gases or Vapors
in a Raceway. Raceways containing cables must be sealed after
removing the jacket and any other coverings so that the sealing compound
surrounds each individual insulated conductor or optical
fiber tube in a manner so as to minimize the passage of gases
and vapors.
Ex: The
removal of shielding material or the separation of the twisted pairs
isn’t required within the raceway seal fitting.
(3) Cables Not Capable of Transmitting Gases or
Vapors in a Raceway. Each multiconductor cable installed in a raceway is considered to be a single
conductor if the cable is incapable of transmitting gases or vapors through the
cable core.
(E) Cable Seal—Class I,
Division 2. In Class I, Division 2 locations, cable seals must be located as
follows:
Ex: Seals aren’t
required in a Class 1 Division 2 location if the cable passes through the
location and has an unbroken gas or vaportight sheath.
(1) Multiconductor Cable. Multiconductor or optical fiber cables
that enter an explosionproof enclosure must be sealed after removing the jacket
and any other coverings so that the sealing compound will surround each
individual insulated conductor or optical
fiber tube in a manner so as to minimize the passage of gases
and vapors.
Multiconductor
cables or optical fiber cables installed
in a raceway must be sealed in accordance with 501.15(D)(2)
or (3).
Ex 2: The
removal of shielding material or the separation of the twisted pairs
isn’t required within the cable seal fitting.
(4) Cable Seal—Boundary. Cables
without a gas/vaportight continuous sheath must be sealed at the boundary of
the Class I, Division 2 location in a manner so as to minimize the passage of
gases or vapors into an unclassified location.
|