Grounding vs Bonding: 250.68 Grounding Electrode Conductor Termination

February 24, 2006  

  View Comments | Add Comments | Notify Me When Comments Are Added  

PART III. GROUNDING ELECTRODE SYSTEM AND GROUNDING ELECTRODE CONDUCTOR  Hi Res - Cable/DSL [24352Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
       Page 13 of 14
Sections

250.68 Grounding Electrode Conductor Termination.

(A) Attachment Fitting. The grounding electrode attachment fitting must be accessible.

Exception 1: The grounding electrode attachment fitting to an encased or buried grounding electrode isn’t required to be accessible. Figure 250–119

Author’s Comment: When the grounding electrode attachment fitting is encased in concrete or buried, it must be listed and identified for this purpose [250.70].
Exception 2: An exothermic or irreversible compression connection to fireproofed structural metal isn’t required to be accessible.

(B) Effective Ground-Fault Current Path. To ensure a permanent and effective grounding path for an underground metal water pipe electrode, a bonding jumper must be installed around insulated joints and equipment likely to be disconnected for repairs or replacement. Figure 250–120

Author’s Comment: Continuity of the conductive bonding path for metal water piping as required by 250.104(A) cannot rely on water meters, filtering devices, or similar equipment [250.53(D)(1)].



Figure 250–119
(Click on image to enlarge)


Figure 250–120
(Click on image to enlarge)

     

Copyright © 2005 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments
  • My E-mail address changed to rosejc@iowatelecom.net

    Jim Rose
  • Reply from: Tara Moffitt   
    Any time your e-mail address changes you can update that by clicking on newsletters and then change e-mail address. OR Go directly there with this link: http://www.mikeholt.com/newslettersRegister.php?action=modify

    I'll go ahead and take care of this for you, but just wanted anyone else that may encounter this issue to know how to do this.

    Thank you.


Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter