This article was posted 05/16/2008 and is most likely outdated.

2008 NEC Questions and Answers May Part 1
 

 

Topic - NEC Questions
Subject - 2008 NEC Questions and Answers May Part 1

May 16, 2008
This newsletter was sent to 29028 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

NEC Questions Based on the 2008 NEC

May Part 1

 

Here is the follow up to yesterday’s newsletter. This includes all of the answers to the questions sent yesterday so you can see how you did.

 

By Mike Holt, for EC&M Magazine

 

Q1. When adjusting the ampacity of a conductor due to conductor bundling, do we use the 90 degree column ampacity, or the 75 degree column ampacity, when the conductor insulation is THHN?

A1. Conductor ampacity adjustments are based on the conductor temperature insulation rating [110.14(C)]. For example: The ampacity of nine current-carrying 12 THHN conductors in a dry location would be need to be adjusted by a 70 percent adjustment factor [Table 310.15(B)(2)(a)].

Adjusted Conductor Ampacity = 30A [Table 310.16] x 0.70

Adjusted Conductor Ampacity = 21A

 

Q2. Can Type NM cable be installed in a raceway in a ground floor slab?

A2. Maybe. Type NM cable is not permitted to be installed in a wet location [334.12(B)(4)] and a raceway in a concrete slab in direct contact with the earth is considered a wet location [Article 100]. If however, there is a plastic vapor barrier between the earth and the concrete slab, then the raceway would not be located in a wet location.

 

Q3. Does the NEC specify a particular color arrangement for three phase systems?

A3. No, but electricians often use the following color system for power and lighting conductor identification:

120/240V, single-phase—black, red, and white

120/208V, three-phase—black, red, blue, and white

120/240V, three-phase—black, orange, blue, and white

277/480V, three-phase—brown, orange, yellow, and gray; or, brown, purple, yellow, and gray.

 

Q4. If the interior of a panel has overspray from acoustical spray, what do you do?

A4. The panel must be replaced because the internal parts of electrical equipment must not be damaged or contaminated by foreign material, such as paint, plaster, cleaners, etc [110.12(B)]

 

Q5. I have a building that has two services from the utility. Do I have to use the same grounding system for both?

A5. Yes [250.58].

 

Q6. What are the NEC requirements for installing panels in closets??

A6.  Overcurrent devices must not be located near easily ignitible material, such as in clothes closets. According to Article 100, a clothes closet is a nonhabitable room or space intended primarily for storage of garments and apparel.

 

Q7. What is the minimum size feeder/service for a construction trailer?

A7. The feeder/service conductors must have a rating not less than 60A [225.39(D) and 230.79(D)].

 

Q8. What is the smallest size wire you can use for a lighting fixture whip?

A8. Fixture wires as small as 18 AWG are allowed to run from the luminaire to an outlet box, as long as the conductors are not over 6 ft long [410.117(C)] and they are connected to a circuit rated not more than 20A [240.5(B)(2)].

 

Q9. Can I use 14 AWG conductor pigtails from 12 AWG, 20A circuit so that I can back-stab the wires to the receptacle?

A9. No. Branch circuit tap conductors are not permitted for receptacle outlets [210.19(A)(4) Ex No.1 (c)].

 

Q10. Can I run Type NM cable in a raceway outdoors on the building?

A10. No. Cables installed in raceways in above ground wet locations must be listed for use in wet locations [300.9], and Type NM cable is not listed for use in a wet location [334.12(B)(4)].

 

 

 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • Regarding Question #1, Bundled Conductor derating using the 75 oC or 90 oC column, one caveat:

    Even if the wire is rated at 90 oC, like THHN, if either end terminates to lugs of a device rated for a maximum of 75 oC, then the 75 oC ampacities must be used. This is often the case with motor control equipment (combination motor starters) and some breaker panels on the main lugs.

    Jim S. Nasby
    Reply to this comment

  • Your answer to Q2 contradicts your answer for Q10. If it is installed in a raceway (raintight conduit or plastic vapor barrier) is not a wet location. Why would NM cable not be allowed if temp derated for the overprotection of having a raceway that protects it from the elements?

    Q2. Can Type NM cable be installed in a raceway in a ground floor slab?

    A2. Maybe. Type NM cable is not permitted to be installed in a wet location [334.12(B)(4)] and a raceway in a concrete slab in direct contact with the earth is considered a wet location [Article 100]. If however, there is a plastic vapor barrier between the earth and the concrete slab, then the raceway would not be located in a wet location. Q10. Can I run Type NM cable in a raceway outdoors on the building?

    A10. No. Cables installed in raceways in above ground wet locations must be listed for use in wet locations [300.9], and Type NM cable is not listed for use in a wet location [334.12(B)(4)].

    Steven Ray Webb
    Reply to this comment

  • Hi Mike

    Can you tell me the ampacity of the type nm cable installed in a raceway, I was giged on this before because the raceway was from box to box it was not concidered a sleve for protection. thanks

    Mike
    Reply to this comment

  • Q9. Can I use 14 AWG conductor pigtails from 12 AWG, 20A circuit so that I can back-stab the wires to the receptacle? A9. No. Branch circuit tap conductors are not permitted for receptacle outlets [210.19(A)(4) Ex No.1 (c)].

    Pigtailing is so common and required for ground and Neutral(removal of a device cannot interrupt neutral or ground lines) so this is conflicting. Now down sizing is a different story.

    So what gives?

    Kid Stevens
    Reply to this comment

  • Regarding question 3. The answer is essentially correct but their are foot notes so to speak. The wild leg of an open delta 3 phase is coded orange and isolation transformer legs also per NEC are color coded (Health Care Facilities 517). The open delta wild leg ID may be otherwise identified but if color is used I believe it must be orange. However, all 3 phase conductors must be somehow identified for voltage-though color is an alternative for this identification. I'm writing this from memory but I'll try to find exact references if they're needed. To be truthful, I haven't checked the 2008 NEC on the open delta high or wild leg rule.

    Bob
    Reply to this comment

  • ENJOY YOUR CODE QUESTION, FOR US OLD ELECTRICIAN`S,

    CHARLES WINCHELL
    Reply to this comment

  • Regarding color coding. Notice that the traditional coding follows the spectrum left to right. Phase A is black or brown, Then phase B would be red, Phase C would be toward the blue end of the spectrum. If you come across a color code that you're not familiar with, think of the resistor color code which also follows the color spectrum-left to right. This rule is not written in stone but it will help getting motor rotation right the first time.

    Bob
    Reply to this comment

  • FOR QUESTION 2 NM, I WOULD NOT USE IT, ONLY IN DRY LOCATION'S

    DAVID KLEIN
    Reply to this comment

  • In regards to Question #3 - Did the 1975 NEC have a "required" color code, including "required" colors for even switch legs? I have been told this is where these colors originated at by a couple of "old timers". Just wanted to know if this is fact or not.

    Mike Britt
    Reply to this comment

  • On Q2, I understand your reference to the definition Art 100, but I don't think the vapor barrier makes a difference. I think the reason that conduit in a slab is a wet location needs to be uncovered. I have always understood it is the temperature differential that causes the condensation in the conduit resulting in the conduit filling up with water. I don't think the vapor barrier would make a difference.

    Larry
    Reply to this comment

  • Mike:

    IIn the 1950s my father needed power to an enclosure 30 feet away from the house. Not knowing that it was a code violation rans four runs of #12 with #14 ground ROMEX underground to the building. These conductors lasted until 2004 when a gas line developed a leak and the ROMEX was damagfed by a backhoe putting in a new gas line. We replaced the old ROMEX, that looked like new, with type UF cable. Location: Missoula Montana.

    That old NM was tough stuff.

    Mike Stoianoff
    Reply to this comment

  • Thanks , Mike, I always appreciate the extra you do to enhance this industry!

    On Q7. I don"t think we Know enough about this installation. If this were just supplying a single circuit it seems to me 230.31(B) exception would apply giving us a min. of 12awg. Also 230.18 (A) If this were a two circuit installation, 230.18 (B) would apply giving us a 10 awg wire.

    ON Q10. I believe it would depend on where the conduit is run outside the building. A conduit under the eaves or below the sofit would be in a damp location and therefore acceptable.

    On Q4. I don,t see anything that prohibits the cleaning of the componants in this case. I believe the key words in 112.12(C) are "damaged or contaminated" and "internal parts", so I don't believe we are talking about the can. Granted it would depend on how encrusted things were and how you would clean them. Acoustical spray is readily water soluable and aesily remofed by a damp cloth. I would remove the bus assembly and clean it with nothing but a cloth dampened with water, (no solvents allowed) let it dry thoroughly and replace. of course if really encrusted, this could take more time than it is worth. Usually overspray is no harder to remove with a damp cloth than dust.

    On Q6. Depends on what kind of closet it is. if it is a utility closet, requirements of110.26, 230.211, 312.3 would apply.

    On Q9 I agree that according to210.19(A)4(c) this is disallowed but I can't figure out why this would be disallowed on an individual type recept. Can you shed any light on this?

    Wes Gerrans
    Reply to this comment

  • can romex wires in a residential home have paint on the outer insulation,

    jay tankersley
    Reply to this comment


Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter