NEC Questions and Answers based on 2020 NEC® - April 2020

Figure 01

For EC&M Magazine
By Mike Holt, NEC® Consultant
Here's the follow-up to yesterday's newsletter. This includes the answers to the questions sent, so you can see how you did.

Note: The answers to these questions are based on the 2020 NEC.
Underlined text indicates a change for the 2020 NEC.

Q1. What is the Code rule for the marking of disconnects?
A1. 110.22 Identification of Disconnecting Means
(A) General. Each disconnect must be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking must include the identification of the circuit source that supplies the disconnecting means. The marking must be of sufficient durability to withstand the environment involved [110.22].‚Figure 01

Author's Comment:
See 408.4 for additional requirements for identification markings on circuit directories for switchboards and panelboards.
These rules are intended to make it safer to work on electrical equipment. The premise is that if the worker knows the location of the power source, he or she is much more likely than not to lockout and tagout the power source.

Q2. What is the Code requirement for the GFCI protection of pool pump motors?
A2. 680.21 Pool Motors
(A) Wiring Methods. The wiring to a pool-associated motor must comply with 680.21(A)(1) unless modified by (A)(2) or (A)(3).

(1) General. Branch-circuit wiring for pool-associated motors installed in corrosive locations must be rigid metal conduit, intermediate metal conduit, rigid polyvinyl chloride conduit, reinforced thermosetting resin conduit [680.14], or Type MC cable listed for the location.

The wiring methods must contain an insulated copper equipment grounding conductor sized in accordance with 250.122, but in no case can the equipment grounding conductor be sized smaller than 12 AWG.

Where installed in noncorrosive environments, any Chapter 3 wiring method is permitted.

(2) Flexible Connections. Liquidtight flexible metal or liquidtight flexible nonmetallic conduit are permitted.

(C) GFCI Protection. GFCI protection is required for all pool motors rated 60A or less, at not over 150V to ground, single- or 3-phase, whether by receptacle or by direct connection.

Ex: Listed low-voltage motors not requiring grounding, with ratings not exceeding the low-voltage contact limit supplied by transformers or power supplies that comply with 680.23(A)(2), may be installed without GFCI protection.

Q3. When a pool pump motor is replaced, what does the NEC require regarding GFCI protection?
A3. (D) Pool Pump Motor Replacement. Where a pool pump motor is replaced, the replacement pump motor must be provided with GFCI protection [680.21(D)].

Q4. What are the NEC requirements for the bonding and grounding of fountains?
A4. 680.54 Connection to an Equipment Grounding Conductor

(A) Connection to Equipment Grounding Conductor. The following equipment must be connected to the circuit equipment grounding conductor:

(1) Other than listed low-voltage luminaires not requiring grounding, all electrical equipment located within the fountain or within 5 ft of the inside wall of the fountain.

(2) All electrical equipment associated with the recirculating system of the fountain.

(3) Panelboards that are not part of the service equipment and that supply any electrical equipment associated with the fountain.

Note: See 250.122 for sizing of these conductors.

(B) Bonding. The following parts must be bonded together and connected to an equipment grounding conductor of the branch circuit supplying the fountain:
(1) All metal piping systems associated with the fountain
(2) All metal fittings within or attached to the fountain
(3) Metal parts of electrical equipment associated with the fountain water-circulating system, including pump motors
(4) Metal raceways within 5 ft of the inside wall or perimeter of the fountain and not separated from the fountain by a permanent barrier
(5) All metal surfaces within 5 ft of the inside wall or perimeter of the fountain and not separated from the fountain by a permanent barrier
(6) Electrical devices and controls that are not associated with the fountain and are located less than 5 ft of the inside wall or perimeter of the fountain

Q5. What identification is required by the NEC for neutral conductors?
A5. 200.6 Identification of Grounded Conductors
(A) 6 AWG or Smaller. Neutral conductors 6 AWG and smaller must be identified by any of the following means:

(1) Insulated conductors with a continuous white outer finish.
(2) Insulated conductors with a continuous gray outer finish.
(3) Insulated conductors with three continuous white or gray stripes along its entire length on other than green insulation.
(4) Insulated conductors with their outer covering finished to show a white or gray color but have colored tracer threads in the braid identifying the source of manufacture.

Author's Comment:
The use of white tape, paint, or other methods of identification is not permitted for neutral conductors 6 AWG and smaller.

(B) 4 AWG or Larger. Neutral conductors 4 AWG or larger must be identified by any of the following means:
(1) A continuous white outer finish along their entire length.
(2) A continuous gray outer finish along their entire length.
(3) Three continuous white or gray stripes along their length.
(4) White or gray tape or markings at the terminations.

(E) Neutral Conductors of Multiconductor Cables. Insulated neutral conductor(s) sized 6 AWG and smaller in multiconductor cables must be identified by a continuous white or gray outer finish, or by three continuous white or gray stripes. Conductors in multiconductor cables sized 4 AWG or larger can have the neutral conductor identified in accordance with 200.6(B).

Ex 1: Conductors within multiconductor cables are permitted to be re-identified at their terminations at the time of installation by a distinctive white or gray marking.

Comments
  • Thanks for all the code references.

    Mike Owens  April 17 2020, 7:56 am EDT
    Reply to this comment

  • Mike, I am an instructor of electricians at a local community college, and I would like to thank you for all the correspondence and advice you have supplied us with throughout the years. Please keep up the great work. Bless you and your family during this time of uncertainty due to the Coronavirus pandemic.

    Felix Sandoval  April 17 2020, 6:37 am EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter