Box Fill Calculations
 

 

Topic - NEC
Subject - Box Fill Calculations

July 24, 2008
This newsletter was sent to 29530 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Box Fill Calculations

By Mike Holt for EC&M Magazine

 

Calculate conductor equivalents to prevent box fill violations.

 

Box fill isn’t just the number of wires in the box. It’s the total volume of the conductors, devices, and fittings in a box.

 

Every outlet box has a specific amount of space for conductors, devices, and fittings—we call that the box volume. You calculate box volume per 314.16(A) and box fill per 314.16(B). You need to make sure your 314.16(A) box volume is greater than or equal to your 314.16(B) box fill.

 

Box volume

 

Table 314.16(A) seems to make it very simple to determine the volume of a box. But, don’t get too excited. You can use Table 314.16(A) only if the box contains no switches, receptacles, luminaire studs, luminaire hickeys, internal cable clamps, or equipment grounding conductors. This is rarely the case.

 

If Table 314.16(A) is inapplicable for your installation, which it typically will be, how do you calculate box volume? It’s a matter of adding up individual volumes of assembled parts [314.16(A)].

 

Start by with the box itself. If the box is not a standard size, the volume will be marked on the box by the manufacturer [314.16(A)(2)]. Then, add to it the sum of the individual volumes of the assembled parts, such as plaster rings, extension rings, etc. Include only those parts that are marked with their volumes in cubic inches [314.16(A)] or included in NEC Table 314.16(A).

 

Conductor volume

 

Calculating conductor volume is a matter of adding up individual conductor equivalent volumes-- and there are five such volumes. After you calculate all five volumes using Table 314.16(B), add up them up. The number you get is the total conductor volume. In no case can this exceed the box volume [314.16].

 

In this process, you don’t need to count raceway and cable fittings (including locknuts and bushings), wire connectors, or cable connectors with their clamping mechanism outside of the box. Nor do you need to count conductors that originate and terminate within the outlet box (such as equipment bonding jumpers and pigtails) [314.16(A)].

 

Using Table 314.16(B), calculate each of the five following conductor equivalent volumes:

 

(1) Conductor Volume. Each unbroken conductor that runs through a box, as well as each conductor that terminates in a box, is counted as a single conductor volume. Each loop or coil of unbroken conductor having a length of at least twice the minimum length required for free conductors in 300.14 must be counted as two conductor volumes. Conductors that originate and terminate within the box (e.g., pigtails) aren’t counted at all.

 

You can omit equipment grounding conductors, and up to four 16 AWG and smaller fixture wires, from box fill calculations if they enter the box from a domed luminaire or similar canopy (e.g., a ceiling paddle fan canopy) [413.16(B)(1) Ex].

 

(2) Cable Clamp Volume. One or more internal cable clamps count as a single conductor volume, based on the largest conductor that enters the box. Cable connectors that have their clamping mechanism outside the box aren’t counted.

 

(3) Support Fitting Volume. Each luminaire stud or luminaire hickey counts as a single conductor volume, based on the largest conductor that enters the box.

 

(4) Device Yoke Volume. Each single gang device yoke (regardless of the ampere rating of the device) counts as two conductor volumes, based on the largest conductor that terminates on the device. Each multigang device yoke counts as two conductor volumes for each gang, based on the largest conductor that terminates on the device.

 

A device that’s too wide for mounting in a single gang box, as described in Table 314.16(A), is counted based on the number of gangs required for the device.

 

5) Equipment Grounding Conductor Volume. All equipment grounding conductors in a box count as a single conductor volume, based on the largest equipment grounding conductor that enters the box. Insulated equipment grounding conductors for receptacles having insulated grounding terminals (isolated ground receptacles) [250.146(D)] count as an additional single conductor volume.

 

Total conductorsImage

 

What is the total number of conductors used for the box fill calculations in Figure 5–27?

 

(a) 5 conductors         (b) 7 conductors

(c) 9 conductors         (d) 11 conductors

 

Answer: (d) 11 conductors

 

Switch and conductors                     5 – 14 AWG    †

Receptacles and conductors             4 – 14 AWG    ††

Equipment grounding conductor        1 – 14 AWG

Cable clamps                                  + 1 – 14 AWG

Total                                               11 – 14 AWG

†two conductors for the device and three conductors terminating

††two conductors for the device and two conductors terminating

Each 14 AWG counts as 2 cu in. [Table 314.16(B)].

11 conductors x 2 cu in. = 22 cu in.

 

If the cubic inch volume of the mud ring is not stamped on it, or given in the problem, we cannot include it in the box volume. Without knowing the mud ring volume, a 4 in. square by 21⁄8 in. deep box would be the minimum required for this example.

 

Box Sizing

 

To determine the size of the outlet box when the conductors are of different sizes, follow these steps:

 

Step 1: Determine the number and size of conductor equivalents in the box.

Step 2: Determine the volume of the conductor equivalents from Table 314.16(B).

Step 3: Size the box by using Table 314.16(A).

 

Let’s work an example. What is the minimum size square outlet box required for one 14/3 Type NM cable that terminates on a 3-way switch, and one 12/2 Type NM cable that terminates on a receptacle? The box has internally installed cable clamps.

 

(a) 4 x 1¼ square       (b) 4 x 1½ square

(c) 4 x 21/8 square      (d) any of these

 

Answer: (c) 4 x 21/8 square

Step 1:            Determine the number of each size conductor.

14 AWG

14/3 NM =        3 – 14 AWG

Switch + 2 – 14 AWG

Total    5 – 14 AWG

12 AWG

12/2 NM           2 – 12 AWG

Cable clamp    1 – 12 AWG

Receptacle      2 – 12 AWG

Equipment grounding conductor        + 1 – 12 AWG

Total    6 – 12 AWG

 

All equipment grounding conductors count as one conductor, based on the largest equipment grounding conductor entering the box [314.16(B)(5)].

Step 2:            Determine the volume of the conductors [Table 314.16(B)].

14 AWG          2 cu in. each

2 cu in. x 5 conductors           10 cu in.

12 AWG          2.25 cu in. each

2.25 cu in. x 6 conductors      13.50 cu in.

Total Volume   10 cu in. + 13.50 cu in.

Total Volume   23.50 cu in.

Step 3:            Select the outlet box from Table 314.16(A).

4 x 21/8 square, 30.30 cu in. meets the minimum cu in. requirements.

 

Getting it right

 

Sometimes, you already have a box in place and need to make sure you don’t overfill it. This could easily be the case during remodeling/retrofit work, or following a change order on new construction. Other times, you know how many conductors will go in a given run and you need to make sure you install a big enough box.

 

Either way, you calculate box volume and conductor volume. But you can summarize the whole process this way:

 

  • If conductors are the same size, add them together and size the box using the AWG size columns of Table 314.16(A). Your conductor equivalents will all be the same size as the conductors.
  • If the box contains different sizes of conductors, use Table 314.16(B) to find the area of each conductor, add them up, and size the box from Table 314.16(A) using the cu in. column.

Remember:

  1. Calculating box volume is a matter of adding up individual volumes of assembled parts [314.16(A)].
  2. Calculating conductor volume is a matter of adding up individual conductor equivalent volumes [314.16(B)].

If box fill exceeds box volume, you need to reduce the number of conductors or use a larger box.

 

Keep in mind that these are minimum requirements [90.1]. There’s no penalty for using a box that’s too big, other than the additional cost of that box versus a smaller one. It’s typically more cost-effective on a project to use a smaller quantity of box sizes and have a few that are over-sized, than to calculate the exact minimum needed at every point and try to match them all up in the field.

 

 

 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • Many thanks for the notification of box fill calculations.

    Thanks and regards,

    Kabir.

    Kabir A Rehman
    Reply to this comment

  • Thanks for the article. In the future could there be an article that covers conductors larger than #4 AWG for a splice box / pull box . What is mind is: Retrofit / remodeling with a pullbox above switchgear or a distribution panel having 1/0 wires. this would help in design with the ability to predict the size of the box (ie. 24x36x12) in tight spaces.

    George Marr
    Reply to this comment

  • just got tagged for box fill. first time ever for me. seems you cant put 3 12 ga romexes in a handy box as a junction. This would mean if you calculate it that you cannot put an outlet in a handy box fed with 12 romex and then leave the bow with anothr 12 romex to feed downlin loads. wow didnt realize iI had been doing this wrong for years!!!

    joe stewart
    Reply to this comment

  • also means you cant put a 12 romex to feed a switch and then take a 12 romex out to feed the lite!!!. handy boxes are 2x4x1.875= 15 cu in. you have 4 #12 coductors and 1 for your egc for a total of 5 and a 2 count for your switch for a total of a 7 count x 2.25= 15.75. too much by the size of a cube of sugar!!!

    joe stewart
    Reply to this comment

  • Thank you so much for having everything at my fingertips! I use your website almost 10 times per week for knowledge extension, updates, formulas etc... Thanks again!

    Tom Boos
    Reply to this comment

  • i'm so glad about what u guys doing and it is very important to us specialy for me because i'm from ethiopia. it is quite difference the way we use when wireing the house and completely diffrence the material we use except copper wire. please continue as it is for now thnkyou

    yonas mebrhatu
    Reply to this comment

  • so many times i have just guessed at this. now i will be sure. thank you!

    ron g.

    ron g.
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter