The secondary neutral terminal of a 3-wire delta primary and 4-wire delta secondary transformer should not be used for any purpose whatsoever because there is no guarantee that the nuetral current will never exceed 5% of transformer capacity.
The same thing can be said about connecting a generator winding in a closed 4-wire delta configuration. Both generators and 3 legged 3-phase delta delta transformers have very little zero sequence impedance to stop circulating current in a closed delta winding.
Superior transformer configuration for 4-wire delta power are:
1. 2 single phase transformers wired 3-wire T-primary 4-wire T-secondary. This is very easy to build and conventional primary/secondary overcurrent protection can be used. Primary neutral point MUST NOT be connected to source neutral and must be fully insulated from ground. Primary system can be ungrounded.
2. 3 single phase transformers in the 3-wire floating neutral wye primary 4-wire delta secondary configuration. Primary neutral must be insulated from ground and any primary system neutral. Primary system can be ungrounded. A standard single phase transformer is 277 volts primary 120/240 volts secondary. Conventional secondary overload protection does NOT protect the primary windings from overload and does not protect the 2 halves of the center tapped secondary winding. Supplemental overload protection such as motor overload relays arranged to open a primary contactor with conventional circuit breakers providing magnetic tripping for short circuits would work.
3. A 3-wire delta secondary ( or say a 138Y240 volt winding used as a 3-wire secondary ) with a balance coil used to derive a neutral. A balance coil is a single phase version of a zig-zag set for converting 3-wire 3-phase systems to 4-wire wye operation. For a 240 volt secondary a balance coil that is rated 240 volts phase to neutral ( can be made from a standard 240x480 primary 120.240 secondary transformer ) should be used so that ground faults will not cause core saturation. Under normal conditions the 50% applied voltage will give the balance coil some amount of a K rating by running the core cooler.Similar to a zig-zag set a current transformer connected to detect a 50% imbalance in hot lead current should be used to protect the balance coil and the balance coil also needs supplemental overload protection. A secondary circuit breaker that is 4-pole ( protecting the neutral ) would work if the balance coil is big enough.
For gnerators:
4. Connect the generator 138Y240 volts and use a balance coil as in 3 above.
5. Have the generator rewound with a T-connected winding which was a configuration that General Electric one time made. This is essentially an asymmetrical 2-phase generator which produces 4-wire delta power without risk of circulating current in the generator windings.
By the way, 4-wire delta power from a utility is metered as an asymmetrical 2-phase system even though the source and loads are 3-phase.
Mike Cole, mc5w at earthlink dot net Michael R.Cole Reply to this comment |