Mike Holt Enterprises Electrical News Source

Overvoltage Protection, based on the 2020 NEC

January 23, 2023 | Share: Facebook Twitter Instagram

Figure 01

By Mike Holt
NEC® Consultant for EC&M Magazine

Note: This article is based on the 2020 NEC.

Don't rely on a single type of surge protection device. Implement a strategy based on tiered protection.

With the 2020 revision of the NEC, Article 242 replaced two articles that appeared in earlier editions. These were Article 280 (Surge Arrestors) and Article 285 Transient Voltage Surge Suppressors (TVSSs).

Implementing a good strategy for overvoltage protection encompasses the material contained in both of those articles. Overcurrent protection is covered by Article 240, it was logical to cover overvoltage protection in a new Article 242 rather than stick two overvoltage protection articles at the end of Chapter Two.

Part I of Article 242 provides the general, installation, and connection requirements for overvoltage protection and overvoltage protective devices (Surge protective devices or SPDs). Part II covers SPDs rated 1,000V or less that are permanently installed on premises wiring systems. Part III covers surge arresters permanently installed on premises wiring systems over 1,000V nominal.

It will bring you to tiers
Distribution stepdown transformers do not filter out transients. They reduce transients by the same proportion they step down the line voltage. For example, a 480V/120V delta/wye transformer has a 4 to 1 turns ratio which means a 1,800V spike coming into that transformer will be 450V spike on the other side of it.

It helps to think of power distribution voltage levels as a series of layers that get smaller as you go from the source toward the point of use. We start with the higher voltages and further break down voltage levels into what we call a tiered protection strategy.

SPDs are designed to reduce transient voltages present on premises power distribution wiring and load-side equipment. These transient voltages can originate from sources ranging from lightning to laser printers. Voltage spikes and transients that are caused by:

  • The switching of utility power lines, power factor correction capacitors, or lightning can reach thousands of volts and amperes.
  • Utilization equipment such as photocopiers, laser printers, and other high reactive loads can be in the hundreds of volts.

Transients produced by utilization equipment are the usual culprits when you have frequent failures of electronic equipment such as computers, telecommunications equipment, security systems, and electronic appliances.

The intent of an SPD is to limit transient voltages by diverting or limiting surge current and preventing continued flow of current while remaining capable of repeating these functions [Article 100].

A key concept in the application of these devices is they limit transient voltages rather than eliminate them. How much a particular device limits transient voltages depends on which level of power distribution and particular environment it is designed for.

A given SPD device can limit voltage only within a certain range. That's why a tiered system is necessary. The first SPD device downstream of the disturbance handles the voltage down to something on par with that level of voltage distribution. This continues for as many levels as needed until you're at the branch circuit SPD which can't possibly handle the original transient but can easily handle what the other SPDs have passed to it.

Prohibited uses
You cannot use an SPD [242.6]:
(1) In circuits that exceed 1,000V.
(2) In ungrounded systems, impedance grounded systems, or corner-grounded delta systems unless listed specifically for use on these systems.
(3) If the voltage rating of the SPD is less than the maximum continuous phase-to-ground voltage available at the point of connection.

SPD requirements
SPDs must be listed [242.8]. UL 1449, Standard for SPDs, says these units are intended to limit the maximum extent of transient voltage surges on power lines to specified values. They are not intended to function as lightning arresters.

SPDs are susceptible to failure at high fault currents. SPDs must be marked with their short-circuit current rating. You cannot install an SPD where the available fault current exceeds its rating [242.10].

Where you use SPDs, ensure each phase conductor the SPD-protected circuit is connected [242.20]. If the SPD comes as a three-phase system in a box, simply connect the phase wires of the SPD to the electrical system's phase wires. Otherwise, you will probably be connecting an individual SPD between any two conductors (whether ungrounded or grounded). A grounded conductor and the equipment grounding conductor can be interconnected only by the normal operation of the SPD during a surge [242.30].

Line and grounding conductors must be at least 14AWG (12AWG if aluminum) [242.28]. Connect only one conductor to a terminal, unless the terminal is identified for multiple conductors [110.14(A)]. Don't make the leads any longer than necessary, and avoid bends that are sharp or unnecessary [242.24]. Shorter conductors and minimal bends improve SPD performance by helping to reduce conductor impedance during high-frequency transient events. Figure 01

Types 1, 2, 3, and 4
SPD types are numbered from the service (Type 1), feeder (Type 2), branch circuits (Type 3) to components integrated into the equipment (Type 4). As the energy level decreases the Type number increases. For that reason, using each Type in a tiered strategy is the only way to effectively protect infrastructure and loads from transients. Here are the tiers:

Type 1 SPDs normally go on the supply side of the service disconnect [242.12(A)(1)]. However, you can install them on the load side of the service disconnect per the requirements of 242.14 [242.12(A)(2)]. For example, you might want to use a Type 1 SPD on a particular feeder that supplies a large motor.

Type 2 SPDs must be connected to the load side of the service disconnect [242.14(A)] rather than the supply side. You can connect them anywhere on the load side of the feeder overcurrent protective device [242.14(B)] and you can connect them anywhere on the premises wiring of a separately derived system [242.14(C)].

Type 3 SPDs must be connected somewhere on the load side of branch circuit protection [242.16], and their application stops at the equipment served.

Type 4 SPDs are installed in the equipment served, and can be installed only by the equipment manufacturer [242.18]. A common scheme is metal oxide varistors (MOVs) connected between each power input line and ground. You may see these, for example, inside a case power supply. They shunt the remaining overvoltage out of the power line. However, they are easily destroyed if the incoming voltage exceeds their rating. Proper application of Types 1, 2, and 3 upstream of the MOV protected equipment is essential.

Effective protection
Your transient protection system needs to consist of layers of transient shields, each one at a lower energy level as you peel back another layer of the transient protection onion. The idea is to keep knocking down the voltage level of the transient.

Correctly select the SPDs that will most economically and most effectively protect your branch circuits and their loads.

Learn more with Mike's Understanding the NEC Complete Library:


Comments
    No comments to display

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter