Reply from: Bruce Rockwell What is "Remote Earth"?
What are you indicating isolated from "Remote Earth"
Earthing, as long as it is done correctly, is a good thing. This does not necessarilly mean we are direct connected into the soil, just that there is proper connection to an electrode (via throundinmg electrode conductor). All electrodes present in a facility need to be bonded together. Remember the ground system is made up of a few unique components:
Equipment Grounding Conductor
Grounded Conductor
Electrode (Sometimes referred to as "Earth")
Grounding Electrode Conductor
Isolated Ground - Just an equipment grounding conductor isolated from its utilization point back to the source. The source being a separately dervived system (ups/transformer/generator) or the building service if there is no transformer in between..
Lets not forget the MBJ - Main Bonding Jumper which is the neutral to ground connection at the service and the BJ - Bonding Jumper needed at separately dervied systems to connect neutral and ground and sometimes allowed elsewhere.
When considering grounding issues, always be clear about what part of the system you are investigating. Missing a component or having one where it should not be is never good.
Reply from: Mike Holt Remote Earth is a term indicating a point in the earth that is at least 50 ft away from any metal parts that you are attempting to measure voltage-to-earth from. |