This article was posted 01/05/2007 and is most likely outdated.

Article 820: Community Antenna Television (CATV) and Radio Distribution Systems
 

 
Topic - NEC
Subject
- Article 820: Community Antenna Television (CATV) and Radio Distribution Systems

January 5, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 820: Community Antenna Television (CATV) and Radio Distribution Systems

By Mike Holt for EC&M Magazine

Demystify the rules for Installing cables for CATV or Radio Distribution Systems.

Article 820 covers the distribution of television and radio signals via cable. This is in contrast to Article 810, which covers the distribution of television and radio signals via antenna.

Any installation involving coaxial cables that connect antennas to any of the following must comply with Article 820:

  • Television receiving equipment [810.3]
  • Radio receiving equipment [810.3]
  • Community television systems (CATV) [810.4]

In these cable applications, CATV coaxial cable delivers low-energy power from a power-limited power supply to equipment associated with the radio frequency distribution system. This occurs at a maximum of 60V from a power supply that has energy-limiting characteristics. Examples of such supplies include boosters, amplifiers, and some splitters [820.15].

Cable installation basics
Install equipment and cabling in a neat and workmanlike manner [820.24]. You can find the industry practices described in ANSI/NECA/BICSI 568, Standard for Installing Commercial Building Telecommunications Cabling [820.24 FPN].

Exposed cables must be supported by the structural components of the building to prevent cable damage due to normal building use. Secure cables with straps, staples, hangers, or similar fittings designed and installed so as not to damage the cable.

Cables installed parallel to framing members or furring strips must be protected where they are likely to be penetrated by nails or screws. To provide this protection, you have two options:

  1. Install the cables at least 1-1⁄4 in. from the nearest edge of the framing member or furring strips, or
  2. Protect the cable with a 1⁄16 in. thick steel plate [300.4(D)].

Raceways that contain coaxial cables must be securely fastened in place [820.110], and they are not allowed to be supported by raceways [820.133(C)]. Don’t use ceiling-support wires or the ceiling grid to support raceways or cables (Figure 820-9). You can support raceways and cables with independent support wires attached to the suspended ceiling per 300.11(A).

Remove the accessible portion of cable that isn’t terminated at equipment (and not identified for future use with a tag) [820.3(A)]. This rule doesn’t require the removal of concealed cables that are abandoned in place. A cable in a raceway is concealed (per the Article 100 definition). If you run cables through fire-resistant-rated walls, partitions, floors, or ceilings, make sure you firestop them [820.3(A)].

Overhead Cables
Don’t attach coaxial cables to a mast that encloses or supports power and lighting conductors [820.44(C)]. Separate the coaxial cable at least 4 in. from electric light and power conductors. Where practicable, maintain a separation of at least 6 ft between coaxial cables and lightning protection conductors [820.44(F)(3)].

Underground Circuits Entering Buildings
Underground coaxial cables in a pedestal or a handhole enclosure must be in a section permanently separated from exposed electric light, power, or Class 1 circuit conductors by a suitable barrier [820.47].

Run direct-buried coaxial cable at least 12 in. from underground light, power, or Class 1 circuit conductors [820.47(B)] (Figure 820-12). You don’t need to separate underground coaxial cables from service conductors, if the service conductors or coaxial cables are installed in a raceway or cable armor. You don’t need to separate underground coaxial cables from feeder or branch-circuit power conductors, if the power conductors are installed in a raceway or in metal-sheathed, metal-clad, UF, or USE cables, or the coaxial cables have metal cable armor or are installed in a raceway.

Grounding methods
When grounding the shield of the coaxial cable, use an insulated grounding conductor made of copper or other corrosion-resistant conductive material [820.100]. The conductor can’t be smaller than 14 AWG. It doesn’t have to be larger than 6 AWG, but it must have a current-carrying capacity equal to that of the outer conductor of the cable. Make it as short as practicable and run it in as straight a line as practicable.

In one- and two-family dwellings, limit the grounding conductor length to 20 ft unless such a limitation just isn’t practicable. If you need more than a 20 ft length, then you also have to install a separate ground rod that’s at least 8 ft long [820.100(A)(4) Ex.]. Bond the rod to the power grounding electrode system with a minimum 6 AWG conductor [820.100(D)] (Figure 820-19). If you don’t bond the rod to the main system, you create a difference of potential and a flashover hazard.

If you run the grounding conductor in a ferrous metal raceway, bond each end of the conductor to the raceway. This, like bonding a grounding electrode conductor [250.64E], helps with inductive reactance during a lightning event.

The grounding conductor must terminate to the nearest accessible point or item from the list below [820.100(B)]:

  • Grounding electrode system [250.50].
  • Interior metal water piping system, within 5 ft from its point of entrance [250.52(A)(1)].
  • Accessible service bonding means [250.94].
  • Metallic service raceway.
  • Service equipment enclosure.
  • Grounding electrode conductor or associated metal enclosure.
  • The grounding electrode conductor or grounding electrode of a building disconnecting means that is grounded per 250.32.

Indoor cables
To prevent a fire or shock hazard that could occur from a ground fault or short circuit between higher-voltage circuits and coaxial cable, keep these conductors and coaxial cable separated. You’ll find specific rules and exceptions in 820.133(A).

You can never install coaxial cables in ducts or plenums [820.3(B)], unless the cables are required to be in the duct or plenum for direct action upon (or sensing of) the contained air. If you do run coaxial cables into ducts or plenums, install them in electrical metallic tubing, intermediate metal conduit, or rigid metal conduit [300.22(B)]. Even plenum rated coaxial cables can never be run in a duct or plenum without one of these metallic raceways.

You can install plenum-rated Type CATVP cables [820.179(A)] above a suspended ceiling or below a raised floor that is used for environmental air [300.22(C)]. Nonplenum-rated Type CATV cables can be installed in these spaces if installed in a metallic raceway type listed in 300.22(C)(1).

If coaxial cables run vertically and penetrate more than one floor, they must be Type CATVR [820.179(B)] or Type CATVP [820.179(A)], unless you run them in metal raceway. You can always install Type CATVP, CATVR, and CATV coaxial cables in a cable tray [820.154(C)].

Listings
Are you installing cables in areas that move or transport environmental air? Pay close attention to installation requirements. If these seem confusing, just remember that the NEC is trying to reduce the hazards that arise from the burning of conductor insulation, the jackets of cables, and nonmetallic raceways.

Because listed plenum-rated cables have adequate fire-resistant and low smoke-producing characteristics, you can install them exposed in environmental air spaces. You cannot install exposed cable in ducts or plenums for any reason.

Article 820 provides four designations for listed coaxial cable types [820/179]:

  1. CATV. The letters stand for “Community Antenna Television,” and this is your basic, general purpose cable.
  2. CATVP. The P is for plenum.
  3. CATVR. The R is for riser.
  4. CATVX. This is a limited-use cable for dwellings and in raceway.

Article 820 provides three designations for listed coaxial raceway types [820.182]:

  1. General-Purpose Coaxial Raceway. These can contain CATV, CATVX, CATVR, or CATVP cables.
  2. Plenum Coaxial Raceway. These are listed for use in other spaces used for environmental air, and they must contain only Type CATVP cable [820.179(A)]. Plenum coaxial raceways cannot be installed in ducts or plenums [300.22(B)], even though they are rated for it.
  3. Riser Coaxial Raceway. These are listed as being suitable to be run vertically through more than one floor. If they run vertically and penetrate more than one floor, they can contain only CATVR and CATVP cables [820.179(B)].

Article 820 can seem a bit mystifying and abstract, especially if you have been working in Chapters 1 through 4 and are just now entering the world of communications installations. But when you examine Article 820 carefully, you can see that it doesn’t tell you much that you don’t already know about installation practices. For example, you’ve got to bond metallic parts together —that’s an Article 250 fundamental. You also need to use the correct cable and raceway, which is something Chapter 3 veterans already know.

Still, Article 820 does contain some specifics that you should know about to make sure you do the job right. If you remember to apply the same general concepts that you’ve already been applying in traditional electrical work, these specifics will easily make sense to you.

820 Tips

  • Determine the “point of entrance.”
  • Ground the incoming cable as close as practicable to the point of entrance.
  • If you run cables above a suspended ceiling, route and support them to allow access via ceiling panel removal.
  • If you use a separate grounding electrode, bond it to the power grounding system.
  • Use the correct cable type and raceway for the application—general, plenum, or riser.

 

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • thanks for information

    lacticarp@yahoo.com
    Reply to this comment

  • Thanks Mike for the 820 tips. My question concerns the install of antennas on roofs with lightning protection. With a new high point on the roof is a lightning rod needed to be added or relocated? My understanding is that the work be done by a certified installer. Is bonding required? Is an electrical inspection required? THANX r u h2o skiing?

    Doug Vickers
    Reply to this comment

  • Hello Mike. If I understand Art. 820-100(D) correctly, If a ground rod is added for the CATV cable it must be bonded to the main service panel with a minimum #6 awg. First I must say I have never seen this done by the local cable installers who simply put in a rod and attach a ground wire to the CATV distribution block on the outside of the building. So my question than isn't this a violation? If it is than isn't it also required that the person who runs the #6 to bond in the main panel be a licensed electrician and is a permit required? Thanks.

    Dan
    Reply to this comment

  • How do spaces above ceilings and below raised floors used for transport of environmental air differ from ducts and ducts and plenums? This question pertains to the requirements for routing plenum rated coaxial cable in raceway when routing through ducts or plenums. Raceway is not required when routing plenum rated coaxial cables above drop cielings or below raised floors used for transport of environmental air.

    Paul McNichol
    Reply to this comment


Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter