This article was posted 03/05/2009 and is most likely outdated.

Smoke Detectors on AFCI Protected Circuit?
 

 

Topic - AFCI
Subject - Smoke Detectors on AFCI Protected Circuit?

March 5, 2009
This newsletter was sent to 22048 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Smoke Detectors on AFCI Protected Circuit?

Let’s review the 2008 NEC

ImageDwelling Unit Circuits. All 15A or 20A, 120V branch circuits in dwelling units supplying outlets in family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas must be protected by a listed AFCI device of the combination type [210.12(B)].

The 120V circuit limitation means AFCI protection isn’t required for equipment rated 230V, such as a baseboard heater or room air conditioner. For more information, visit www.MikeHolt.com, click on the “Search” link, and search for “AFCI.”

Smoke alarms connected to a 15A or 20A circuit of a dwelling unit must be AFCI protected if the smoke alarm is located in one of the areas specified In 210.12(B). The exemption from AFCI protection for the “fire alarm circuit” contained in 760.41(B) and 760.121(B) doesn’t apply to the single-or multiple-station smoke alarm circuit typically installed in dwelling unit bedroom areas. This is because a smoke alarm circuit isn’t a fire alarm circuit as defined in NFPA 72, National Fire Alarm Code. Unlike single-or multiple-station smoke alarms, fire alarm systems are managed by a fire alarm control panel.

Note: An arc-fault circuit interrupter is a device intended to de-energize the circuit when it detects the current waveform characteristics unique to an arcing fault [210.12(A)].

Mike Holt’s Comment: The National Fire Marshals Association supports the NEC requirement that circuits for smoke detectors be AFCI protected.

You might find the following news article from The Buffalo News (New York) http://www.buffalonews.com/437/story/596807.html to be of some interest.

A faulty smoke detector sparked a fire that caused $175,000 damage to a Clarence home at about 4:45 p.m. Tuesday, Amherst Fire Control said.

The fire at 8895 County Road started shortly before 4:45 p. m. and was noted by a volunteer firefighter passing the scene.

Clarence Center firefighters battled the blaze with crews from Clarence, Getzville and East Amherst. Clarence Center Chief David Case said the fire was caused by the smoke detector in the living room ceiling. The blaze caused extensive fire, heat and smoke damage throughout the 1-1/2-story wood frame house.

No one was home at the time of the blaze. The American Red Cross was assisting the family, which was displaced by the fire.

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • One of the concerns that I have with AFCIs and well as GFCIs is that an AFCI contains equipment ground fault protection. The amount of static electricity that the human body can carry is capable of nuisance tripping a GFCI - I am not sure if the 30 mA or 50 mA trip level in an AFCI would also be susceptible. On very cold and dry days during the winter, if I do not first ground my body and then the current carrying prongs of my electric shaver plug, the electric shaver will nuisance trip the GFCI in the bathroom. The mechanism is electrostatic induction. The static charge on my body induces and equal an opposite charge in the motor windings of the shaver. When I plug in the shaver ( without first discharging the static electricity ) the GFCI reads the static as a ground fault and trips. There is just not a way to make a GFCI that is smart enough to tell the difference between a real ground fault or a phantom ground fault from static electricity.

    A similar thing can happen when a motor turns off or when the starting winding shuts off during the starting sequence. What happens is that the voltage spike from motor inductance forces a phantom ground fault pulse to flow through the winding to frame capacitance. Essentially, a small and transient version of how if you do not ground the frame of the hoist motor of a 480 volt 15 ton bridge crane the hoist ropes will have a nasty tingle voltage when the hoist is energized no matter hlw good the motor insulation is. Since 120 volt motors are built cheaply you can expect them to have more than their fair share of insulation capacitance and resistance problems.

    What gets me is that I install a har-wired uninterruptible power supply in the smoke alarm circuit and that would completely defeat the AFCI.

    I also consider 120 volt smoke alarms to be a bogus product. The 9 volt backup battery can be very difficult to replace for the mechanically inclined not to mention that there are a lot of people out there who are NOT mechanically inclined or who even own a ladder. The 9 volt battery could just as easily be located on the wall along with the test button. I have seen some smokes at trade shows that have an allegedly permanent battery that allegedly lives that same 10 years as the bit of radioactive material. There is also an alarm that speaks, "low battery," when the battery runs down.

    In the case of one commercial customer in Cleveland, Ohio the owner, employees, and customers ignored the low battery chirp for like 3 years. One problem was that the ceiling was high enough ( 11 feet ) that the only ladder for changing the batteries required 2 people to handle it.

    Sure, 120 volt smoke alarms are better than nothing, but my feeling is that a dwelling is better off to have a REAL fire alarm system. The backup battery is rechargeable and relatively easy to reach. A system that is moderately smart can periodically test the battery and if the battery is bad it can speak, "backup battery needs service or replacement."

    My other feeling is that like other people have written is that an AFCI will not necessarily stop a fire from starting. In fact, I tell people that a GFCI will not stop you getting shocked, it will only stop the shock from killing you.

    A further point is that General Electric and Siemens are the only 2 companies that have made a 2-pole AFCI for use with 3-wire circuits. These are common for higher load densities such as kitchens. There were some places such a Trumbull County, Ohio that required both 120 volt and 240 volt 15 ampere or 20 ampere receptacles in kitchens. Threfore, the kitchen circuits were essentially required to be 3-wire plus ground.

    I have also experienced that even having 4 AFCIs in a SquareD 40 slot panelboard creates a lot of congestion because they stick so far into the gutter. SquareD would be better off to make a version that takes up an extra plle space ( like neutral switching breakers do ) in order to free up gutter space. Expect to need to use a lot of 16-slot subpanels when using SquareD.

    Michael R. Cole

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter