Electrical Hazards for Aircraft and the NEC
 

 

Topic - Grounding
Subject - Electrical Hazards for Aircraft and the NEC

May 20, 2009
This newsletter was sent to 22102 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Electrical Hazards for Aircraft and the NEC

 

The National Electric Code, Article 90.2(B)(1)(Scope, Not Covered) specifically excludes electrical installations in aircraft. How then, can there be electrical hazards involving the NEC and aircraft applications? Whenever the aircraft is receiving electrical power from fixed premises wiring, such as when loading passengers or undergoing maintenance at an aviation facility such as an airport.

Such electrical hazards are created by the inherent aircraft electrical design philosophy colliding with specific requirements for electrical safety contained in the NEC.

During ground operations, aircraft may be receiving electrical power, defined by MIL-STD-704 as a three-phase, four-wire, grounded-WYE electrical service of 115/200 volts, 400-Hz. This Military Standard is used for all commercial aircraft using 400-Hz power. This power is derived from the building electrical service and is a permanent installation, connecting to the aircraft via a pendant cord. The NEC, Article 513.10(C)(3) requires that such cord “shall include an equipment grounding conductor.” The cord assemblies available today do not contain the required grounding conductor. See Figure 1.

Image1
Figure 1: Typical Aircraft Cord Connector

In this design, pins A, B, C, and N carry the respective circuit conductors, including the grounded conductor. The two smaller pins are reserved for the 28-VDC Safety circuit; pins E & F. The aircraft mating plug does not provide for an equipment grounding conductor and the grounded conductor is bonded to the aircraft skin. The aircraft structure then serves as a Neutral or Return conductor.

It is common practice in aircraft power distribution design to provide single phase load power via a single conductor, the aircraft structure then providing the missing conductor [1, 2].

Consider then a commercial aircraft at the boarding gate, powered by the premises power system, with fuel in the tanks, people boarding, and power currents flowing through the structure of the aircraft, including the fuel tanks.

By not providing a grounding conductor, it will be difficult to detect a low level single-phase power fault. This is especially true since the skin or fuselage is acting as the grounded conductor.

Author: 
Mike McClelland
Principal Engineer
559-583-7491
mmcclelland43@comcast.net

Bibliography

1. Standard Handbook for Electrical Engineers, 12th Edition, Donald G. Fink and H. Wayne Beaty © McGraw-Hill 1987, Chapter 23, page 23-4.

2. Aircraft Electromagnetic Compatibility Final Report, Boeing Commercial Airplane Company, Seattle, WA, June 87, published by U.S. Department of Commerce, National Technical Information Service. DOT/FAA/CT-86/40. Page 77. Download this report from: http://ntrs.nasa.gov/archive/nasa/casi.ntrs.nasa.gov/19870014423_1987014423.pdf

 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • The neutral wire (same size as A, B, and C) is bonded to the generator case which is bonded to earth ground. The aircraft neutral buss is connected to the feed plug neutral. This neutral connection to the aircraft is NOT broken by any other means than the pluged connection.

    Aircraft switches over to ground power via load contactors , first the ground power load concator which sends power to the aircraft, then after quality check passes, the aircraft load contactor energizes. The aircraft then monitors the power durring the entire power cycle and holds the generator ON via the smaller E & F 28 vdc signal. The neutral is NOT broken other than the matting plug pictured.

    Micah

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter