This article was posted 02/01/2008 and is most likely outdated.

Article 450: Transformers and Transformer Vaults
 

 

Topic - NEC
Subject - Article 450: Transformers and Transformer Vaults

February 1, 2008
This newsletter was sent to 28106 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 450: Transformers and Transformer Vaults

By Mike Holt for EC&M Magazine

 

Keep transformers cool, safe, and reliable.

 

The operation of any facility depends on power distribution, which in turn depends on transformers. Safe and reliable operation of transformers is crucial, and that’s where Article 450 comes in.

 

Part I of Article 450 contains general requirements such as guarding, marking, accessibility, and ventilation. Part II contains the requirements for different types of transformers, and Part III provides the requirements for transformer vaults.

 

Article 450 opens by telling you that it applies to the installation of all transformers, but then it immediately lists eight exceptions. Given the amount of exceptions, what’s left? The three most common areas of application: power transformers, most kinds of lighting transformers, and transformer vaults. It also covers transformers that are dedicated to supplying fire pumps, except as modified by Article 695.

 

Our discussion will focus on systems that are 600V or below (secondary side), although Article 450 also applies to secondary systems of more than 600V.

 

Read the label

 

Every transformer comes with a nameplate that identifies:

  • Manufacturer.
  • Rated kVA.
  • Primary and secondary voltage.
  • Impedance (if 25 kVA or larger).
  • Required clearances (if it has ventilating openings).

Manufacturers provide this nameplate to comply with 450.11. The information on the nameplate tells you what you’re working with. Make sure the drawings and other references match that information. If there’s a conflict, either you have the wrong transformer or your references are wrong.

 

Accessibility

 

Transformers must be readily accessible to qualified personnel for inspection and maintenance [450.13]. But you don’t need to make dry-type transformers readily accessible, if you locate them:

  • In the open on walls, columns, or structures.
  • Above suspended ceilings or in hollow spaces of buildings. Transformers installed in that space, however, must be rated not more than 50 kVA, and can’t be permanently closed in by the structure.

Stay cool

 

Although overheating is a core issue with transformers, the NEC doesn’t completely address it, because the NEC isn’t a design manual [90.1].

 

Selecting the right transformer for the application is the first step in addressing the heat issue. The NEC doesn’t tell you how to do this, because it assumes you have made the proper selection in the design of the system. With Article 450, the NEC takes you to the next step in the process of protecting the transformer against overheating: providing overcurrent protection. The Code also addresses other transformer and vault factors that determine whether you have a safe installation.

 

Overcurrent Protection

 

To protect the primary winding of a transformer against overcurrent, use the percentages listed in Table 450.3(B) and its applicable notes. Typically the Code places the requirements for over 600V installations after the less than 600V rules, but not for transformers, so be careful not to use Table 450.3(A) when you need to use Table 450.3(B). Remember that Article 450 is for the protection of the transformer windings, and not the conductors supplying the transformer or leaving the transformer. When using Table 450.3(B), you will notice that there are two main options: primary protection only, and primary and secondary protection. Secondary protection is very seldom required, so we will concentrate on primary only protection in this discussion.

 

Where 125 percent of the primary current doesn’t correspond to a standard fuse or nonadjustable circuit breaker, you can use the next higher rating of overcurrent device, as listed in 240.6(A). This note only applies to currents of 9A or more, however.

 

Let’s see if you can apply that table. Here’s a practice question.

 

What primary overcurrent device rating and conductor size do you need for a 45 kVA, three-phase, 480V—120/208V transformer that will operate at its full rating continuously? Terminals are rated 75°C.

 

(a) 8 AWG, 40A                       (b) 6 AWG, 50A

(c) 6 AWG, 60A                       (d) 4 AWG, 70A

 

Answer: (d) 70A

 

Step 1. Primary current

I = VA/(E x 1.732)

I = 45,000 VA/(480V x 1.732)

I = 54A

 

Step 2. The primary overcurrent device rating [240.6(A)]

54A x 1.25 = 68A, next size up 70A [Table 450.3(B) Note 1]

 

Step 3. Size the primary conductor to carry 54A continuously (54A x 1.25 = 68A) [215.2(A)(1)]. Protect it with a 70A protection device [240.4(B)]. A 4 AWG conductor rated 85A at 75°C meets all of the requirements [110.14(C)(1) and 310.16].

 

Step 4. Secondary current

I = VA/(E x 1.732)

I = 45,000 VA/(208V x 1.732)

I = 125A

 

If the secondary conductors are no longer than 25 ft, and they terminate in an overcurrent device that doesn’t exceed the ampacity of the conductors, size them at 125 percent of the continuous load [215.2(A)(1) and 240.21(C)(6)].

 

Try another question:

 

What size secondary conductors are required for a 45 kVA, three-phase, 480V—120/208V transformer that supplies a 200A panelboard that is continuously loaded? Terminals are rated 75°C.

 

(a) 1 AWG       (b) 1/0 AWG    (c) 2/0 AWG    (d) 3/0 AWG

 

Answer: (c) 2/0 AWG

 

Step 1. Secondary current

I = VA/(E x 1.732)

I = 45,000 VA/(208V x 1.732)

I = 125A

 

Step 2. Size secondary conductors to 125 percent of the continuous load [215.2(A)(1)].

125A x 1.25 = 156A, 2/0 AWG rated 175A at 75°C termination

 

Secondary conductors must terminate in an overcurrent device that doesn’t exceed the ampacity of the conductors [240.21(C)(6)]. 2/0 AWG, rated 175A at 75°C, terminating on a 175A overcurrent device meets this requirement.

 

Transformer Ventilation

 

Transformer ventilation requirements [450.9] can be summed up as follows:

  • Provide enough ventilation so the transformer doesn’t overheat.
  • Make sure the openings aren’t blocked by walls or other obstructions.
  • Install per the manufacturer’s instructions.

The Fine Print Notes (FPNs) in 450.9 help address the heating issue. The first FPN recommends a couple of related standards. The second FPN, as well as 450.3 FPN No.2, tells you that transformers can heat up beyond their rating because of odd triplen harmonic currents (3rd, 9th, 15th, etc).

 

The heating from harmonic currents is proportional to the square of the harmonic current. This means the third (3rd) harmonic currents (180 Hz) cause heat at nine times the rate of 60 Hz current.

 

Vault ventilation

 

When designing and locating a transformer vault, do your best to ventilate it to the outside air without using flues or ducts [450.41]. Other considerations may apply, and design compromises might make some or all such ventilation impractical. In that case, the NEC allows you to use flues and/or ducts. Ventilating ducts must be of fire-resistant material [450.45(F)].

 

Locate ventilation openings as far as possible from doors, windows, and combustible material [450.45]. A vault ventilated by natural circulation must have no more than 50 percent of the total opening area near the floor, with the remainder of the opening area in the roof or sidewalls near the roof [450.45(B)]. For a vault ventilated by natural circulation, the total opening area must be at least 3 sq in. per kVA capacity. In no case can the area be less than 1 sq ft for 50 kVA or less [450.45(C)].

 

Cover ventilation openings to avoid unsafe conditions. You can use durable gratings, screens, or louvers to provide this protection [450.45(D), but if you have indoor ventilation openings, you must provide them with automatic closing fire dampers rated not less than 11⁄2 hours [450.45(E)]. These must close in response to a vault fire. See ANSI/UL 555-1995, Standard for Fire Dampers [450.45 FPN].

 

Vault Construction

 

The floors, walls, ceilings, and roofs of vaults must have adequate structural strength with a minimum fire resistance of 3 hours, such as 6 in. thick reinforced concrete [450.42]. Provide each vault doorway with a tight-fitting door with a minimum fire-resistance rating of 3 hours [450.43(A)]. This minimum fire resistance (for the vault and the door) drops to one hour, where an automatic sprinkler system protects the vault.

 

Vault doors must [450.43(C)]:

  • Swing out.
  • Be equipped with panic bars or pressure plates so the door can open from inside under simple pressure.
  • Be provided with locks that are accessible only to qualified persons.

Not a U-Store-It

 

Don’t allow the vault to double as a storage room [450.48]. Many occupants believe that “electrical things” like lamps belong in a vault, and the “unused space” is ideal for storing paper files. Actually, that “unused space” is very much in use—for cooling the transformers.

 

Filling vault space with combustibles (or items that may explode) defeats one purpose of having a vault. Making it a storage room defeats another purpose of having a vault, which is keeping people and transformers separated. The deposit and retrieval aspects of storage mean unnecessary exposure to possible hazards, such as arc blast.

 

An architect might think the vault is a handy place to locate a water heater or phone closet. If so, get the drawing changed. Nothing unrelated to the transformers can go in a vault. Not even piping, except for vault fire protection or cooling [450.47].

 

Most of the Article 450 requirements are aimed at keeping transformers cool and away from people. . That effort doesn’t begin or end with the NEC, however, understanding and correctly applying Article 450 is a crucial part of that effort. When you begin  determining where transformers will be installed, vaulted, or ventilated, evaluate all of your options against the requirements of Article 450.

 

Table 450.3(B) Primary Protection only

 

            Primary Current Rating           Maximum Protection

            9A or More                              125%, see Note 1

            Less Than 9A                          167%

            Less Than 2A                          300%

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • TABLE 450.3B. THE SECOND METHOD PRIMARY AND SECONDARY PROTECTIN, WHEN IS THIS METHOD REQUIRED? I USUALLY USE METHOD ONE BUT A CO WORKER QUESTION ME THAT THIS IS NOT ENOUGH THAT USING 250% AT THE PRIMARY IS RIGHT TO ALLEVIATE NUISANCE TRIPPING.

    ANEROM
    Reply to this comment
  • Reply from: Mike Holt   
    No reason to use 250% on primary, just size secondary at 125%; nuisance tripping is not a problem with transformers. Why 250% in Code, well maybe you want to supply multiple transformers from with a primary tap.
    Reply to Mike Holt


  • Mike-see the excellent paper by Bob Fuhr

    [PDF]Power Quality and Protective Device Cordination ... Table P2-2 Inrush Values for Siemens Dry Type Transformers ... Overcurrent protection of transformers rated 600 volts, nominal, or less shall comply with ...

    www.powerstudies.com/articles/PDC_Currents.pdf - Similar pages

    http://www.powerstudies.com/articles/PDC_Currents.pdf

    wyatt
    Reply to this comment

  • regarding heating by third harmonic currents - all currents, including fundamental and upper harmonics, cause heating proportional to the square of current, not the square of the harmonic frequency. The third is no better or worse than any other (except for skin effects). Using RMS measurement takes all this into account.

    glenn robinson
    Reply to this comment

  • 125% sizing of that 70A pri. OCPD may allow a trip on transformer inrush. NEC allows up to 250% for this reason. Rec. at least 150%

    Wyatt
    Reply to this comment

  • Note that the vault requirements only apply if you choose to provide a vault - a vault is not always required and will depend on the transformer type

    paul highley
    Reply to this comment

  • I think it is short sighted to think of the OCPDs for the transformer without thinking of the secondary conductor protection. 240.21(C)(1) pertains to the secondary conductors and seems to require secondary protection because of the multiphase 4 wire secondary. Most installations wouldn't fall into the "industrial installation", so 10' to the OCPD on the secondary may be a better legnth to consider.

    Ron
    Reply to this comment

  • Great article. I will use this to help explain a typical transformer installation to some of my students.

    Bob
    Reply to this comment

  • Transformer primary over current per Table 450.3(B):

    To avoid nuisance tripping I set the primary over current device at 250% of the full load amps and the secondary over current device at 125% of the secondary full load amps. Thus in the case of the 45-KVA 480/120/208 3-phase transformer the primary over current device would be 150-amps and the secondary over current device would be 150-amps. Per Table 450.3(B) note #3 the primary over current device could be set as high as 600% FLA (400-amps). This might be used to supply power to a fire pump.

    Michael Stoianoff
    Reply to this comment

  • There is always some magnetizing current in excess of the operating current on start up of the transformer regardless of what primary overcurrent device we select. Table 450.3(B) allows for the primary overcurrent protection to be sized at 250% of rated primary current to address this issue for both primary and secondary protection. If the overcurrent device for primary only protection is set at 125% of rated primary current the risk of overcurrent tripping is higher on start up.

    The more important point is that we size the primary conductor so that the overcurrent device selected can protect it. If we select 250% of the rated primary current as the maximum setting for the primary overcurrent device, then we would still need to protect the conductor based on 240.4, not on 125% or the rated primary current. Essentially, the conductor will have to “match” the overcurrent device selected.

    Samuel Alexander
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter