This article was posted 12/21/2011 and is most likely outdated.

Mike Holt Newsletters
 

 

Topic - NEC Questions
Subject - 2011 NEC Questions & Answers - December 2011

December 21, 2011
This newsletter was sent to 18475 newsletter subscribers

Ask a Question |  Continuing EducationQuizzes |  Free Stuff Instructors Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ]  

NEC Questions and Answers – Based on the 2011 NEC
December 2011

By Mike Holt for EC&M Magazine

Here’s the follow up to Monday's newsletter. This includes all of the answers to the questions sent, so you can see how you did.

 

Q1. Is it acceptable to use a portable cord with male cord caps on both ends to connect a portable generator?

A1.  No. Attachment plugs must be installed so their prongs, blades, or pins aren’t energized unless inserted into an energized receptacle or cord connector [406.7(B)].

 

Q2. Is the service neutral conductor allowed to perform bonding between the meter can and disconnect?

A2. Yes. Electrical continuity at service equipment, service raceways, and service conductor enclosures can be established by bonding the metal parts to the service neutral conductor [250.92(B)(1)]. Figure 250-92B1 01

Author’s Comments:

•  A main bonding jumper is required to bond the service disconnect to the service neutral conductor [250.24(B) and 250.28].

•  At service equipment, the service neutral conductor provides the effective ground-fault current path to the power supply [250.24(C)]; therefore, an equipment grounding conductor isn’t required to be installed within PVC conduit containing service-entrance conductors [250.142(A)(1) and 352.60 Ex 2].

 

Q3. What are the permitted methods for terminating equipment grounding conductors, grounding electrode conductors, and bonding jumpers?

A3. Equipment grounding conductors, grounding electrode conductors, and bonding jumpers must terminate in one of the following methods [250.8(A)]:

•  Listed pressure connectors

•  Terminal bars

•  Pressure connectors listed for direct burial or concrete encasement [250.70]

•  Exothermic welding

•  Machine screws that engage at least two threads or are secured with a nut

•  Self-tapping machine screws that engage at least two threads

•  Connections that are part of a listed assembly

•  Other listed means

 

Q4. What panelboard identification is required for a panelboard that contains a 3 phase 4-wire, 120/240V delta-connected system?

A4.  A switchboard or panelboard containing a 4-wire delta-connected system where the midpoint of one phase winding is grounded shall be legibly and permanently field-marked as follows [408.3(F)(1)]:

“Caution _____ Phase Has _____ Volts to Ground”

 

Q5. When a panelboard is supplied by a 4-wire, delta-connected, three-phase (high-leg) system, where must the high-leg conductor terminate?

A5. Panelboards supplied by a 4-wire, delta-connected, three-phase (high-leg) system must have the high-leg conductor (which operates at 208V to ground) terminate to the “B” phase of the panelboard  [408.3(E)] . Figure 408-03E0 02

Ex: The high-leg conductor can terminate to the “C” phase when the meter is located in the same section of a switchboard or panelboard.

Note: Orange identification, or some other effective means, is required for the high-leg conductor [110.15 and 230.56].

Warning: The ANSI standard for meter equipment requires the high-leg conductor (208V to neutral) to terminate on the “C” (right) phase of the meter socket enclosure. This is because the demand meter needs 120V and it gets it from the “B” phase.

WARNING: When replacing equipment in existing facilities that contain a high-leg conductor, use care to ensure that the high-leg conductor is replaced in the original location. Prior to 1975, the high-leg conductor was required to terminate on the “C” phase of panelboards and switchboards. Failure to re-terminate the high leg in accordance with the existing installation can result in 120V circuits being inadvertently connected to the 208V high leg, with disastrous results.

 

Q6. What must be done to protect Type NM cable where it is run through or parallel to framing members?

A6. Type NM cable installed through or parallel to framing members or furring strips must be protected against physical damage from penetration by screws or nails by 1¼ in. of separation or by a suitable metal plate [300.4(A) and (D) and 334.17]. Figure 334-17 02

If Type NM cable passes through holes in metal studs, a listed bushing or listed grommet is required [300.4(B)(1)] to be in place before the cable is installed.

 

Q7. What is the Code rule for sizing branch circuit conductors?

A7. Conductors must be sized no less than 125 percent of the continuous loads, plus 100 percent of the noncontinuous loads, based on the terminal temperature rating ampacities [110.14(C)(1)] as listed in Table 310.15(B)(16), before any ampacity adjustment [210.19(A)(1)].

Ex 1: If the assembly and the overcurrent device are both listed for operation at 100 percent of its rating, the conductors can be sized at 100 percent of the continuous load.

Author’s Comments:

•  Equipment suitable for 100 percent continuous loading is rarely available in ratings under 400A.

•  See the definition of “Continuous Load” in Article 100.

•  See 210.20 for the sizing requirements for the branch-circuit overcurrent device for continuous and noncontinuous loads.

Example: What size branch-circuit conductors are required for the ungrounded conductors of a 44A continuous load, if the equipment terminals are rated 75ºC?

(a) 10 AWG    (b) 8 AWG     (c) 6 AWG   (d) 4 AWG

Answer: (c) 6 AWG

Since the load is 44A continuous, the ungrounded conductors must be sized to have an ampacity of not less than 55A (44A x 1.25). According to the 75ºC column of Table 310.15(B)(16), a 6 AWG conductor is suitable, because it has an ampere rating of 65A at 75ºC before any conductor ampacity adjustment for ambient temperature [310.15(B)(2)(a)], conductor bundling [310.15(B)(3)(a)], or both.

Q8. What does the NEC recommend in regard to voltage drop when sizing conductors?

A8. The Code recommends: to provide reasonable efficiency of operation of electrical equipment, branch-circuit conductors should be sized to prevent a voltage drop not to exceed 3 percent. In addition, the maximum total voltage drop on both feeders and branch circuits shouldn’t exceed 5 percent. [210.19(A)(1) Note 4 and 215.2(A) Note 2] Figure 210-19A1 02 N4

Author’s Comments:

•  Many believe the NEC requires conductor voltage drop, as per Note 4 to be applied when sizing conductors. Although this is often a good practice, it’s not a Code requirement because Notes are only advisory statements [90.5(C)].

•  The NEC doesn’t consider voltage drop to be a safety issue, except for sensitive electronic equipment [647.4(D)] and fire pumps [695.7].

 

Q9. Is AFCI protection required in hotel guest rooms?

A9. No, the Code requirements for AFCI protection are for dwelling units only.

All 15A or 20A, 120V branch circuits in dwelling units supplying outlets in family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas must be protected by a listed AFCI device of the combination type [210.12(A)].

Author’s Comment: The 120V circuit limitation means AFCI protection isn’t required for equipment rated 230V, such as a baseboard heater or room air conditioner. For more information, visit www.MikeHolt.com, click on the “Search” link, and search for “AFCI.”

210.12(A) Note 3: See 760.41(B) and 760.121(B) for power-supply requirements for fire alarm systems.

Author’s Comment: Smoke alarms connected to a 15A or 20A circuit of a dwelling unit must be AFCI protected if the smoke alarm is located in one of the areas specified in 210.12(A). The exemption from AFCI protection for the “fire alarm circuit” contained in 760.41(B) and 760.121(B) doesn’t apply to the single- or multiple-station smoke alarm circuit typically installed in dwelling unit bedroom areas. This is because a smoke alarm circuit isn’t a fire alarm circuit as defined in NFPA 72, National Fire Alarm Code. Unlike single- or multiple-station smoke alarms, fire alarm systems are managed by a fire alarm control panel.

 

Q10. What labeling does the Code require in regard to arc-flash hazard warning?

A10. Electrical equipment such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers in other than dwelling units that are likely to require examination, adjustment, servicing, or maintenance while energized must be field-marked to warn qualified persons of the danger associated with an arc flash from short circuits or ground faults. The field-marking must be clearly visible to qualified persons before they examine, adjust, service, or perform maintenance on the equipment [110.16].

Author’s Comments:

•  See the definition of “Qualified Person” in Article 100.

•  This rule is meant to warn qualified persons who work on energized electrical systems that an arc flash hazard exists so they’ll select proper personal protective equipment (PPE) in accordance with industry accepted safe work practice standards.

110.16 Note 1: NFPA 70E, Standard for Electrical Safety in the Workplace, provides assistance in determining the severity of potential exposure, planning safe work practices, and selecting personal protective equipment.

 

 

Image2 

 

 

For more NEC Practice purchase Mike Holt's NEC Practice Questions book, Based on the 2011 NEC.

 

 

 

Click here to post a comment

[ Post Your Comments | View Comments | Notify Me When Comments Are Added ]
[ View More Newsletters ]

Bookmark and Share


Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

 

 
Comments
  • Q1 - Variation to this question. If "mobile" is substitued for "portable", what would the answer be? I think that NEC is silent on this matter. Almost always mobile E-G set is installed by trained electricians, and that their company's SOP for safe installation requires LOTO generator output CB, and not to start and run E-G set until generator feeder is connected to the loads to comply with OSHA safety requirements. Do you see flaws in my thoght?

    Max Takaki  December 23 2011, 4:13 pm EST

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter