Motor Calculations, Part 2 - Based on the 2014 NEC®    

 

In case you missed it, you can click here to view Motor Calculations, Part 1.

 

By Mike Holt, NEC Consultant

How do you correctly size devices that protect motor systems from overcurrent?

In Part 1, we saw why we must separate overload protection from fault and short circuit protection for motor circuits. But correctly sizing these different devices can be confusing. And if you follow the rules for one while doing the other, you’re liable to burn something up.

Two important numbers

When sizing motor overload protection devices (OPDs), two numbers that you don’t use for other types of circuits are vitally important.

1. You must know the motor nameplate service factor (SF). An SF of 1.15 means the motor can periodically operate at 115 percent of its rated horsepower.

2. When you size motor OPDs, you use the motor nameplate current rating (FLA). This differs from the Full Load Current (FLC) from the NEC tables that you use for sizing overcurrent protection devices (OCPDs) for motor branch circuits.

Supersize me

For motors with an SF of 1.15 or more, size the OPD no more than 125 percent of the FLA [430.6(A)(2)]. If your OPDs are fuses, you can’t exceed the values of 430.32(A)(1). That means you must round down to the next smaller fuse. Standard fuse sizes are listed in 240.6(A).

But what if the motor can’t start without blowing the OPD? If the sensing element, setting, or sizing of the motor OPD isn’t sufficient to allow the motor to start (or carry the load), you can increase the OPD size or setting. But the limit is:

  • 140 percent for motors with a marked SF of 1.15 or greater [430.32(C)].
  • 130 percent for motors with a SF of less than 1.15 and a marked temperature rise over 40ºC [430.32(C)].
  • 125 percent for motors with a nameplate temperature rise rating not over 40ºC.

A motor with a nameplate temperature rise of 40ºC means the motor is designed so that it won’t heat up more than 40ºC above its rated ambient temperature when operated at its rated load and voltage.

Combo OCPD and OPD

As noted earlier, for motor circuits we separate the functions of overload protection from those of protection against short circuits and faults. But with short-time, intermittent, periodic, or varying duty motors, you can combine these functions in the OCPD [430.33].

The catch here is the rating or setting of the OCPD can’t exceed the values in Table 430.52. And, of course, the controls or the nature of the application must ensure the motor can’t operate continuously under any conditions of use.

In many cases, the inrush isn’t enough to create the problems that requires the separation of OCP and OCPD, even if you do have a continuous duty motor. In these cases, you can use a single OCPD to protect a motor against overload, short circuit, and ground faults. But you must size it to the overload requirements in 430.32 [430.55].

Here’s an example problem. Question: What size dual-element fuse is permitted to protect a 5 hp, 230V, single-phase motor with a service factor of 1.15 and a nameplate current rating of 23.50A from overloads and from short circuits and ground faults?

(a) 20A fuse     (b) 25A fuse     (c) 30A fuse     (d) 35A fuse

Answer: (b) 25A fuse

Overload Protection [430.32(A)(1) and 430.55]

23.50A x 1.25 = 29.40A, use a fuse [240.6(A)]

In this example, we used a small motor. It doesn’t draw much current, so the inrush and heat are also on that small scale. But this ability to combine isn’t limited to small motors. The separation of OPD and OCDP accommodates the inrush that occurs when you start the motor across the line. What if you use a soft starter or a variable frequency drive (VFD) with soft start function?

Soft starters and VFDs provide the OPD function, so you don’t need to size OPDs in a separate starter. More importantly, they dramatically reduce inrush. With one of these devices inserted between the supply and the motor, your branch-circuit OCPD now sees a very different load. Because of this, the manufacturer provides OCPD sizing instructions so you can correctly size the OCPD [430.130(A)(2)].

Branch-Circuit Short-Circuit and Ground-Fault Protection

A branch-circuit OCPD protects the motor, motor control apparatus, and conductors against short circuits or ground faults. But it doesn’t protect them against overload [430.51]; that’s the job of the OPD (except as noted earlier).

The branch-circuit OCPD must able to carry the motor’s starting current [430.52(B)]. You can size that OCPD no greater than the percentages listed in Table 430.52 [430.52(C)].

What if the size OCPD you need doesn’t correspond with the standard OCPD ratings listed in 240.6(A)? In that case, you can apply the “next size up rule” and use the next higher OCPD rating [430.52(C)(1) Ex 1].

Here’s an example to illustrate. Question: What size conductor and inverse time circuit breaker are required for a 7½ hp, 230V, three-phase motor with terminals rated 75 ºC?

(a) 10 AWG, 50A breaker     (b) 10 AWG, 60A breaker     (c) 8 AWG, 70A breaker     (d) 8 AWG, 80A breaker

Answer: (b) 10 AWG, 60A breaker

Step 1: Determine the branch-circuit conductor, 125% of FLC

[Table 310.15(B)(16), 430.22, and Table 430.250]:

22A x 1.25 = 27.50A, rated 35A at 75ºC

Step 2: Determine the branch-circuit protection, 250% of FLC

[240.6(A), 430.52(C)(1) Ex 1, and Table 430.250]:

22A x 2.50 = 55A, next size up = 60A

Feeder OCPDs

How you size OCPDs for a motor feeder depends upon whether it supplies a motor load and other loads [430.62] or only a motor load [430.61]. Let’s look at the “motor loads only” application, first.

Size the OCPD not more than the largest rating of the branch-circuit OCPD for any motor, plus the sum of the full-load currents of the other motors in the group.

▶ Motor Feeder Protection Example

Question: What size feeder protection and conductors are required for these two motors with terminals rated 75 ºC?

Motor 1: 10 hp, 460V, three-phase: FLC = 14A [Table 430.250]

Motor 2: 20 hp, 460V, three-phase: FLC = 27A [Table 430.250]

(a) 70A breaker, 4 AWG (b) 80A breaker, 8 AWG

(c) 90A breaker, 3 AWG (d) 100A breaker, 3 AWG

Answer: (b) 80A breaker

Size feeder protection [430.62(A)] no greater than the largest branch-circuit OCPD plus the other motors’ FLC.

Step 1: Determine the largest branch-circuit OCPD [430.52(C)(1) Ex].

10 hp Motor = 14A x 2.50 = 35A

20 hp Motor = 27A x 2.50 = 68, next size up = 70A

Step 2: Determine the size feeder protection.

Not more than 70A + 14A = 84A,

Next size down = 80A [240.6(A)]

The “next size up protection” rule for branch circuits [430.52(C)(1) Ex 1] doesn’t apply to the motor feeder OCPD rating.

Feeder conductor size.

Feeder conductor size is based on 125% of the FLC of the highest rated motor in the group plus 100% of all other motor FLCs on the same phase [430.24].

(27A x 1.25) + 14A = 48A

[110.14(C) and Table 310.15(B)(16)]

8 AWG rated 50A at 75ºC

If the circuit contains other loads in addition to motors, the OCPD rating must not be less than that required for the sum of the other loads plus the rating permitted by:

  • 430.62, for two or more motors.
  • 430.52, for a single motor
  • 440.22, for a single hermetic motor.

Hermetics

Article 440 applies to the hermetic motors that drive the compressors of air-conditioning and refrigeration equipment. These motors are of a special construction. Your typical industrial pump motor has its own housing and you bolt it to a pedestal. There’s a coupling from the motor to the pump unit. These are clearly separate structures.

But a hermetic motor doesn’t have its own housing. It’s enclosed in the same housing as the refrigerant. This motor thus has different heat dissipation capability from a non-hermetic motor. For that reason, you apply Article 440 when sizing OPDs for these motors and OCPDs for systems with these motors.

Avoiding mistakes

Article 430 can be confusing because provisions for motor circuits differ from general rules. The overload protection for motors is (usually) treated separately from short-circuit and ground-fault protection. Motor circuits must accommodate increased starting current and still provide satisfactory running protection. For this reason, the overcurrent protection rules you learned in Article 240 don’t apply to motor circuits.

A common mistake made in motor circuits is the use of the motor nameplate current for calculations that should be made using the full-load current from the Article 430 tables. Use the nameplate FLA only used for overload protection. Use Tables 430.248, 430.249, and 430.250 for sizing conductors, short-circuit and ground-fault protection, and disconnect switches.

Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 
Book

 

Taken from Mike Holt's Illustrated Guide to Electrical Exam Preparation, based on the 2014 NEC®.

To order your copy, please click here, or call 888.632.2633

 

Mike Holt's products give you the edge:

  • Designed to make learning easy.
  • Detailed instructional graphics to illustrate the concept in real-life situations.
  • DVD programs that feature Mike and a panel of industry experts to give you an in-depth analysis of the rules and how to apply them.
  • Visit www.MikeHolt.com/14examprep

 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
"... as for me and my house, we will serve the Lord" [Joshua 24:15]
 
Comments
  • Mike, under the Branch-Circuit Short-Circuit and Ground-Fault Protection section, step 1 under 240.6(A) the next higher amp rating is 30A. Why did you choose 35A? Thanks.

    Martin  February 11 2015, 10:01 am EST

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter