Eaton has identified a potential nonconformance with certain Eaton Heavy Duty 30A and 60A Safety Switches. The
safety switch can potentially supply power when the handle is in the off position, subjecting the operator of the
switch or any downstream equipment to risk of serious bodily injury or death.
Hazard Identified: This issue affects various configurations of 30A and 60A Heavy Duty safety switches manufactured between
November 19, 2015 and January 23, 2018. Please see Appendix B for a complete list of affected catalog number
prefixes. Potentially affected switches can be identified using the information identified in Figures 1 and 2.
For Units that have been installed: DANGER -
Inspection of installed units should only be performed by qualified individuals. Apply appropriate personal
protective equipment and follow safe electrical work practices. Verify unit is de-energized prior to any
inspection. Failure to follow these instructions will result in serious bodily injury or death. De-energize switch and lock out upstream equipment. Follow the instructions on the attached PDF.
For Units that have not been installed: Identify potentially affected units using the shipping label or publication shown above in the images below. If
a yellow dot is located as shown in the images below, no further action is necessary for that unit.
If any potentially affected units are found:
Download the PDF safety bulletin here.
Catalog Number and Manufacturing Date can be identified on the shipping label as shown above. |
Catalog number and Manufacturing Date can be identified on the unit publication inside the switch. |
Switch cartons with a yellow dot adjacent to the catalog number are conforming. |
Switches with a yellow dot on the handle arm are conforming. |
|
|