Eagle GFCI Follow Up
 

 

Topic - Safety
Subject - Eagle GFCI Receptacle Problems - A Follow Up

February 24, 2010
This newsletter was sent to 19270 newsletter subscribers

Ask a Question |  Continuing EducationQuizzes |  Free Stuff Instructors Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ]  

Eagle GFCI Analysis
A Follow-up

Image1 On December 30, 2009 we sent out a newsletter titled Eagle GFCI Receptacle Problems in which Anthony requested information from anyone who could help regarding a faulty/burnt GFCI receptacle he discovered in his home.

In addition to generating more comments than any other newsletter that month, it caught the attention of Darron Lacey who leads the engineering group for Cooper Wiring Devices and who told Mike:
“My company puts quality as the number one priority. My goal in calling the electrician will be to determine the cause of failure and then respond to your web site in a more definitive manner. “ 

After the faulty receptacle was sent to Cooper Wiring Devices for analysis, Dan Fielder, Manager of Engineering Services reported on his findings in a letter to Anthony.

Summary: …evidence strongly suggests moisture was involved with this failure. Moisture and contaminates on a printed circuit board can lead to current leakage, carbon tracking and possible arcing. As noted the device was under an overhang and had a weatherproof cover, however moisture infiltration is very difficult to inhibit as it can occur in numerous ways such as wind blown rain, extreme humidity, pressure washing condensation……increasing the importance of keeping GFCIs dry with weatherproof enclosures, proper gaskets and caulking. Click here to read the complete analysis.

Anthony’s comment: I think the industry really needs to address a solution for this problem. Ironically the device is required in locations that are subject to moisture and the presence of a source of water. In southwest Florida where our humidity averages somewhere near 100% during our rainy season and usually near 80% the rest of the year, it is nearly impossible to keep the moisture out. We also have blowing rain. Maybe it would be a good practice to install the GFCI device on the inside of the building and use the feed through feature to protect the outlets on the exterior of the building?

 

Click here to post a comment

[ Post Your Comments | View Comments | Notify Me When Comments Are Added ]
[ View More Newsletters ]

Bookmark and Share


Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

 

 
Comments
  • I work at a plant that the Corporate Mandate is to follow the guidlines of the NEEC and use the GFCI'S anytime that we need to replace a outlet. However we are in a total washdown area and with the best of covers and Gaskets installed we still have a moisture problem We do not use High pressure but our water pressure is about 60 PSI and even with that we still get mositure on the insdie of the outlet boxes. Yes part of it can be Humidty but there might even be cracks in the mortore or in the block walls. So how would one get things pefectly mositure proof? I agree GFCI's should be used however lets make them a little better to help some of the issues. It is not like we don't pay a premium for the item anyways.

    John

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter