This article was posted 06/23/2006 and is most likely outdated.

Grounding vs Bonding Online Training
 

 
Grounding vs Bonding: 250.110 Fixed Equipment Connected by Permanent Wiring Methods—General

June 23, 2006  

  View Comments | Add Comments | Notify Me When Comments Are Added  

PART VI.   Hi Res - Cable/DSL [13032Kb]VIEWING Video FILE requires
Real Media Player [ FREE ]

Sections

250.110 Fixed Equipment Connected by Permanent Wiring Methods—General.

Exposed metal parts of fixed equipment likely to become energized must be grounded (bonded) to an effective ground-fault current path where the fixed equipment is:

(1) Within 8 ft vertically or 5 ft horizontally of earth or grounded metal objects
(2) Located in a wet or damp location
(3) In electrical contact with metal
(4) In a hazardous (classified) location [Articles 500 through 517]
(5) Supplied by a wiring method that provides an equipment grounding (bonding) conductor of a type specified in 250.118
(6) Supplied by a 277V or 480V circuit

Exception 3: Double-insulated equipment isn’t required to be grounded (bonded) to an effective ground-fault current path.

imageSend to a Friend


 
 

       

Copyright © 2006 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter