Reply from: David Rifkin May 11 2019, 3:45 pm EDT Having ground fault protection may not protect from currents in the water in some unusual circumstances. Let's say you two boats sharing a 120/240v service on a single feeder breaker (that's a GFP tripping at 30ma). Boat A develops a 2amp leak from L1 to the water. Boat B develops a 2amp leak from L2 to the water.
It is possible that not enough of this leakage current will escape and cause a ground fault trip. It's simply traveling between L1 and L2 using the water as a sort of neutral conductor.
This has been observed in the field, although at the time it was not fully understood.
555 of the NEC now requires an individual GFP not exceeding 30ma on each shore power receptacle. This will prevent the above scenario from occurring.
This problem is only present due to the split voltage multiwire branch circuits we use in the USA. If we went to 240v to ground exclusively, this problem goes away (but yes, there are other dangers associated with double the voltage to ground). Reply to David Rifkin |