This article was posted 05/02/2007 and is most likely outdated.

Article 215: Feeders
 

 
Topic - NEC
Subject
- Article 215: Feeders

May 2, 2007
This newsletter was sent to 25238 newsletter subscribers
 

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 215: Feeders

By Mike Holt for EC&M Magazine

 

Feeders occupy the “between space” in power distribution.

 

Last month, we looked at branch circuit requirements in Article 210. The next logical step up from the branch circuit is the feeder circuit. Thus, Article 215, which provides the requirements for sizing and installing feeders (see Sidebar), follows Article 210.

 

The difference in length between Article 215 and Article 210 may seem puzzling, at first glance. And why have a separate Article just for feeders, anyhow?

 

This is an object lesson in the value of Article 100. A quick review of the definitions of “branch circuit” and “feeder” helps us see why a separate Article is necessary and why Article 215 is so much shorter than Article 210.

 

The main difference is that a feeder runs between an overcurrent protection device (OCPD) at the supply and a downstream OCPD (typically supplying a branch circuit), while a branch circuit runs between an OCPD and an outlet (or final load). In other words, a feeder supplies power to a branch circuit OCPD—which in turn powers a branch circuit. But you size that branch circuit OCPD based on branch circuit load calculations (and outlet requirements), not on feeder calculations.

 

Because a feeder occupies this “between space” in power distribution, feeder requirements are simpler and fewer than branch requirements. Consequently, Article 215 is much shorter than Article 210.

 

Article 210 also devotes extensive space to dwelling-area branch circuits. But because they occupy the “between space” in power distribution, feeders have minimal requirements for dwellings [215.2(A)(3)].

 

Minimum Rating

 

Determine the minimum feeder conductor size, before you apply any conductor adjustment and/or correction factors, by adding the two following quantities:

  1. 125 percent of the continuous load [215.2]
  2. 100 percent of the noncontinuous load.

Once you have the total load, you size the minimum conductor required to carry that load based on the terminal temperature rating ampacities as listed in Table 310.16 [110.14(C)]. You size the OCPDs, based on this same ampacity [215.3 and 240.4].

 

Here’s a pop quiz to see if you can size a feeder. What size feeder conductor do you need for a 200A continuous load, if the terminals are rated 75ºC?

 

(a) 2/0 AWG    (b) 3/0 AWG   (c) 4/0 AWG   (d) 250 kcmil

 

How do we determine the correct answer? Since the continuous load is 200A, the feeder conductors must have an ampacity at least 250A (200A x 1.25). Using the 75ºC column of Table 310.16, we find that 250 kcmil conductors are suitable because they have an ampere rating of 255A at 75ºC. Thus, “d” is the correct answer.

 

There is an exception to the 125% rule. Where the assembly and the OCPD are both listed for 100 percent continuous load operation, you can size the feeder conductors at 100 percent of the continuous load. Note that equipment suitable for 100 percent continuous loading is rarely available in ratings under 400A.

 

The feeder grounded (neutral) conductor must not be smaller than the size listed in Table 250.122, based on the rating of the feeder OCPD.

 

Test your knowledge, with another pop quiz. What size grounded (neutral) conductor do you need for a feeder consisting of 250 kcmil ungrounded conductors and one grounded (neutral) conductor protected by a 250A protection device, where the unbalanced load is only 50A, with 75ºC terminals?

 

(a) 6 AWG       (b) 4 AWG      (c) 1/0 AWG   (d) 3/0 AWG

 

Table 310.16 and 220.61 would permit an 8 AWG grounded (neutral) conductor, rated 50A at 75ºC to carry the 50A unbalanced load. But Table 250.122 requires that the grounded (neutral) conductor not be smaller than 4 AWG. So, the correct answer is “b.”

 

You also have to consider the size of the service conductors, when you size feeder conductors. Feeder conductors for individual dwelling units or mobile homes needn’t be larger than service conductors sized per 310.15(B)(6).

 

For the sake of efficiency, you should size the conductors to minimize voltage drop. Doing so is an engineering consideration, not an NEC requirement [215.2(A)(3) FPN No. 2].

 

High-leg identification

 

On a 4-wire, delta-connected, three-phase system, where the midpoint of one phase winding is grounded, the conductor with the highest phase voltage-to-ground (208V) is called the high-leg.

 

Panelboards supplied by a 4-wire, delta-connected, three-phase system must have the high-leg conductor (208V) terminate to the “B” (center) phase of a panelboard [408.3(E)] (this has been a rule since 1975). An exception to 408.3(E) permits the high-leg conductor to terminate to the “C” phase when the meter is located in the same section of a switchboard or panelboard.

 

Ensure this high-leg conductor is durably and permanently marked with an orange outer finish at each point a connection is made where the grounded (neutral) conductor is present [110.15]. The NEC says you can use “other means” but doesn’t provide further detail. Get permission from the Authority Having Jurisdiction (AHJ) to use some “other means.”

 

Ground-fault protection of equipment

 

Article 100 tells us that “Ground-Fault Protection of Equipment” systems interrupt power to protect equipment, but at lower current levels than  those required to protect conductors through the operation of a supply circuit overcurrent device.

 

Each solidly grounded wye electrical 277/480V feeder disconnecting means rated 1,000A or more must be provided with ground-fault protection of equipment, and the installation must comply with 230.95 or 240.13 [215.10].

 

If ground-fault protection is on the supply side of the feeder, you don’t have to also provide it on the load side. Nor do you have to provide it for emergency systems [700.26] or legally required standby systems [701.17].

 

Never apply ground fault protection to fire pumps [695.6(H)]. Fire pumps must run no matter what—it makes no sense to save the pump but burn down the building.

 

Identification

 

The grounded (neutral) conductor of a feeder must be identified per 200.6 [215.12(A)].

 

The equipment grounding conductor must be identified per the requirements of 205.119. But, it’s not really a grounding conductor. It’s actually a bonding conductor.

 

This conductor creates a low impedance path between metallic objects. Because of the low impedance, the voltage differential between objects is low. The result is an equipotential plane between objects bonded by the equipment grounding (bonding) conductors. Equipment grounding (bonding) conductors:

  • Can be bare, or individually covered or insulated.
  • Sized 6 AWG and smaller that are insulated must have a continuous outer finish that is either green or green with one or more yellow stripes [250.119].
  • Larger than 6 AWG and insulated can be permanently reidentified with green marking (at the time of installation) at every point where the conductor is accessible [250.119(A)].

Ungrounded Conductors

 

Where the premises wiring system contains feeders supplied from more than one voltage system, each ungrounded conductor (where accessible) must be identified. Identification can be by color-coding, marking tape, tagging, or other means approved by the AHJ. System identification must be permanently posted at each feeder panelboard or similar feeder distribution equipment.

 

Service conductors supply power to the service equipment, and feeders run from the service equipment to the branch OCPD. Feeders are the “between circuits” that occupy the “between space” in power distribution. Keeping this in mind will help simplify your feeder work.

 

What’s a Feeder?

 

Article 100 defines feeders as: “All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch circuit overcurrent device.” The clumsiness of this wording makes this definition hard to follow.

 

An easier way to look at it is this: “The circuit conductors that supply power to a branch circuit overcurrent device or to a panel that contains such devices. The power may come from the service equipment, a separately derived system, or other power supply source.”

 

Color system

 

Electricians often use the following color system for power and lighting conductor identification:

  • 120/240V single-phase—black, red, and white
  • 120/208V, three-phase—black, red, blue, and white
  • 120/240V, three-phase—black, orange, blue, and white
  • 277/480V, three-phase—brown, orange, yellow, and gray; or, brown, purple, yellow, and gray.

 

Table 250.122—Minimum Size Equipment Grounding (Bonding) Conductor

            Protection         Copper

            Rating               Conductor

            15A                  14 AWG

            20A                  12 AWG

            30—60A            10 AWG

            70—100A          8 AWG

            110—200A        6 AWG

            225—300A        4 AWG

            350—400A        3 AWG

            450—500A        2 AWG

            600A                 1 AWG

            700—800A        1/0 AWG

            1,000A              2/0 AWG

            1,200A              3/0 AWG

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • Thank yyyooouuuu!!! for the clarifications.

    God has given you a talent of helping others understand what others say... please keep up the Good work!!

    Troy Watkins
    Reply to this comment

  • Table 250.122 identifies the minimum size equipment grounding conductors for grounding raceways and equipment. What section of the code requires Table 250.122 to apply to the grounded (neutral) conductor?

    Tony
    Reply to this comment

  • Although automatic ground fault protection is not required on emergency systems protection still required by providing a an indicator simuliar to undgrounded systems in industry. See section 700.7 (D);700.7(D) NEC. There is no requirement of the same on LRS in section 701.17, probably should be addressed as the hazard still remains the same.

    Jim Yancey-NCDOI_OSFM Engineering Code Consultant jyancey@ncdoi.net

    Jim Yancey-NCDOI
    Reply to this comment

  • Hey Mike, On this one you state that the requirement for voltage drop considerations is a FPN in the NEC. All in all that is the standard, but inspectors in Florida need to know requirements for installations are required to factor in compliance for voltage drop; look in the the revisions to the FBC 2004.

    Tom O
    Reply to this comment

  • Hi Mike,

    Re: Article 215: Feeders on 5.2.07 - Your comments Re: Test your knowledge - "Sizing the neutral conductor". You stated "But Table 250.122 requires that the grounded (neutral) conductor not be smaller than 4 AWG. So, the correct answer is “b.”

    I thought table 250.122 refers to “grounding” conductors only?

    By the way, I really appreciate everything you’re doing for the electrical industry. I wish you were available when I started 30 years ago.

    Looking forward to your response.

    Ray

    ray
    Reply to this comment

  • In the second pop quiz neutral is in parenthesis at each mention of the grounded conductor and then Table 250.122 is referenced. Is that table not for the grounding(bonding) conductor?

    eddy.williams
    Reply to this comment

  • in comment to the netural conductor question I was always under the impression that table 250-122 was for the equipment grounding conductors for raceways and cables I had never used it to size a "netural" current carring conductor.

    LouL
    Reply to this comment

  • I have a 3 ph motor wired for low voltage I went to wire it for high voltage and found it would not run due to winding 1 to 4 being open but yet it runs on low voltage. My question is what is this doing to the motor if anything?

    Jim Bruce
    Reply to this comment

  • Mike- your minimum rating example indicates the "Nuetral" conductor is to be not less than that indicated by Table 250.122, however that table is for sizing equipment grounding conductors.

    Bob
    Reply to this comment

  • In reference to the Color Codes. The use of colors Orange & Yellow for the 480VAC Systems can be very dangerous when doing industrial control systems. UL508A & NFPA 79 uses Orange & Yellow for different purposes. I have seen control panels that have Brown, Orange and Yellow in them for 480VAC 3 Phase, Yellow for Electrical interlocks that will remain energized when the panel is Disconnected and Orange use for PLC digital outputs. The parctice of using these colors needs addressed or another identification system used when marking the 480 VAC 3 Phase Systems. Typically we use L1, L2, L3 or A, B, C, instead of colors for the 480 VAC.

    Mike Dionne
    Reply to this comment

  • Hi Mike: Color codeing depends on where you have been apprenticed, and how far back you go in the industry. 120/208 has always been Bk,Rd,Bl,Grey this Grey distinguished a 208 System. The orange in the 120/240 3 phace Volt System distinguished a Delta system indentifing the High Leg. There was NEVER a purple in the 277/480 volt 3 phace systems.

    Purple was used in travelers between 3-way branch circuits.

    Barry DeWees
    Reply to this comment

  • How do you size the grounding conductor on parallel feeders? Where is it stated in the NEC? Thank you.

    Steve G
    Reply to this comment

  • The NEC is only a minimum, not a "requirenent'. Neutrals are very commonly specified to be the same size as phase conductors. Is the unbalance for today?...tomorrow?....next year? Electrical systems change, and so does neutral current; also, more & more non-linear loads are being seen these days, giving rise to zero-sequence currents which add in the neutral, furthering the argument for up-sizing the neutrals. Maybe there should be a statement in the code saying...."It is not against the code to exceed the code."....or similar words.

    Jim
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter