This article was posted 11/29/2007 and is most likely outdated.

Transformer Secondary Conductors
 

 

Topic - NEC
Subject - Transformer Secondary Conductors

November 29, 2007
This newsletter was sent to 27591 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Transformer Secondary Conductors

By Mike Holt for EC&M Magazine

 

Don’t let transformer secondary rules get you wound up.

 

A transformer secondary conductor is similar to a feeder tap, which we covered in the previous issue. The rules for transformer secondary conductors are in 240.21(C). And, they can be every bit as confusing as those for feeder taps.

 

Basic rules

 

As with feeder taps, you can’t use the “next size up OPCD” rule provided in 240.4(B) for any transformer secondary conductor. Normally, you can use the next highest OCPD above the ampacity of the conductors being protected. But not with transformer secondary conductors.

 

The rule is the same because the physics are the same. As with feeder taps, the sizing of that transformer secondary conductor depends on its length and application.

 

Scenarios

 

When we demystified feeder taps in the previous issue, we presented the information in an arrangement that differs from what you see in the NEC. We also described an easy way to pick the correct scenario from the five possible. That same tip applies to transformer secondary conductors, which also have five scenarios.

Here are the scenarios:

  1. Scenario One: Secondary conductors from a feeder-tapped transformer.
  2. Scenario Two: Outside secondary conductors.
  3. Scenario Three: Secondary conductors not over 10 feet long.
  4. Scenario Four: Secondary conductors 10 to 25 feet long.
  5. Scenario Five: Secondary conductors 10 to 25 feet long, industrial installation.

To pick the right one, answer three easy questions:

  1. Is the transformer outside? Choose Scenario Two.
  2. Is the secondary conductor under 10 feet long or between 10 and 25 feet long? Choose Scenario Three or Four, but choose Scenario Five if it’s an industrial installation.
  3. Is the transformer supplied by a feeder tap? Choose scenario one.

Scenario One: Secondary conductors from a feeder-tapped transformer

This one is simply a reference to 240.21(B)(3). So apply 240.21(B)(3) if you have a tap-supplied transformer.

Scenario Two: Outside secondary conductors

Outside secondary conductors can be of unlimited length, without overcurrent protection at the point they receive their supply, if they:

  • Are suitably protected from physical damage in a raceway or manner approved by the authority having jurisdiction (AHJ).
  • Terminate at a single circuit breaker (or a single set of fuses) that limit the load to the ampacity of the conductors.

Also:

  • The OCPD for the ungrounded conductors must be an integral part of a disconnecting means or located immediately adjacent to it.
  • The disconnecting means must be located at a readily accessible location near the point of entrance of the conductors.

Scenario Three: Secondary conductors not over 10 feet long

 

You can install secondary conductors up to 10 ft long, without overcurrent protection at the point they receive their supply, if they have an ampacity that is not less than:

  • The calculated load per Article 220.
  • The rating of the device supplied by the secondary conductors or the OCPD at the termination of the secondary conductors, and
  • One-tenth the rating of the OCPD (protecting the primary of the transformer) multiplied by the primary-to-secondary transformer voltage ratio.

Also:

  • The secondary conductors must not extend beyond the switchboard, panelboard, disconnecting means, or control devices they supply.
  • The secondary conductors must be enclosed in a raceway.

Overcurrent protection is not required on the secondary side of the transformer to protect the secondary conductors, but overcurrent protection is required for branch-circuit panelboards. This OCPD must be on the secondary side of the transformer, and typically it’s within the panelboard. The FPN under 240.21(C)(2)(3) says to see 408.36 for the overcurrent protection requirements for panelboards.

 

Scenario Four: Secondary conductors 10 to 25 feet long.

 

You can install secondary conductors up to 25 ft long, without overcurrent protection at the point they receive their supply, if they:

  • Have an ampacity that is at least the value of the primary-to-secondary voltage ratio multiplied by one-third of the rating of the OCPD that protects the primary of the transformer.
  • Terminate in a single circuit breaker (or set of fuses) rated no more than the secondary conductor ampacity per 310.15 [Table 310.16].
  • Are protected from physical damage by being enclosed in a manner approved by the AHJ (such as within a raceway).

Scenario Five: Taps 10 to 25 feet long, industrial installation.

 

In an industrial application (only), you can install secondary conductors up to 25 ft long, without overcurrent protection at the point they receive their supply if:

  • The ampacity of the secondary conductors is at least the value of the secondary current rating of the transformer.
  • The sum of the ratings of the secondary OCPDs doesn’t exceed the ampacity of the secondary conductors.
  • The secondary OCPDs are grouped.
  • The secondary conductors are protected from physical damage by being enclosed in a manner approved by the AHJ (such as within a raceway).

Test yourself

 

Now, let’s see if you can put all this together to solve a practice problem. Question: What is the minimum size 15-foot secondary conductor required for a 2-wire, 480V to 120V indoor transformer rated 1.50 kVA in an office installation?

 

(a) 16 AWG     (b) 14 AWG     (c) 12 AWG     (d) 10 AWG

 

Answer: (b) 14 AWG

 

Why is (b) the correct answer? Based on those two easy questions, you select Scenario Four. Then, you size the secondary to comply with Scenario Four requirements.

To calculate the primary OCPD size, we need to first calculate the primary current. To do that, we need to know a couple of things:

  • VA = 1,500 VA
  • E = 480V

Now we can calculate primary current:

  • Primary Current = VA/E
  • Primary Current = 1,500 VA/480V
  • Primary Current = 3.13A

Now we can calculate primary protection. Per 450.3(B), it has to be 167% of the primary current. So, 3.13A x 1.67 = 5.22A. We can’t apply the next size up rule, so we need a 5A OCPD.

To calculate the secondary conductor size:

  • Determine the primary to secondary voltage ratio: 480/120 = 4.
  • Multiply the primary OCPD size by 1/3: 5/3 = 1.67.
  • Multiply the two values together: 4 x 1.67 = 6.67A.
  • Look in the 60ºC, Table 310.16 for the smallest conductor with an ampacity larger than 6.67A.

Answer: 14AWG.

If you want more practice, try changing the transformer in the example above, and try different scenarios. For example, what if this is an industrial installation? Then, do the same thing but choose Scenario Five. You might find it useful to spend a few minutes trying variations. This will help you better understand transformer tap conductor rules. They aren’t difficult, if you can approach them methodically and apply those that fit your installation.

If those confusing transformer secondary rules have ever tripped your personal breaker, that’s understandable! But now you can steer through those rules with confidence. The next time you need to size secondary conductors, stop to answer a couple of easy questions. Then, select the correct scenario for your installation.

 

With some transformer secondary conductors, you can use the primary OCPD to provide the  overcurrent protection (just as you use the feeder OCDP to protect the feeder tap conductors). But, there’s a catch: you can do this only for two specific transformer configurations. Those are:

  • Single-phase transformer with 2-wire (single voltage) secondary.
  • Three-phase delta-delta transformer with 3-wire (single voltage) secondary.

And:

  • The OCPDs for those transformers must be sized per Article 450.
  • The secondary conductors must meet the sizing minimum required by the installation type described in 240.21(C).

 

Due to the unfortunate convergence of content arrangement and the NEC numbering system, the rules for outside secondary conductors can appear to blend right in with those for those for a feeder-tapped transformer (which the NEC lists after the ones for outside secondary conductors). That’s another reason to think in terms of scenarios. This allows you to quickly pick the relevant requirements.

 

 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • Scenario Three: Secondary conductors not over 10 feet long: ... "but overcurrent protection is required for branch-circuit panelboards". Rebuttal: This is to generic, Section 408.36 (D) requires that a "lighting and appliance" branch-circuit panelboard supplied through a transformer have overcurrent protection located on the secondary side of the transformer. A lighting and appliance branch circuit is a branch circuit that has a connection to the neutral of the panelboard and that has overcurrent protection of 30 amperes or less in one or more conductors. A lighting and appliance branch-circuit panelboard is one having more than 10 percent of its overcurrent devices protecting lighting and appliance branch circuits. Secondary protection isn't required for a Power Panelboard except where it has supply conductors that include a neutral, and have more than 10 percent of its overcurrent devices protecting branch circuits rated 30 amperes or less.

    Chuck Bailey
    Reply to this comment

  • I enjoyed reading something in an organized form that discusses a topic that can be confusing.

    I would like to make one comment and ask a question about Scenario Four:

    Articles 240 and 450 need to be referenced when tapping transformer secondaries.

    Article 240 addresses overcurrent protection for conductors. Article 450 addresses overcurrent protection for transformers and the number of OCP devices on the secondary.

    240.21(C) FPN refers to 450.3 for overcurrent requirements for transformers. 240.3(C) states that "Each set of conductors feeding separate loads shall be permitted to be connected to a transformer secondary, without overcurrent protection at the secondary, as specified in 240.21(C)(1) through (C)(6). The provisions of 240.4(B) shall not be permitted for transformer secondary conductors." The FPN for 240.3(C) states "For overcurrent protection requirements for transformers, see 450.3"

    Table 450.3(B), Note #2, allows up to 6 taps from the transformer secondary.

    Table 450.3(B) Note #1 appears to be in conflict with 240.21(C), "Where the required fuse rating or circuit breaker setting does not correspond to a standard rating or setting, a higher rating or setting that does not exceed the next higher standard rating or setting shall be permitted."

    So, is the next standard setting allowed?

    Rodney Welch
    Reply to this comment

  • The code rules always go into great detail on allowable primary and secondary feeder and OCPD sizing, but never allow, or state the need to allow for Magnetizing Inrush on the transformer. I've talked with many transformer manufacturers over the years, and all have said they can't guarantee that the magnetizing inrush of the transformer won't trip the feeding breaker on startup unless that breaker is sized at least 125% of the transformer full load current rating. I've had many instances that this has been confirmed as a problem, although generally anything much over 110% has not tripped the breaker. I would think the code would make some comment or allowance for this known transformer parameter.

    Don Barker
    Reply to this comment

  • thank you for that easy to understand info!

    jimmy
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter