Mike Holt Enterprises Electrical News Source

NEC Questions and Answers based on 2020 NEC® - May 2021

Figure 01

For EC&M Magazine
By Mike Holt, NEC® Consultant
Here's the follow-up to yesterday's newsletter. This includes the answers to the questions sent, so you can see how you did.

Note: The answers to these questions are based on the 2020 NEC.

Q1. What does the Code require when conductors 4 AWG and larger enter a cabinet, box, enclosure, or raceway?
A1. Where subject to physical damage, conductors, raceways, and cables must be protected in accordance with (A) through (H) [300.4].

(G) Fittings. Raceways containing insulated circuit conductors 4 AWG and larger that enter a cabinet, box, enclosure, or raceway, must have the conductors protected as follows:

(1) A fitting providing a smoothly rounded insulating surface
(2) A listed metal fitting that has smoothly rounded edges.
(3) Separation from the fitting or raceway using an identified insulating material that is securely fastened in place
(4) Threaded hubs or bosses that are an integral part of a cabinet, box, enclosure, or raceway that provide a smoothly rounded or flared entry for conductors. Figure 01

Q2. What does the Code require when a raceway is subjected to different temperatures and condensations is known to be a problem?
A2. (A) Sealing. If a raceway is subjected to different temperatures, and where condensation is known to be a problem, the raceway must be filled with a material approved by the authority having jurisdiction that will prevent the circulation of warm air to a colder section of the raceway. Sealants must be identified for use with cable insulation, conductor insulation, a bare conductor, a shield, or other components. Special sealing fittings such as an explosionproof seal is not required [300.7(A)].‚

Author's Comment:
One common product used for this is electrical duct seal and it is so identified. There are other identified products such as Polywater's FST Duct Sealant. Typical expanding foams used to seal buildings are not identified for this application.

Q3. What is the NEC rule about wiring installed in exit enclosures (stair towers)?
A3. 300.25 Exit Enclosures (Stair Towers)
Where an exit enclosure is required to be separated from the building, only electrical wiring methods serving equipment permitted by the authority having jurisdiction in the exit enclosure are permitted to be installed within the exit enclosure.

Author's Comment:
As used here, separated from the building does not necessarily mean detached. Article 100 defines a ˜building' as a structure that stands alone or that is separated from adjoining structures by fire walls. The fire rating rules for walls surrounding a star tower are much more stringent and serve to ˜separate' it from the main building. The intent of this requirement is to limit the materials within an exit enclosure to only those needed to serve the intended function of the exit enclosure for a safe passage out of the building in the event of an emergency, such as egress lighting. If the need should arise that a stair tower landing was the only place for a sub-panel, (for example), to be installed, it would require documented special permission from the authority having jurisdiction.

Informational Note: For more information, refer to NFPA 101, Life Safety Code, 7.1.3.2(10)(b).

Q4. What is the maximum voltage rating for conductors covered in Article 310 of the NEC?
A4. Article 310 contains the general requirements for conductors rated up to and including 2,000V, such as insulation markings, ampacity ratings, and their use [310.1].

Informational Note: For flexible cords and cable, see Article 400. For fixture wires, see Article 402.

Q5. What are the Code rules for sizing of service and feeder conductors supplying a single dwelling?
A5. Dwelling unit service and feeder conductors supplied by a single-phase, 120/240V systems can be sized in accordance with 310.12(A) through (D) and dwelling unit single-phase feeder conductors supplied by a three-phase 120/208V wye system can be sized in accordance with 310.12(A) through (C):

(A) Services rated 100A through 400A. Single-phase 120/240V service conductors supplying the entire load associated with the dwelling unit can have the conductor sized in accordance with Table 310.12 where there is no conductor ampacity adjustment or correction as required by 310.14.

Example
Question: What size service conductors are required if the calculated load for a dwelling unit requires a service disconnect rated 200A?
(a) 1/0 AWG (b) 2/0 AWG (c) 3/0 AWG (d) 4/0 AWG
Answer: (b) 2/0 AWG [Table 310.12]

Author's Comment:
Section 310.12 cannot be used for service conductors for two-family or multifamily dwelling buildings.

(B) Feeders rated 100A through 400A. Single-phase 120/240V or 120/208V feeder conductors supplying the entire load associated with the dwelling unit can have the conductor sized in accordance with Table 310.12 where there is no conductor ampacity adjustment or correction as required by 310.14.

Example
Question: What size feeder conductors are required if the calculated load for a dwelling unit requires a service disconnect rated 200A, and the feeder conductors carry the entire load of the dwelling unit?‚
(a) 1/0 AWG (b) 2/0 AWG (c) 3/0 AWG (d) 4/0 AWG
Answer: (b) 2/0 AWG [Table 310.12]

Author's Comment:
Table 310.12 cannot be used to size feeder conductors where a feeder does not carry the entire load of the dwelling unit, except as permitted in 310.12(C).

(C) Feeder Conductors Not Greater Than Service Conductors. Feeder conductors for an individual dwelling unit are not required to be sized larger than the service conductors sized to Table 310.12.

(D) Neutral Conductors. Neutral conductors are permitted to be sized smaller than the phase conductors if the requirements of 220.61(A) and 230.42 for service conductors and the requirements of 215.2 and 220.61(A) for feeder conductors are met.

Comments
  • MIKE YOU ARE THE MOST QUALIFIDE AND CORRECT INSTRUCTOR I HAVE EVER HAD OR LISTENED TO. YOUR BOOKS AND POWER POINTS MAKE THINGS A LOT EASIER TO UNDERSTAND ANYTHING ABOUT ELECTRICAL WORK AND CODE RULES. WHEN I TEACH ELECTRICIANS THEY ARE SO GLAD ABOUT YOUR BOOKS AND OTHER TEACHING MATERIALS BECAUSE IT MAKES IT EASIR TO PASS THEIR NEXT TEST POSSABLY IN ANY OF THE 6 STATES I AM APPROVED TO TEACH IN THANKS TO YOUR LEARNING MATERIALS.

    HERB OGDEN  June 1 2021, 11:52 pm EDT
    Reply to this comment
  • Reply from: Mike Holt   June 2 2021, 12:59 am EDT
    Thanks Herb, it's our honor to serve others with all we can and all of our might. You know why... Brother.
    Reply to Mike Holt


  • Hello.Mr. Mike i hope you're doing well, and thanks for all the free video you have, and has posted through the years, I am a follower for more than 10 years, My name is Jorge angel Flores, I live in Houston Texas, I have bought some book from you, like bonding and grounding, I love article 250, Basic electrical theory, because you said this is the first book than an electrician have to have, etc. Ok, here is the question, I read this article, and I remenber in one of your videos, Like 6 months ago, you said you were gonna make a full video about Neutral and all related to it, when can be smaller, Armonica, etc, I would really Appreciate if you do a video about service entrance like one single family and when the neutro is smaller or not, or commercial services with or without neutral reducction. Thanks in Advance.

    Atte. Jorge A. Flores

    JORGE A FLORES  May 19 2021, 12:26 am EDT
    Reply to this comment
  • Reply from: Mike Holt   May 20 2021, 3:24 pm EDT
    I don't remember this and I'm not creating any such video. Sorry.
    Reply to Mike Holt



Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter