Electrical Problems at a Boat Dock

Electrical Problems at a Boat Dock

 

By Chuck Newcombe (aka Bish)

 

During the eight years that I’ve been writing the Beyond the Basics column for Fluke News Plus, I’ve discussed wiring and grounding problems in industrial plants, homes, and dairy farms. This one adds grounding issues at boat docks.

 

Consider what can happen when an unsuspecting swimmer comes near a boat with stray ac leakage current flowing between the boat hull and grounded dock components or the bottom of a lake.

 

The grim reality is that ac leakage current, often less than 100 milliamps, may be flowing undetected in the water. That’s far from the amount required to trip a 20 amp breaker, but enough to paralyze a swimmer. You wouldn’t see any thrashing in the water, or hear a call for help. Later, a drowned person would be pulled from the water with no clue provided as to the cause of the drowning.

 

How can one detect the likely presence of ac leakage currents in the water?

 

My choice is the Fluke model 360 Leakage Clamp Meter. This meter can measure up to 60 amps ac in normal use but has two special features that make it appropriate for leakage current testing.

1. The current measurement sensitivity extends down to a 3 mA range with 1 μA resolution.

2. The jaw size is 1.5 inches, allowing the jaws to be placed around thick cables and conduit.

 

Where to measure

 

Text Box:    The 1 2 3 test for ac leakage  Kirchoff’s current law states that the sum of all currents flowing into and out of a node must equal zero. We can use this information to devise a test procedure for a dock. In the diagram below, the node we’ll use is marked “N.” Arrows with solid lines show where current should flow, and the dotted lines show where leakage can occur.

 

If you want to measure the current flowing from the source to the load, you would place the clamp around a single conductor (1). But, using Kirchoff’s current law you can place the clamp around multiple conductors as shown at positions 2 and 3.

 

In a properly wired circuit, the clamp meter reading should be zero for positions 2 and 3. Any leakage current flowing in the green safety ground wire would be seen as a non-zero reading at position 2, and any leakage current from the load to earth would show a non-zero reading at positions 2 or 3.

Text Box:

Since the green wire is included in the test at position 3, only the earth current, is registered as leakage in that case. I’ve made an accessory to allow convenient measurements in the three test positions shown in the diagram above. I bought a short extension cord and modified it as shown here to make the three conductors individually accessible.

 

You can read additional details in my original article here.

 

footer
This newsletter was sent to 60907 Subscribers
Unsubscribe
Comments
  • The probe in the water doesn't tell you much unless the voltage is very high (10s of volts). It's normal to see a few volts in a saltwater marina when everyone is running their A/C units. Our grounded neutral system results in ground currents everywhere. Ideally there shouldn't be any, but there are many parallel return paths since pole transformers and pad transformers are all grounded to the earth.

    To find the water leakage. Clamp the cord on the boat with AC loads running. Ideally it will read zero. Any current you read is current that is either leaking from the boat you are clamping or coming back from another source via the cord you are clamping. After getting that reading, turn off the pedestal breaker for the boat you are clamping. Any current change is the result of a ground fault on that boat.

    Example: clamp reads 500ma. open breaker and it now reads 100ma. This means that 100ma is coming back on the ground wire from another source (maybe the boat next door for example) and 400ma is going in the water from a fault on the boat you are clamping.

    At this point you can use an adapter to split out the conductors and measure the currents individually. In many cases you will see even more current on the bonding conductor (green wire in the cord). Add this to what's going into the water and you have the total fault current from the fault. Remember, only takes about 60w to start a fire. That's half an amp at 120v.

    Contact me if you have more questions.

      July 24 2014, 3:57 pm EDT