Visit MikeHolt.com
Section 690.47 Grounding Electrode System - Based on the 2014 NEC    

 

We’re excited to bring you an extract from Mike Holt’s Illustrated Guide to Understanding NEC® Requirements for Solar Photovoltaic Systems to give you an introduction to the book and DVDs. As part of our ongoing effort to provide free resources to help the industry, this is our 3rd in a series of newsletters that include graphics and text taken directly from a Mike Holt textbook and a video clip from the DVD program.

 

Image1

 

Watch the Video Clip!

To get the most out of this instruction, watch the video clip as you review this content. Click here or on the image to the right [duration 26:33]. Mike and the DVD team weigh in on the rule and discuss the practical impact of its everyday application.

 

In case you missed them, here are links to the previous newsletters in this series:

250.54 Auxiliary Grounding Electrodes

680.26 Equipotential Bonding

 

*Please note in the follwing extraction that blue underlined text indicates a 2014 NEC change.

 

Section 690.47 – Grounding Electrode System

 

(A) Alternating-Current PV System Grounding Requirements. For ac PV systems, a grounding electrode system must be provided in accordance with 250.50 through 250.60, with the ac grounding electrode conductor installed in accordance with 250.64.Figure 690–109

 

Im,age

 

Figure 690–109

 

(B) Direct-Current PV System Grounding Requirements. For dc PV systems, a grounding electrode system in accordance with 250.166 for grounded systems, or 250.169 for ungrounded systems, must be provided. Figure 690–110

 

Image3

Figure 690–110

 

A common dc grounding-electrode conductor can service multiple inverters. Section 250.166 is used to size the common grounding electrode and the tap conductors. The tap conductors must be connected to the common grounding-electrode conductor by exothermic welding or with connectors listed as grounding and bonding equipment.

 

The ac grounding electrode system can be used for equipment grounding of inverters and for the ground-fault detection reference for un-grounded PV systems.

 

(C) PV Grounded System with Alternating-Current Power System. Grounded PV systems constructed of dc modules must have the dc system grounded by one of the following methods:

 

(1) Separate dc Electrode. A grounding electrode conductor run from the marked dc GEC point at the inverter to the separate dc grounding electrode sized no smaller than the largest ungrounded dc conductor, but no smaller than 8 AWG [250.166(B)]. The dc grounding electrode must be bonded to the ac grounding electrode with a bonding jumper sized to the larger of the dc grounding electrode conductor [250.166] or ac grounding electrode conductor [250.66]. Figure 690–111

 

Image4

Figure 690–111

 

(2) Alternating-Current Grounding Electrode. A grounding electrode conductor sized in accordance with 250.166 must be run from the marked dc GEC point at the inverter to the ac grounding electrode. Figure 690–112

 

Image3

Figure 690–112

 

Where an ac grounding electrode isn’t accessible, the dc grounding electrode conductor must terminate to the ac grounding electrode conductor with a connector listed as grounding and bonding equipment. 690–113

 

Image2

Figure 690–113

 

(3) Combination ac Equipment Grounding Conductor/dc Grounding Electrode Conductor. For grounded PV Systems, the ac equipment grounding conductor sized to the larger of 250.122 or 250.166 can serve as both the ac circuit equipment grounding conductor and dc grounding electrode conductor. Figure 690–114

 

Image3

Figure 690–114

 

Author’s Comment:

  • The ac equipment grounding conductor is sized in accordance with 250.122 based on the rating of the ac circuit overcurrent protection device; the dc grounding electrode conductor is sized no smaller than 8 AWG and no smaller than the dc circuit conductors [250.166(B)].

 

Question: What size EGC/GEC is required for a grounded PV system, where the inverter dc input circuit conductors are 14 AWG and the inverter ac output circuit conductors are 10 AWG protected by a 30A breaker? Figure 690–115

 

Answer: Table 250.122 requires the ac EGC to be sized no smaller than 10 AWG, and 250.166(B) requires the dc grounding electrode conductor to be no smaller than the largest dc circuit conductors, but no smaller than 8 AWG. In this case, the combined EGC/GEC must be no smaller than 8 AWG.

Image3

Figure 690–115

 

For ungrounded systems, the ac equipment grounding conductor sized no smaller than required by 250.122 based on the rating of the ac circuit overcurrent protection device can serve as both the ac circuit equipment grounding conductor and dc grounding electrode conductor. Figure 690–116

 

Image3

Figure 690–116

 

(D) Auxiliary Electrode for Array. A dc grounding electrode conductor from the array structure sized in accordance with 250.166 must be connected to a grounding electrode that complies with 250.52 and 250.54.

 

The metal structure of a ground- or pole-mounted PV array can serve as the grounding electrode if it complies with 250.52.

 

Roof-mounted PV arrays can use the metal frame of a building or structure as the electrode if it meets 250.52(A)(2). Figure 690–117

 

Image3

Figure 690–117

 

Ex No. 1: An array grounding electrode(s) isn’t required where the load served by the array is integral with the array.

Ex No. 2: An additional array grounding electrode(s) isn’t required if located within 6 ft of the premises wiring electrode.

Author’s Comment:

  • Auxiliary electrodes have no NEC requirements since they serve no useful purpose relating to electrical safety, yet are permitted. If an auxiliary electrode is installed, it isn’t required to be bonded to the building grounding electrode system, required to have the grounding conductor sized to 250.66, or to comply with the 25-ohm requirement of 250.53(A)(2) Ex [250.54].

 

CAUTION: An auxiliary electrode typically serves no useful purpose, and in some cases it may actually cause equipment failures by providing a path for lightning to travel through electronic equipment. Figure 690–118

 

Image3

Figure 690–118

 

2014 Change Analysis: The requirements for grounding the PV array were included in the 2008 Code, but disappeared in the 2011 edition. Due to the fact that there was no technical substantiation in either the report on proposals or the report on comments to remove it from the 2011 edition, it was inserted back into the 2014 Code without substantiation.

Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 

This Article is extracted from Mike Holt’s Illustrated Guide to Understanding NEC® Requirements for Solar Photovoltaic Systems based on the 2014 NEC®. To order your copy of the full program, click on the image below or visit www.mikeholt.com and save 20% when you use discount code NL14SOL.

Image5

 

 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
"... as for me and my house, we will serve the Lord" [Joshua 24:15]
 
Comments
  • What about auxiliary grounding electrodes for outdoor transformers like the one in required in 250.24(a)(2) of the 2011 nec. Does that also creat the dangerous situation you describe here? Would the solution be to bond the auxiliary electrode to the original service electrode?

    Gary  January 14 2015, 7:35 pm EST

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter