Mike Holt Enterprises Electrical News Source

NEC Questions and Answers based on 2017 NEC - April 2018

View in browser

Figure 01

 

For EC&M Magazine
By Mike Holt, NEC® Consultant

Here's the follow-up to yesterday's newsletter.
This includes the answers to the questions sent, so you can see how you did.

Note: The answers to these questions are based on the 2017 NEC.
Underlined text indicates a change in the rule for the 2017 NEC.

Q1. What are the uses permitted by the NEC for Metal-Clad cable (Type MC)?
A1.
General Uses [330.10 (A)].
(1) In branch circuits, feeders, and services
(2) In power, lighting, control, and signal circuits
(3) Indoors or outdoors
(4) Exposed or concealed
(5) Directly buried (if identified for the purpose)
(6) In a cable tray
(7) In a raceway
(8) As aerial cable on a messenger
(9) In hazardous locations as permitted in 501.10(B), 502.10(B), and 503.10
(10) Embedded in plaster or brick in dry locations
(11) In wet locations, where a corrosion-resistant jacket is provided over the metal sheath and any of the following are met: 
    a. The metallic covering is impervious to moisture.
    b. A jacket is provided under the metal covering that’s moisture resistant. Figure 01
    c. The insulated conductors under the metallic covering are listed for use in wet locations.
(12) If single-conductor cables are used, all circuit conductors must be grouped together to minimize induced voltage on the sheath [300.3(B)].

Author’s Comment: Installing the conductors of a circuit close together will minimize the circuit impedance.

(B) Specific Uses.

Informational Note: The “Uses Permitted” isn’t an all-inclusive list, which indicates that other suitable uses are permitted if approved by the authority having jurisdiction.

(1) Cable Tray. Type MC cable installed in a cable tray in accordance with Article 392.
(2) Direct Buried. Direct-buried cables must be protected in accordance with 300.5.
(3) Installed as Service-Entrance Cable. Type MC cable is permitted for service entrances when installed in accordance with 230.43.
(4) Installed Outside of Buildings. Type MC cable installed outside of buildings must comply with 225.10, 396.10, and 396.12.

Q2. What are the uses not permitted by the NEC for Metal-Clad cable (Type MC)?
A2.
Type MC cable isn’t permitted to be used where: [330.12]
(1) Subject to physical damage.
(2) Exposed to the destructive corrosive conditions in (a) or (b), unless the metallic sheath or armor is resistant to the conditions, or protected by material resistant to the conditions:
    a. Direct burial in the earth or embedded in concrete unless identified for the application.
    b. Exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.

Q3. What does the Code require when installing Metal-Clad cable (Type MC) in exposed work?
A3.
Exposed runs of Type MC cable must closely follow the surface of the building finish or running boards. Type MC cable installed on the bottom of floor or ceiling joists must be secured at every joist and not be subject to physical damage  [330.15]

Q4. What does the NEC require for the protection of Type MC cable installed through or parallel to framing members?
A4.
Type MC cable installed through or parallel to framing members or furring strips must be protected against physical damage from penetration of screws or nails by maintaining a 1¼ in. separation, or by installing a suitable metal plate in accordance with 300.4(A), (C), and (D) [330.17].

Q5. What are the Code requirements when installing Type MC cable in accessible attics or roof spaces?
A5.
Type MC cable installed in accessible attics or roof spaces must comply with 320.23 [330.23].

Author’s Comment:
• On the Surface of Floor Joists, Rafters, or Studs. In attics and roof spaces that are accessible, substantial guards must protect cables installed across the top of floor joists, or across the face of rafters or studding within 7 ft of the floor or floor joists. If this space isn’t accessible by permanent stairs or ladders, protection is required only within 6 ft of the nearest edge of the scuttle hole or attic entrance [320.23(A)].
• Along the Side of Framing Members [320.23(B)]. When Type MC cable is installed on the side of rafters, studs, or floor joists, no protection is required if the cable is installed and supported so the nearest outside surface of the cable or raceway is at least 1¼ in. from the nearest edge of the framing member where nails or screws are likely to penetrate [300.4(D)].

Q6. What are the NEC requirements for bends made in Type MC cable?
A6.
Bends must be made so the cable won’t be damaged, and the radius of the curve of any bend at the inner edge of the cable isn’t permitted to be less than what’s dictated in each of the following instances [330.24]:
(A) Smooth-Sheath Cables.
(1) Smooth-sheath Type MC cables aren’t permitted to be bent so the bending radius of the inner edge of the cable is less than 10 times the external diameter of the metallic sheath for cable up to ¾ in. in external diameter.
(B) Interlocked or Corrugated Sheath. Interlocked- or corrugated-sheath Type MC cable isn’t permitted to be bent so the bending radius of the inner edge of the cable is less than seven times the external diameter of the cable.  

Comments
  • Our company is doing a dorm building at a college. On the outside in a court area is a natural gas firepit. Is this firepit required to have a emergency shutoff within 50 ft and within site of.

    Les Witwer  April 17 2018, 9:47 pm EDT
    Reply to this comment

  • Mike, so in your figure 01, you show the MC Cable below the panel that looks like it does not have protection from physical damage.

    This is a problem I run into all the time, no one can identify what physical damage can be caused by.

    If the cable is in a garage, anything in the garage can damage it according to the inspector. In a utility closet, kitchen, anywhere.. MC is a much stronger product than NMB but WA says it must be used just like NMB. So it cannot be exposed below 10’ or it must be protected with a 1.25” guard...

    In CA they treat it like flex and it can run open...

    Where can I find a valid description what levels of physical damage is?

    A broom handle can cause damage to a piece of paper but not MC... there seems to be not justification to level of objects that could cause damage...

    Thoughts?,

    Jerry Beck  April 12 2018, 2:51 am EDT
    Reply to this comment

  • Wouldn't it need to be sleeved when emerging from grade to be compliant with 300.5 D (1)

    Eric Peters   April 11 2018, 11:11 pm EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter