"Author’s Comment: Cables identified as suitable for plenum
use can be installed in environmental air spaces, but they are
not permitted to be installed in ducts or plenums! See 760.3(B)
in this textbook for details."
THis statement is repeated in the illustration adjacent. Uh, it doesn't make any sense. If a cable is listed for installation in a plenum, then it should be allowed in a plenum! Why does the author make this statement? Since it was said twice, I assume there is some truth to it and it isn't a typo. What is the explanation? Lawrence Lile
|