This article was posted 09/28/2005 and is most likely outdated.

History of two-phase system
 

 
Topic - History
Subject - History of two-phase system

September 28, 2005 

| Ask a Question |  Code Graphic Code Quiz Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
  Web Page Version [Printer-Friendly]    
History of two-phase system

A look back at two-phase power for AC distribution

Thomas J. Blalock


This article describes the first "polyphase" (more than one phase) system developed for the distribution of alternating current (ac) power. This two-phase system was subsequently rendered obsolete, however, by the superior three-phase system that is now universally used throughout the world.

The Origins of Two-Phase Power

Today, the large-scale generation, transmission, and distribution of electric power is by means of the three-phase ac system; that is, three individual single-phase voltages and currents having a 120° phase relationship to each other and intermingled on three wires (excluding a neutral). The three-phase system has been adopted because it provides for a constant rather than pulsating power flow to motors, and because it is an efficient system as far as the amount of copper required per kilowatt transmitted. The theoretical complexity of the three-phase system, however, delayed its complete acceptance in the early days of electric power system development.

During the early 1890s, understanding the behavior of simple single-phase ac was enough of a challenge. It was not until Charles P. Steinmetz, the legendary General Electric scientist, developed the concept of the use of the "j" operator (unity magnitude at a 90° phase angle) and complex numbers for ac circuit calculations that the behavior of voltages and currents in ac circuits and machines was truly understandable. Likewise, it was not until the introduction of what eventually came to be known as "symmetrical components," during the early 20th century, that the calculation of three-phase voltages and currents became relatively straightforward. This technique utilized an "a" operator that was of unity magnitude at a 120° phase angle (–0.5 + j0.866). This operator was of significant value since, in a balanced three-phase system, the voltages and currents are at 120° phase relationships to each other.

Symmetrical components actually facilitated calculations in unbalanced three-phase circuits. They were originally known as "Fortescue components" since the method was introduced in 1918 by Charles L. Fortescue of the Westinghouse Electric Corporation. Significant additional work in this area was later contributed by Edith L. Clarke of the General Electric Company. During the late 19th century, however, this calculation tool did not exist, and the fact that changes in voltage or current magnitudes in one phase of a three-phase system affected the voltages and currents in the other two phases contributed to the difficulty in understanding three-phase circuits.

Thus, the first ventures into the realm of polyphase electric power used only two alternating current phases rather than three. The two phases were generated with a 90° phase difference between them, and the system that resulted was called two-phase power. In fact, the first two-phase generators employed during the early 1890s were merely two single-phase machines coupled together with their rotors carefully set relative to each other so as to achieve the required quadrature phase relationship. Each generator, then, really fed a separate two-wire, single-phase circuit. Since the two phases were completely electrically isolated from each other, there were no interactions between voltage and current magnitudes in one phase with those quantities in the other phase. Therefore, from a theoretical standpoint, the two-phase system was more easily understood than was the three-phase system.

The two phases were used together in a four-wire system to enable the operation of the new Tesla (or induction) motor that had been developed by Nikola Tesla. In order to be self-starting, the Tesla motor required some form of rotating magnetic field that had to be produced by a polyphase type of supply. The two-phase system was adequate for this purpose. The Westinghouse Electric Corporation supplied the power plant and lighting for the Colombian Exposition in Chicago in 1893. Two-phase power, produced by pairs of coupled single-phase generators, was used throughout this installation.

Two-Phase Power at Niagara Falls

The experience gained with the use of two-phase power at the Colombian Exposition may have had some influence on the decision by Westinghouse to employ a two-phase generator design for the first ac powerhouse at Niagara Falls , which went into operation in 1895. The generators used at Niagara Falls were of a more conventional design, being single machines having two interleaved windings rather than two distinct machines coupled together. These generators operated at a frequency of 25 cycles (25 Hz) since it was expected that a significant portion of the power produced would be used to operate rotary converters so as to obtain direct current (dc) for industrial uses such as aluminum production. These early rotary converters required a low frequency for satisfactory operation.

There was obviously still a mistrust of the practicality of three-phase power throughout the electric power industry at that time. For example, according to an 1896 article titled "Present Status of the Transmission and Distribution of Electrical Energy" in the AIEE Transactions :

Where a two-phase transmission with separate circuits is used, then if the separate circuits are wound on different armatures, each can be regulated to give a constant voltage at the receiving end. This is the case, for instance, in the large dynamos built by the Westinghouse Company for use at the World's Fair in Chicago . The difficulty due to the uneven loading of the circuits is specially marked in the case of the three-phase system, and it is one of the principal objections that have been urged against the employment of this system for purposes of distribution.

It had already been realized, however, that the three-phase configuration was superior for transmission from the point of view of efficiency. Thus, special phase-changing transformers were designed by Charles F. Scott of Westinghouse in order to step up the two-phase generated voltage at Niagara Falls to 11,000-V, three-phase for transmission to Buffalo , New York . The General Electric Company was awarded the contract to build the phase-changing transformers and so was licensed by Westinghouse to utilize the connection developed by Scott for this purpose.

At Buffalo , some of this three-phase power was used for rotary converters that supplied 110/220-V dc power for the Edison distribution system downtown. However, some of the received power was converted back into two-phase power for general lighting purposes in outlying areas. Motor- generator sets were used for this latter conversion because the frequency of the ac power was increased as well in order to avoid undesirable flickering of incandescent lamps. The frequency used was actually 62.5 cycles, rather than 60 cycles, so as to simplify the design of these frequency changers. The conversion back to two-phase power was motivated by the conviction, at that time, that satisfactory voltage regulation was more easily achieved in the two separate phases of a two-phase system than in a three-phase system.

This belief in the superiority of two-phase systems with respect to voltage regulation led to the extended use of two-phase distribution in many locales. For example, in Cohoes , New York , (north of Albany ) a 1915 hydroelectric station was designed to generate three-phase power. However, some of that power was converted to two-phase using "Scott" type transformers in order to supply an extensive network of existing two-phase feeders for lighting, rather than change those feeders to three-phase operation.

William Stanley Adopts Two-Phase

William Stanley, the man credited with the first practical application of the ac system using transformers (in Great Barrington, Massachusetts, in 1886), subsequently formed the Stanley Electric Manufacturing Company in Pittsfield, Massachusetts, in 1891. Stanley adhered to the design and construction of two-phase generators and motors throughout the 1890s. This was only partly a result of his belief in the superiority of the two-phase system for voltage regulation purposes. Another factor had to do with the increasing development of three-phase equipment by his major competitors, General Electric and Westinghouse, during the 1890s. Stanley 's decision to manufacture two-phase equipment allowed him to avoid excessive patent infringement problems with his competitors. Regardless of the reasons, however, Stanley contributed to the perpetuation of the use of two-phase power in many locations.

The Stanley Works itself generated and utilized two-phase power. In 1907, this plant became the Pittsfield Works of the General Electric Company, and the two-phase power system that it had inherited from Stanley remained in use until the closing of the facility in 1987. In fact, to this day, there is still one elevator in an old office building there operating with a two-phase motor.

The two-phase system in this plant was somewhat unusual in that it was a three-wire system. One wire from each phase was combined into what was called a "common" wire (not a "neutral"). The advantage in this was the ability to use more commonly available three-pole circuit breakers and switches. A disadvantage, however, was that even with the two phases balanced, the common wire carried 1.414 times the current in the other two phase wires. Thus, economy in pulling circuits through conduits required the use of two different sized cables. Eventually, the plant had two power distribution systems, the original two-phase system and a newer three-phase system. The two systems were interconnected by means of phase-changing transformers. These were of a design by Louis F. Blume of the General Electric Company and utilized a winding configuration differing from the "Scott" connection, presumably to avoid patent conflicts with the Westinghouse Electric Corporation.

Since Stanley supplied equipment to the local municipal power company, the Pittsfield Electric Company, downtown Pittsfield was also served by a two-phase system. This, however, was the more conventional four-wire type of two-phase distribution requiring four-pole service switches. This two-phase distribution system remained in use until the middle of the last century, and vestiges of it in the form of four-pole switches could still be found on the service switchboard of at least one old building in Pittsfield in the early 1980s. Also, two-phase motors were still being used to drive the elevator motor-generator sets in Pittsfield 's only department store when it closed in 1988.

Other Two-Phase Installations

In the village of Middle Falls, New York , (northeast of Albany ) the Niagara Mohawk Power Corporation operated a 1900 vintage, 350-kW Stanley two-phase generator in a small hydroelectric power station there until 1987. Another identical unit had been retired in 1976. The output of the station was coupled to Niagara Mohawk's three-phase grid by means of phase-changing transformers.

The generation of two-phase power was not exclusively an East Coast phenomenon, however. In 1898, the Pacific Light and Power Company installed four 300-kW Westinghouse two-phase generators in a hydroelectric station located in San Gabriel Canyon , near Los Angeles , California . This station served the nearby town of Azusa .

As the use of ac motors expanded during the early 20th century, the problem of providing both l15 V for lighting and 230 V for motor use from two-phase distribution systems became significant. One solution was the adoption of a two-phase, five-wire system in which center taps on both phases were connected together to create a neutral. This, then, resulted in a "star" configuration (analogous to the three-phase "wye" connection) and, technically, was a four-phase system. As such, 115 V (single-phase) for lighting was available from any of the four phase wires to the neutral, while 230 V (two-phase) was available for motors from the four phase wires themselves.

In New York City , the Bronx District of the New York Edison Company adopted this form of secondary distribution around 1925. At that time, the Company was interested in upgrading its existing 2,400-V, two-phase primary distribution system to 13,200 V, three-phase. The connected two-phase motor load, however, was too great to consider changing the secondary distribution system from two-phase to three-phase as well, so "T"-connected (Scott) phase-changing transformer banks were installed to supply a two-phase, five-wire secondary distribution system.

During this era, the use of the three-phase, four-wire wye-connected distribution system was often considered to be unacceptable because of the nonstandard voltage (199 V) between phases with 115 V available from phase to neutral. Early induction motors, designed for operation at 230 V, were less satisfactory when operated on lower voltages than are induction motors of today. The ability of the two-phase, five-wire distribution system to supply the standard voltages of 115/230 V was a main feature in a lengthy article published in the AIEE Transactions in 1925 by an engineer associated with the Philadelphia Electric Company in Pennsylvania. This article justified the continued use of that system.

The Demise of Two-Phase Systems

Eventually, a hybrid type of three-phase distribution system, which was known as a three-phase, four-wire, "delta" system, came into use in certain regions of the United States . This system included a center tap on one phase of a bank of delta-connected transformers supplying 230 V. The center tap formed a neutral and, in conjunction with the two phase wires of that particular phase, was used to supply 115/230 V services on a single-phase, three-wire basis. Motors operating at 230 V were supplied from the three phase wires of this type of service connection.

Buildings requiring both motor and lighting service were sometimes provided with two separate services, a single-phase, three-wire service for lighting and a three-phase, three-wire service for motors. Otherwise, a single four-wire service was brought into a building, but care had to be exercised by electricians so as not to use the odd phase wire along with the neutral to supply lighting loads. This odd phase was referred to as the "high phase" or "wild phase" because considerably more than 115 V existed between it and the neutral. This complication associated with the four-wire delta type of service led to its gradual abandonment during the latter 20th century because fewer and fewer practicing electricians were able to truly understand it. Also, by that time, induction motors had been developed that operated satisfactorily on voltages lower than 230 V. As a result, the three-phase, wye-connected service, giving 208 V between phases and 120 V from phase to neutral, has become the standard commercial type of service. Also, over the years, old two-phase primary distribution systems were gradually replaced with three-phase systems. A common practice became the conversion of a 2,300-V, two-phase, four-wire distribution system into a 4,000/2,300-V three-phase, four-wire system (with neutral).

Several clever and complex plans were devised for the temporary supply of remaining two-phase loads from a new three-phase system, without the expense of purchasing special phase-changing transformers. One such technique took advantage of the fact that there is a 90° phase relationship between one phase-to-phase voltage and the voltage from the third phase to neutral in a three-phase, four-wire system. Customers were encouraged to purchase three-phase motors, rather than add to their existing inventory of two-phase motors. Many of the old motors, however, lasted for quite some time. Occasionally, a customer actually had to be supplied with two services, one two-phase and one three-phase.

With rare exception today, the two-phase distribution system has become a thing of the past. Its extensive use throughout the 20th century, however, created interesting situations for electrical engineers accustomed to three-phase systems. Occasional oversights, resulting from the unrecognized need for four-pole motor control contactors due to the existence of an old two-phase system, have been known to cause havoc for electrical equipment designers and suppliers.

For Further Reading

J.O. Kraehenbuehl and M.A. Faucett, Circuits and Machines in Electrical Engineering . New York : Wiley, p. 268, 1939.

Electrical Transmission and Distribution Reference Book (4th ed.). East Pittsburgh , PA : Westinghouse Electric Corporation, p. 12, 1950.

E.L. Clarke, "Determination of voltages and currents during unbalanced faults," General Electric Rev., pp. 511–513, Nov. 1937.

C. Passer, The Electrical Manufacturers (1875–1900). Cambridge , MA : Harvard, 1953.

L.B. Stillwell, "The electric transmission of power from Niagara Falls ," AIEE Trans. , pp. 444-486, 23 Aug. 1901.

"Present status of the transmission and distribution of electrical energy," AIEE Trans. , vol. XIII, Sept. 1896.

H.G. Stott, "The distribution and conversion of received currents," AIEE Trans ., pp. 125-163, 22 Mar. 1901.

B.R. Connell, "The Hydro-Electric Development of the Cohoes Company at Cohoes , N.Y. ," General Electric Rev ., pp. 340–352, May 1915.

L.F. Blume, "Transformer connections for three-phase to two-phase transformation," General Electric Rev . pp. 552–559, Sept. 1912.

W.A. Myers, Iron Men and Copper Wires: A Centennial History of the Southern California Edison Company . Glendale , CA : Trans-Anglo Books, 1983.

"Distribution for congested areas," Electr. World , pp. 1031-1032, 16 May 1925.

P.H. Chase, "Two-phase, five-wire distribution," AIEE Trans ., pp. 737–749, June 1925.

"Changing from two-phase four-wire to three-phase four-wire distribution," Electric J. , pp. 214–216, June 1923

[ View More Newsletters ] Please Reply With Your Comments

Basic Electrical Theory Textbook
Do you know where electricity comes from? To be able to say yes to that question, you must understand a bit about the physics of matter. What value does a brief study of the nature of matter have for the student of electrical theory? The understanding that comes from that study lays the foundation for understanding electrical theory. Only when you know the theory can you truly have confidence in the practical aspects of your electrical work.
This all new 430-plus page full-color textbook provides hundreds of illustrated graphics, detailed examples, practice questions, practice exams, summaries and a comprehensive practice final exam.  

Product Code: ETFC
Pages: 352
Illustrations: 278
Price: $50.00 each

 
[ Please Reply With Your Comments ] [ View More Newsletters ]

F o r w a r d   t h i s   N e w s l e t t e r   t o   a   F r i e n d !
Do you have a friend, relative, or colleague who you think would be interested in receiving this free newsletter? If so, we encourage you to forward this message along to them. If you received this email from someone else, and wish to receive your own free issues of our newsletter, sign up today!

C o n t a c t    I n f o r m a t i o n
   
 

Copyright © 2002, 2003, 2004, 2005 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Comments
  • Both the two phase five wire and 240/120 volt delta 4 wire high leg distribution systems are supplying service to many customers in Philadelphia.

    John Whitney
    Reply to this comment
  • Reply from: KC   
    I just bought a building in N-E Phili and this is my frist experience with 2 phase power feed. I asked myself "I never see a 4 phase system " When I first saw the 4 pole breaker. Until I look at the power meter , there is only A anc C phase on the read out.

    Now I am stuck , I was the three phase feed but PECO don't know what I am talking about. They keep saying I have it already. Sigh...why they just send someone out ????
    Reply to KC

    Reply from: Mike Holt   
    Post your technical question at our Code Forum, visit www.MikeHolt.com.
    Reply to Mike Holt


  • Am very happy to read your news letter. I am getting a lot of good information from your side to design my woks. Thanks Mr.Mike

    JOHN PHILIP
    Reply to this comment

  • I thought the article on the History of two-phase systems was very interesting. Thanks


    Reply to this comment

  • I ENJOYED THIS ARTICLE. IN 1974 WHEN I WAS IN THE NAVY I WENT TO ELECTRICIANS MATE A SCHOOL. THEY TOLD US ABOUT 2 PHASE SYSTEMS BUT NEVER EXPLAINED THEM AS THE NAVY DID NOT USE THEM. KEEP UP THE GOOD WORK

    MIKE KIRN
    Reply to this comment

  • I REALLY ENJOYED THIS ARTICLE . I REALLY ENJOY THIS SITE. IN 1974 I WAS I ELECTRICIANS MATE A SCHOOL

    I REALLY ENJOYED THIS ARTICLE. IN 1974 WHEN I WAS IN THE NAVY I WENT TO ELECTRICIANS MATE A SCHOOL. THEY TOLD US ABOUT 2 PHASE SYSTEMS BUT NEVER EXPLAINED THEM AS THE NAVY DID NOT USE THEM. KEEP UP THE GOOD WORK

    MIKE KIRN
    Reply to this comment

  • Mike,

    Absolutely outstanding article! I don't know how this material gets to you (like the article on the beginning of the 25 ohm grouding value), but keep 'um coming. I copy all and print at a later date for use in my classes!

    I guess I can express interest by saying; really good stuff!

    W. Ramage, PE
    Reply to this comment

  • Thank You. That was a very interesting report on two phase systems. I have not heard about two phase since the early 70's.

    Dick
    Reply to this comment

  • Thank you I have allways had zero understanding of two phase power. I have run across two phase elevator motors. very old in old navy buildings. Delta high leg three phase is still very much in use in Key West. They still install it all the time. But they were installing fuse panels here 20 years after the rest of the world went to breakers.

    Jim Schiebrel
    Reply to this comment

  • I needed to comment on the excellent article of Two-Phase Systems by Mr. Thomas J. Blalock. I enjoyed his paper and it has made me go back to my technical transformer books and study some of the information that Mr. Blalock has stated. I have also passed this information on to my students in my National Electrical Code Class that I have at the Delaware Technical & Community College. Again, thank-you Mr. Blalock for your very informative message.


    Reply to this comment

  • Mike, The electric rail transit system in Philadelphia was operated at 25 cycles with rotary converters supplying the 630 V DC traction power distribution system. The rotary converters were started from the 630V DC Traction power bus and synchronized to the 25 cycle supply. The signal system power distribution on the Market Street Elevated was at 2300V 25 cycle

    John Whitney
    Reply to this comment

  • Thank you for the interesting article! It reminds me of an opportunity I had in the mid-1980s to tour an old mill building in eastern Pennsylvania. When I came to the service entrance, I couldn't believe what I was seeing! There were four insulated conductors entering the building to an old marble switchboard. Four-bladed (!) knife switches, each with four fuses, were used to protect the feeders. When I went outside, I discovered that utility power was three-phase delta, but in the past the building owner had installed two special transformers, one with four bushings, and one with five, using the "Scott T" connection to convert three-phase power to two-phase power. The transformers were dated 1921! I told the building owner that he would have a real problem finding replacements if these 60+ years old transformers failed! The building was later completely rewired to use a standard three-phase power system. This required that all of the old two-phase motors be replaced. --Jim Cook

    James M. Cook, PE
    Reply to this comment

  • I Think this is all great information. Although, Nikola Tesla was the only and princple inventor of what we call AC generation. Back then, in the late 19th century, it was referred to as "Polyphase Power Generation" which was solely discovered and invented by Nikola Tesla.

    Before the Niagra Falls power generators were installed there was a disagreement wheather to use Westinghouse DC generators Or to use Teslas' Polyphase generators. It was found that DC generators are much easier and less expensive to build. So, DC generators were installed. It wasn't till about 1915 or so that it was decided to replace the DC system to the AC system. That was because it became just as easy to build and expenses were about the same. The defining moment became when it was found that more equipment is needed to transmit DC power efficently. AC power was simply found that the transmission line had far less power loss.

    The bottom line here is history has a bad habbit of not giving credit where credit is due.


    Reply to this comment

  • I work in Philly for over 30 year. I worked on 2 phase in South Philly. You don't hear much about it.Keep up the good work. JJ

    Jack
    Reply to this comment

  • When I was going to Coyne Electrical School in Chicago in 1968 we took a field trip to a generating station somewhere on the south side of the city.

    I distinctly remember the guide pointing to a very old generator in the far corner of the generation room and telling us that it was still in use generating two phase power for the subway system.

    David Turner
    Reply to this comment

  • Beautiful! just beautiful. I always wanted to know what Ugly's was talking about on page 16, under Two-Phase, Four wire. Thanks Mike!

    Enrique Gurdian
    Reply to this comment

  • Mike, again another great article. As an instructor I often have the what is 2 phase questions to field. Lucky for me I had the opportunity to converse with an older sparky who worked with it and helped me to gain some insights to share. Other than that this is the first educational piece I have read to date of 29 years in the trade. I would love to have some drawings of those phase converter transformers. Most of the other items I can envision, but not the ability to go from 120 degree to 90 degree angles. Thanks, this is a very good and to the point article. JD White

    JD White
    Reply to this comment

  • Boy does this bring back memories. When I started out as an electrician for Westinghouse Electric Corp. in Bloomfield NJ,about 40 years ago, they had a 5 wire two phase system in their plant. You always had to be aware of the high leg when dealing with the neutral. After a while we were hanging phase converters all over the plant as newer 3 phase equipment was purchased.

    John J. Madia
    Reply to this comment

  • An excellent treatise on the history of electricity from te motor and generator standpoint and two phase systems. I have such a requirement and run 3 phase motors inside my trailer for an air compressor that I attain 5 hp 2 phase performance from a 3 hp 3 phase motor. Since almost all residential configurations employ this 180° split phase 240 VAC system, and my trailer lives in a residential environment, I convert the 240 VAC to 384 VDC and phase compute the 3 phase system using a GE controller. The benefit is a system I can tailor to keeping the 3 phase motor within specs and running at peak efficiency.

    Most people thought I was nuts to do this when I started this but I am running with 4 hp performance from a compressor using a 3 hp electric motor. Its quiet, runs up quickly and with keeping within its specs, runs cool to the touch. I couldnt do this with a split phase motor.

    Cheers,

    GasMan
    Reply to this comment

  • Very Interesting Indeed... Should be required reading for all EE students. How about a history of 6.6-amp street lighting ? Thanks.

    Jim Green
    Reply to this comment

  • Interesting; When I started out in the early 70,s building machine tool control, we had a transformer bank for converting 3 phase to 2 phase. If a machine was to be shipped to an area which had only 2 phase available, it still had to be tested. I never remember it being put to use, but the old timers could not be convinced to get rid of it.

    Roger Roossinck
    Reply to this comment

  • The proper term is 3-wire single-phase for the most common residential (and light commercial) electrical delivery method in the USA.


    Reply to this comment
  • Reply from: Mike Holt   
    I think you are confused about what the artice was discussing. Please read it again.
    Reply to Mike Holt



Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter