This is a keeper! I've confused these terms in the past-as have others. These definitions help me explain stray voltage to others and also help me to better understand it myself .
Hey, all of you who have given me flack over the years for advocating the use of insulation on all neutrals please read.
Bob
Bob Gisborn Reply to this comment |
Can you recommend a publication (book or paper) that goes beyond basic grounding and ground path principles.
It would be usefull to view models or narratives that outline the behaviors of the various grounding systems in existence.
Highest Regards, Alex Brace Alex Brace Reply to this comment |
Ground currents are a serious problem especially around swimming pools, and, as conductors and connetions age, it will become worse. It seems to me that the amount of ground current would be directly proportional to the size of the magnetic fields of the transmissions lines that they originated from. The higher the ground currents, the higher the magnetic fields. If there is a way, by measuring the current in the transmition lines, to calculate the strength of the fields, the source of the problem could be tracked down and repaired. Bill Bamford Reply to this comment |
Good Newsletter. Where do I find Figures 1-4 talked about in this Newsletter?
Thanks,
Brad
BRAD LETT Reply to this comment |
An interesting Newsletter.
Aside from the issue of safety, I wonder how much wasted power is involved?
Current that does no "work" is a waste.
Here is an excellent publication on this subject:
http://www.egr.msu.edu/age/extension_outreach/Protocols_Practices_SV_Testing.pdf
Mark Prairie Reply to this comment |
Question: in beach sand, would it be better to just add additional ground rods or would soil modification be the better approach for reduced impedence... Kip Kennedy Reply to this comment |
For the interested: Read the article of Mr. Donald Zipse
The Hazardous Multigrounded Neutral Distribution System
And Dangerous Stray Currents
Copyright Material IEEE
Paper No. PCIC-03-03
Donald W. Zipse, P.E.
Life Fellow, IEEE
Zipse Electrical Engineering, Inc.
PO Box 7052 671 Kadar Drive
Wilmington, DE 19803-0052 West Chester, PA 19382-8123
Abstract – The multigrounded neutral system is the
predominant electrical distribution system used in the United
States. It permits an uncontrolled amount of electric current to
flow over the earth unrestrained, posing the potential of harm
to the public and to animals causing electric shocks and is
presumed responsible for undetected electrocutions. To
compound the problem of uncontrolled current over the earth,
utility practices places harmful current from lightning strokes
directly into customers homes.
As today’s electrical loads continue to escalate, more
current is forced into and over the earth. The question
electrical engineers and the public must answer is what is the
acceptable safe level, if any, of the passage of uncontrolled
flow of electrical current over the earth and into our homes,
office buildings and industrial facilities.
The decisions to “save money” by the adoption of the
multigrounded neutral electrical distribution system
outweighed the public’s safety are disclosed in this paper and
the electrical distributions systems that are safe are
presented.
The history of the development of the multigrounded
neutral distribution system is covered. Examples of the
dangers associated with the multigrounded neutral distribution
system and the ungrounded distribution system are disclosed.
The methods of converting these dangerous and hazardous
distribution systems into safer systems are presented.
Index Terms – Circuit, ground, grounding, earth,
multigrounded neutral distribution system, neutral
Definition of Terms:
The definitions are predominately those used in the United
States unless otherwise noted.
Circuit: Webster’s Dictionary definition, “A path or route,
the complete traversal of, which without local change of
direction, requires returning to the starting point. b. The act of
following such a path or route. 1 3. Electronics (IEEE
Definition): a. A closed path, followed or capable of being
followed by an electric current.” The beginning can be
arbitrarily selected.
A conductor or system of conductors through which an
electric current is intended to flow [1]
Earth: A conducting body of varying resistances, often
used in place of a conductor. Earth is commonly used as a
reference point for building and structure wiring systems. The
term is used interchangeable with the term “ground”.
Earthing: A connection to earth.
Electric Shock: Stimulation of the nerves and possible
convulsive contraction of the muscle caused by the passage
of an electric current through the human or the animal body.
May or may not result in electrocution.
Electrocution: To kill with electricity.
Fault current: (general) A current that flows from one
conductor to ground or to another conductor owing to an
abnormal connection (including an arc) between the two. A
fault current flowing to ground may be called a ground fault
current [2].
Ground: A conducting connection, whether intentional or
unintentional or accidental, by which an electric circuit or
equipment is connected to the earth or to some conducting
body of relative large extent that serves in place of the earth
[3]. (Also, see Grounding)
Ground current: Current that flows through the ground,
earth, equipment ground conductors, etc.
Ground electrode: A conductor buried in the earth and
used for collecting ground current from or dissipating ground
current into the earth.
Ground fault: See Ground fault current below.
Ground fault current: The ground current resulting from any
phase-conductor-to-earth fault.
Ground fault current (Normal): The flow of ground fault
current should be brief, until the protective device opens. This
brief flow of current is considered normal.
Ground fault current (Abnormal): The ground fault current,
which is continuous, resulting from any phase conductor
coming into contact with a grounded conductor or grounded
equipment or to earth, or as the result of a neutral-to-ground
fault, is objectionable and the fault should be removed,
corrected or repaired as soon as possible.
Ground return circuit: “A circuit in which the earth or an
equivalent conducting body is utilized to complete the circuit
and allow the current circulation from or to its current source.”
[3] Connected to earth or to some extended conducting body
that serves instead of the earth, whether the connection is
intentional or unintentional or accidental [4].
Grounded Conductor: “A conductor that is intentionally
grounded, either solidly or through a noninterrupting currentlimiting
device. [1]
A (current carrying) conductor that is intentionally
grounded. This can be the neutral or one of the phase
conductors in a Corner-of-the-Delta Grounding system [5].
2
Grounded: Connected to or in contact with earth or
connected to some extended conductive body that serves
instead of the earth. [1]
The NEC definition is: “Intentionally connected to earth
through a ground connection or connections of sufficiently low
impedance and having sufficient current-carrying capacity to
prevent the buildup of voltages that may result in undue
hazards to connected equipment or to persons.”
Grounded, solidly: Electrical Systems. Connected directly
through an adequate ground connection in which no
impedance has been intentionally inserted [4].
Grounded system: A system of conductors in which at least
one conductor or point is intentionally grounded, either solidly
or through a noninterrupting current-limiting device. [1]
Grounding: “A permanent and continuous conductive path
to the earth with sufficient ampacity to carry any fault current
liable to be imposed on it, and of a sufficiently low impedance
to limit the voltage rise above ground and to facilitate the
operation of the protective devices in the circuit.” (Note: Can
be thought of as being associated with the “green” wire when
associated with the NEC.)
Grounding conductor: A conductor that is used to connect
the equipment or the wiring system with a grounding electrode
or electrodes. [1]
Normally a non-current conductor used to connect
electrical equipment or the grounded circuit of a wiring system
to a grounding electrode or electrodes. Part of the equipment
grounding system.
Grounding electrode: A buried metal water-piping system,
or metal object or device buried in, or driven into the ground
so as to make intimate contact. The grounding conductor is
connected to the grounding electrode. This is usually the
reference connection point for a grounded wiring system [5].
Multigrounded/multiple grounded system: A system of
conductors in which a neutral conductor is intentionally
grounded solidly at specified intervals. A multigrounded or
multiple grounded system may or may not be effectively
grounded. See: effectively grounded. [1]
Neutral: (IEEE Definitions) (1) (rotating machinery) The point
along an insulated winding where the voltage is the
instantaneous average of the line terminal voltages during
normal operation.
Neutral conductor: A system conductor other than a phase
conductor that provides a return path for current to the source.
Not all systems have a neutral conductor. An example is an
ungrounded delta system containing only three energized
phase conductors.
Neutral Point: (IEEE Definitions) (2) (A) (power and
distribution transformers) The common point of a Y
connection in a polyphase system. (B) (power and distribution
transformers) The point of a symmetrical system which is
normally at zero voltage.
Stray current: The uncontrolled flow of continuous electric
current over and through the earth.
Stray voltage: An incorrect term associated with the
measurement of the voltage developed from the flow of stray
current.
System, electrical: The portion of the electrical conductors,
constituting a voltage level, which exists between
transformers, and if the last transformer, generating the lowest
system voltage, the conductors extending from the
transformer to the load.
Zipse’ Law: “In order to have and maintain a safe electrical
installation: All continuous flowing current shall be contained
within an insulated conductor or if a bare conductor, the
conductor shall be installed on insulators, insulated from
earth, except at one place within the system and only one
place can the neutral be connected to earth.”
I. INTRODUCTION
There is no difference between the fundamentals in low
voltage and high voltage as Ohms Law, Kirchhoff’s Laws, etc.
apply equally to each.
Examples of the protective grounding used in low voltage,
600-volt and below, applications will be described and used to
explain the hazards involved with the present day
multigrounded neutral distribution system, used in the United
States. This will allow the reader to see the parallels between
the safe low voltage distribution system and the dangerous
medium voltage multigrounded neutral distribution system.
There will be references to animals in this paper. Cows
and pigs are much more sensitive to electricity than humans.
If animals are dying because of stray current and they are as
in one case at the rate of five cows per day for over a year
until it was discovered that the reason was stray current, how
much increase in electrical load will it take until the human
animal is affected? This could happen in the work place or in
the home. Reports are constantly being received by the
author about showers, swimming pools [ 5] [6 ], and hot tubs
shocking persons.
The term ground will be interchanged with earth in the hope
that in the future the United States will adopt the European
terminology as the term earth is much more descriptive and it
will be one more step in harmonizing and unification of terms.
II. HISTORY
When Thomas Alva Edison started his electric illuminating
company and began the electrical distribution system, he
used only one insulated (from earth) conductor and the earth
for the return conductor. He filed his patent application on
February 5, 1880. This uncontrolled flow of electric current
over the earth resulted in shocking horses and his employees
as they dug along side of the underground distribution system.
Horse pulled traction companies’ employees working on the
tracks received electric shocks, especially when separating
the track joints.
This prompted Edison to devise the three-wire distribution
system, similar to what we use today in our homes. However,
Edison insulated all three conductors. This allowed Edison to
know exactly where all the current was at all times. In his
“SPECIFICATION forming part 0f Letters Patent No.
389,280, dated August 30, 1887” he states on page 2, “the
conductors of which are well insulated from each other and
from the earth.” Edison goes on to give several reasons
for not using the earth for a return conductor.
Likewise, when the Underground Railway was being
developed in London, they also elected to eliminate any stray
current by using a four (4)-rail track system, two rails for
supporting and guiding the coaches, one supply rail and the
return conductor rail. The latter two rails were insulated from
earth.
3
Major debate raged over whether an electrical system
should be connected to earth – ground. Like Edison’s
electrical systems, which originally were not connected to
earth, the ungrounded electrical system flourished until
approximately 1913. In 1913, the National Fire Protection
Association’s (NFPA) National Electrical Code (NEC) made
mandatory the connection to earth of any electrical system of
150 volts or less as measured to earth. However, when more
than one connection to earth exists on the same electrical
system, current can flow uncontrolled over the earth, metallic
piping, equipment and through the earth causing problems
with personnel safety, electrical equipment, etc., [6], [7].
Over time the utilities in the United States have failed to
learn from Edison, as today the utilities use the earth for a
partial ground return path permitting the uncontrolled flow of
parallel current over not only the earth but over the adjacent
underground metallic piping and other conducting materials
resulting in damaging the health of dairy cows, reducing their
milk output and harming humans and other animals.
[6][7][8][9]
III. THE PROBLEM
In low voltage applications, 600-volts and under for safety
purposes the NFPA’s NEC requires in residential, commercial
and industrial facilities, starting approximately in the early
1950s, a third wire, the equipment grounding conductor. In
some cases, the metallic conduit is used for the “equipment
grounding conductor” However the equipment grounding
conductor should be installed in each and every circuit. This
wire was added to electrical appliances such as electric drills,
heaters, washing machines, etc. The equipment grounding
conductor is connected to the neutral at just one point within
the house, at the service entrance panel. The equipment
grounding conductor is connected to earth. However, as will
be discussed later, the neutral is also connected to earth a
second time at the transformer, which results in a parallel
circuit. The green color or bare conductor can be connected
both intentionally and unintentionally to earth at many places,
which is the object of the equipment grounding conductor.
The function of the equipment-grounding conductor, the
green or bare conductor is not to carry any continuous flowing
electric current. The key word here is “continuous.” The only
time the equipment grounding conductor and or earth carries
any electric current is when an electrical fault occurs and then
the object of the equipment grounding conductor is fulfilled by
allowing the fault current to flow back to the source with very
little resistance or impedance in the circuit. This allows the
protective device, such as a fuse or circuit breaker to operate
and turn off the electricity thus ending quickly the hazardous
electrical fault condition.
For over 50 years, the 3-wire concept has been used to
insure electrical safety in 600 volts and below electrical
circuits, which are used in homes, commercial and industrial
establishments:
· Phase conductor (usually black colored) carrying electric
current to the load or appliance
· Neutral conductor (usually white colored) carrying all the
return electric current
· In addition, the equipment grounding conductor (usually
green in color) and/or earth only carrying electric current
when an electrical phase-to-ground fault occurs which will
insure adequate flow of fault current to operate the
protective device such as to blow the fuse or open the
circuit breaker.
This concept of restricting electrical current flow over
the equipment grounding conductor and/or earth to only
momentary fault current is valid for all electric circuits of
any voltage when safety is a major concern. This is true
Figure 1 Circuit diagram showing the black phase
conductor carrying current, the white neutral conductor
carrying return current and the equipment grounding
conductor carrying no continuous current.
whether low voltage or high voltage, whether residential,
commercial or industrial wiring or electrical distribution
wiring.
The majority of the electrical utilities in the United States
have elected to save costs of electrical distribution
installations by combining two conductor functions into one
conductor.
Figure 2. Diagram showing the electrical substation with a
transformer, protective device, the circuit breaker, the two
electrical distribution conductors, the multiple connections of
the neutral to earth and the flow of uncontrolled electric
current over the earth.
By combining the white wire, the neutral return current
conductor carrying continuous electric current with the noncontinuous
current carrying equipment grounding conductor
the utilities have saved billions and billions of dollars over 50
or more years as will be shown later.
The problem is that the utilities have used the earth as a
partial return for the neutral current allowing the neutral
current to continuously flow uncontrolled over the earth, as will
be shown, which has caused irreparable and irreversible harm
to dairy herds and pig farms and has caused electric shocks
4
to humans and most likely may have resulted in
electrocutions.
IV. IS IT “STRAY VOLTAGE” OR
“STRAY CURRENT”?
Before one can fully comprehend the magnitude of the
problem one has to understand the difference between “Stray
Voltage” and “Stray Current” and determine which is the
correct term. When voltage is measured, the measurement is
between two points.
Remember Ohm’s Law which states in order to have a
voltage we must have a current flowing through a resistance;
Voltage = Current times Resistance. Thus, it is very easy to
measure voltage as compared to measuring current. In order
to measure current one method is to place a sensing coil
around the conductor or if possible the animal.
The question that begs an answer is which is the
determining factor, voltage or current. In order to answer that
question we need to look at the human animal sensitivity to
voltage and current.
A. Human Sensitivity to Electricity
It has been reported by Edward Owen, a student of
Professor Charles F. Dalziel, University of California that
Professor Dalziel “required” his students to participate in
experiments to measure the human animal’s response to
voltage and current by placing their feet into a bucket of salt
water and holding onto a conductor. Professor Dalziel then
applied varying amounts of current and measured their
response. As recalled by the author from presentations by
Professor William B. Kouwenhoven, Electrical Engineering,
Johns Hopkins University, he used fresh cadavers to measure
electric current necessary to revive the heart in order to
develop the defibrillator. These experiments and others
produced Table 1.
It has been shown that it takes approximately 35 volts
across dry skin to force electricity into the human body. Less
voltage or electrical pressure is required for a woman’s dry
skin.
As shown in the Table 1, for a 60 Hertz alternating current
(ac) at 0.4 milliamps (mA) or 0.0004 Amps (A) a male will feel
a slight sensation on the hand. For a woman it only takes 0.3
mA. A painful shock requires 9 mA for a man and for a
woman 6 mA. One must note these low values.
Time plays a function in the equation of electrical current
and injury. The longer a person is subjected to an electrical
current flow through the body, the more likely an injury will
occur.
“The most damaging path for electrical current is through
the chest cavity. In short, any prolonged exposure to 60 Hz
current of 20 mA or more may be fatal. Fatal ventricular
fibrillation of the heart (stopping of rhythmic pumping action)
can be initiated by a current flow of as little as several
milliamperes. These injuries can cause fatalities resulting
from either direct paralysis of the respiratory system, failure of
the rhythmic heart pumping action, or immediate heart
stoppage.” [7]
It is clear that it is the current that causes a reaction in
humans, not the voltage. The voltage is the driving force
and there is a threshold below, which there is an inability
to drive any current through the human body.
Comparison of the human animal with the cow animal
shows many similar conditions. Both are mammals with a
blood system and both have an electrical communication
system, nerves.
Professor Dalziel in 1946 states, “Perhaps the most serious
misconception concerns the effects of voltage versus the
effects of current. Current and not voltage is the proper
criterion of shock intensity.” [10] It is a shame the U.S.
Department of Agriculture, the American Society of Agriculture
Engineers and others who coined and use the term “stray
voltage” in the 1970s failed to do adequate research on the
subject.
B. Measuring Electric Potential, Voltage
Electric current flowing into the earth from a ground rod at a
pole will flow into the earth in all directions. The value of
current, in amperes, can be different for various directions.
The resistivity of the soil is not uniform. This is explained in
the IEEE Technical Paper titled: “Analysis of Grounding
Systems in Soils with Hemispherical Layering” [11]. The
paper discusses grounding systems located inside or near
hemispherical soil heterogeneities.
The amount of current flowing into the earth will depend
upon the resistance of the earth. Voltage measurements for
an individual ground electrode at an electric pole are not taken
uniformly around the pole, but usually only one voltage
measurement is taken for each pole in an arbitrary direction
and at an arbitrary distance.
Supposedly, the object of taking a voltage measurement
is to determine if any adverse effects exists due to a stray
voltage being present. As has been shown it is current
that is responsible for adverse reactions of humans and
animals, not voltage.
It is usual for utility personnel to make stray voltage
measurements with one reference lead connected to the
ground rod or the down ground conductor while the other
reference lead, a probe is forced into the soil some distance
from the pole. As is shown in Figure 3, where the second
reference probe is placed will determine the voltage drop
across the earth. The voltage drop will be a function of the
current flow between the ground rod and the reference probe
times the resistance of the soil between the two points, the
rod and the probe.
As is shown in the Figure 3, depending where the rod is
placed could determine the voltage. What if there were
additional current flows from an adjacent pole flowing in or
across the same reference distance, rod to point A. The value
of voltage would not be an indication of current flow from the
rod at the pole under investigation into the earth.
With only a voltage measurement being made the value of
such information is useless and usually a waste of time and
energy. However, this is the standard used to determine if a
problem exists.
5
Direct Current Alternating Current
60 Hz 10kHz
Men Women Men Women Men Women
Slight sensation on hand 1. 0.6 0.4 0.3 7 5
Perception “let go” threshold median 6.2 3.5 1.1 0.7 12 8
Shock – not painful and NO loss of muscular 9. 6. 1.8 1.2 17 11
Painful shock – muscular control loss 62. 41. 9. 6. 55 37
Painful and severe shock breathing difficult 90. 60. 23. 15. 94 63
Table 1. Sensitivity of Humans to Electric Current in Milliamperes
Pole
Phase
Neutral
Down
Grounding
Conductor
Ground Rod
Grade
Earth
Current radiating
out from Ground Rod
A
B
C
D
Figure 3. Current emanating from the ground rod - magnitude
as a function of earth resistance and electrical load.
Ohm’s Law has three unknowns, Voltage, Current and
Resistance. Algebra shows that in order to solve any
equation one must know or have values for one less unknown
than the total number of unknowns. With Ohm’s Law there
are three unknowns, thus to solve Ohm’s Law one must have
values for any two items; voltage and current, current and
resistance or voltage and resistance. Measuring just the
voltage basically does not show anything except the value of
voltage between those two points. That is all; nothing else
can be stated about a voltage measurement between two
points if only the voltage was measured.
Making a voltage measurement only gives the value of
voltage across that one spot. The one voltage measurement
does not tell you the value of current or resistance of the
circuit under investigation. Voltage decreases as resistance is
encountered. However, current remains constant throughout
the circuit.
No matter where one measures the current in the circuit
shown in Figure 1, the current will remain the same. The
current will not change depending on where one
measures the current in the circuit. This concept is
critical in dealing with stray current, not the magnitude of
voltage once the voltage threshold is sufficient to
breakdown the barrier to current flow is exceeded.
V. HISTORY OF ELECTRICAL DISTRIBUTION AND
EARTH RETURN
In order to fully comprehend the detrimental effects of
allowing the earth to continuously conduct electric current it is
imperative that one understands the history and how the
utilities elected to use an unsafe electrical distribution method.
It was shown that earth return had been tried in the early
days of electrical distribution and found to be too
hazardous and harmful to not only the human population
but also to animals.
A. Experience of Thomas A. Edison and Earth Return of
Electrical Current
Thomas Alvin Edison patented the first electrical
distribution system. The patent was filed on February 5, 1880
in the United States and given the number 2,282. It was titled,
“System of Electrical Distribution”.
Edison tried several approaches to distributing electricity.
Tom Shaughnessy, PowerCET Corporation writes, “Early on,
Edison implemented a floating approach for his DC systems
after several events demonstrated the adverse effects of
stray DC currents flowing throughout buildings and
neighborhoods. Once, a horse was shocked when it walked
on "electrified soil" near Edison's Pearl Street generating
station and laborers working on his underground distribution
system believed there was a "devil in the wire."‘ As a result
of some of these problems, Edison apparently adopted a
three wire system which did not rely upon earth return.” [12]
With seven years of experience, Edison in August 30,
1887 in his Specifications forming part of Letters Patent No.
389,280 on page 2, line 34, states:
“All of such conductors from the generators at the station to
the lamps are made in pairs--one for the outgoing current and
the other for the returning current of electricity, the circuits
throughout the system being complete or round metallic
circuits, the conductors of which are well insulated from
each other and from the earth. (Emphasis by the Author)
The use of the earth for one half of the circuit would largely
increase the difficulties arising from the grounding of the
conductors or the crossing of the conductors among
themselves or with the conductors of other circuits to such an
extent that a system so constructed would be impracticable.”
Edison recognized the hazards involved in using the earth
as a return path. “The Edison Three-wire System” is
described in the Instruction book No. 8148, published by the
General Electric Company in Dec. 19, 1900 and consists of a
three wire grounded mid-point at one location only, which
6
supplies phase to phase voltage of 220 and 110 volts for
lighting. This is the basis of the electrical distribution in
homes today. (See figure 5.)
Lights
Loads
+
-
Electric
Current
Generator
Figure 4. Direct Current Electrical System with the Earth
Used as Current Return Path
With a balanced electrical load, that is loads “A” equal to
loads “B” the current in the neutral will cancel and the neutral
will not carry any current. The maximum amount of current
the neutral will carry will be if the load is connected to one
generator only, and only that load, is turned on.
However, an important concept can be learned from figure
5. Figure 5 shows the “A” and “B” loads opposite each other,
which conveniently cancels the neutral current. Let us
assume that the loads are not opposite each other as is
shown in Figure 5 and that the “A” loads are extended beyond
the end of the “B” loads as would occur in an extension of a
single phase circuit.
Loads
+
-
Electric
Current
Generator
+
-
Generator
Lights
A A
B B
Neutral
Postive
Negative
#1
#2 100 V
100 V
200 V
Figure 5. 3-Wire Direct Current Electrical System Conductor
Used as Current Return Path
In the above case, the neutral would be carrying neutral
return current over part of the circuit. If one were to measure
the current on each conductor at the source, it would be a
balanced load. However, out on the system the load would
not be balanced. We will need this concept later. It is also
important to recognize that so far we are dealing with all the
current being contained within a conductor insulated from
earth.
B. Alternating Current Grounding Practices
The Westinghouse-Tesla system of alternating currents
was not always solidly grounded (earthed). The practices of
grounding were first introduced for AC systems in 1885 by
Elihu Thomson. One must note that today European and
Latin American countries may ground (earth) only at the
power source.
Mr. H. H. Dewey states that from the beginning of power
transmission in 1888 or 1890 to 1910 or 1912 that there was
no general practice as regards the question of operating
electrical systems either with grounded neutral or with the
neutral isolated.
Phase A
Phase B
Phase C
2,000 V
2,000 V
2,000 V
Figure 6. Electrical System Secondary Source Connected
in Delta Ungrounded – Not Connected to Earth
“ . . . there was no decided difference in the results
of operating either with the neutral grounded or
ungrounded.. As they (the electrical systems) grew
in extent, voltage surges began to make
themselves felt over wide areas, resulting in
breakdown of insulation at various points. In
seeking a remedy, many engineers grounded the
neutral of their generators or transformers.” [13]
Phase A
Phase B
Phase C
2,000 V
2,000 V
2,000 V
Figure 7. Electrical System Secondary Source Connected
in Wye Ungrounded – Not Connected to Earth
The lack of sufficient insulation to withstand the voltage
surges resulted in grounding the electrical system at the
generator or at the transformers. If more than one
transformer were connected to the system for transmission
purposes, sometimes each transformer was grounded.
Any arcing fault on an ungrounded delta connected
electrical system will result in the electrical system voltage
rising to two, three or to as high as six times the normal
7
voltage from conductor to earth, culminating in insulation
failure [4]. Dewey goes on to write, “The evidence was not
conclusive at that time and perhaps is not conclusive today
(1923) but there are certain fundamental principles that seem
Phase A
Phase B
Phase C
2,000 V
2,000 V
2,000 V
Figure 8. Electrical System Secondary Source Connected
in Wye Grounded – Connected to Earth at One Location Only
– Uni-Grounded
to be reasonable definite and most of them tend to show
important advantages in favor of the grounded neutral
system.”
C. Utilizing the Neutral
In a wye transformer connection the middle point, the
neutral point, can be connected to earth as is shown in Figure
8 without using the neutral for any electrical loads. Figure 9
shows the neutral also connected to earth, but the neutral
conductor is extended along with the phase conductors. The
configuration shown in figure 9 allows electrical loads,
transformers to be placed between any of the three phase
conductors, phase-to-phase and/or phase-to-neutral.
This connection, phase to neutral will force electric current
to flow over the neutral back to the transformer. So far, this
electrical connection is acceptable, as long as the neutral is
insulated or treated as being potentially energized, but
modifications will be made in the future that will negate safety
for the public and animals.
Phase A
Phase B
Phase C
25,000 V
14,400 V
14,400 V
14,400 V
25,000 V
25,000 V
Transformer
Figure 9. Electrical System Secondary Source Connected in
Wye with Neutral Conductor Grounded and a Grounded
Conductor Carried with Phase Conductors – Connected to
Earth at One Location Only – Uni-grounded
In 1914 J. P. Jollyman, et al., writes about the Pacific Gas
and Electric Company’s practices which include the utilization
of the neutral in distribution systems. Transformers are
wound for only 57.7 percent of the insulation voltage
requirements for a full voltage, phase-to-phase transformer.
This amounts to a substantial savings. In addition, there is
only one phase bushing on the transformers. This is
additional savings over the costs of fully rated two bushing
transformer and full transformer insulation rating. The savings
in costs equate to additional profits.
The authors continue to cite additional savings in
construction of the distribution line. The pin type insulator, the
insulator screwed onto a wooden pin mounted in a cross arm,
was the only type that was available in 1904. Savings were
generated by applying only 57.7 percent of the voltage rating
to the insulator. Instead of having an ungrounded electrical
system with 25,000 volts between phases and earth, they now
had, with a grounded neutral, only 14,400 volts to earth from
any phase. There was still between phases 25,000 volts, but
the pin insulator only was stressed to 14,400 volts.
This appears to be a sensible move, but this electrical
configuration led later to other problems. Increasing the
insulation rating would have been one of the correct methods
to resolve the problem along with other solutions that will be
discussed later.
D. Wisconsin Rural Electrification
One of the conditions for harmful stray continuous electric
current flow is the electrical load. As the electrical load
increases the detrimental effects, also increase. In order
to show why dairy farmers are the first to encounter the stray
current problem and are now coming to the forefront of the
stray voltage (incorrect term) or stray current problem, we will
need to go back and look at the growth of both the rural
electrical industry and the dairy industry.
Today the problem manifests itself in the dairy and pig
industry since they are very sensitive to stray current as
compared to humans but as the load increases and
maintenance decreases, tomorrow it will be humans.
Unfortunately, it appears that tomorrow is now making itself
known with the multitude of electric shocks in showers, hot
tubs and swimming pools.
Mr. Post, an early AIEE member [14] writes about the
eastern and southeastern 11 counties served by Milwaukee
Electric Railway & Light Company where there were 21,000
farms. On January 1, 1926 there were only 2,740 farms
receiving electric service, 13 percent of the total. The object
of the utility was to discourage the use of motors and to
encourage the use of lights and electric ranges. Operation of
motors was prohibited from sundown to 11 p.m.
Note that in Figure 10, in 1926 there are two phase
conductors supplying the two bushing transformer. The
secondary neutral is connected to earth at a remote distance
from the pole where the lightning arrester is connected to
earth. This Wisconsin utility started out wiring transformer
and secondary electrical systems correctly in 1926.
“Up to 1923 only about 120,000 of the 6,250,000 farms in
the United States had been wired to use electricity.” By 1930
according to a radio speech made by the General Electric
Company’s President over radio station WGY , “ . . shows
that only about one-tenth of the farms are connected to public
service electric lines and in the second place, that only a small
part of the power used on any farm is electric power.”
This low usage of electricity continued until late 1930s.
There was an increase in the number of farms connected to
8
Figure 10. Pole Mounted 2-bushing Transformer with
Lightning Arrester Separately Connected to Earth with No
Primary Connection to Secondary Conductors, circa 1926.
the electrical distribution systems, however there were few
electric motors used on the farms. The motors that were used
were for water supplies and cream separators. [15]
VI. USING OTHERS PROPERTY WITHOUT
COMPENSATION
A. Lightning Arrester Primary to Secondary Wiring
Connection
In Chicago in 1932, the transformers were failing. By this
time, the NEC was requiring grounding of the neutral in the
electric service to homes. The earthing connection was made
to the metallic water lines.
The Utilities Research Commission of Chicago and the
Engineering Experimental Station at the University of Purdue
conducted an investigation of surge protection of distribution
circuits as to why transformers were failing. Test involved the
interconnection of the primary lightning arrester ground and
the grounded neutral of the secondary main circuit.
The conclusions reached were, “Measurements of the
voltage between primary phase c lead and secondary neutral
have shown that the interconnection of the secondary
neutral with the lightning arrester ground is, in general,
beneficial to the transformer. In particular, with a low
resistance secondary neutral ground and a high resistance
lightning arrester ground, the interconnection reduced the
above voltage by 30 to 50 per cent.” [16]
Instead of lowering the lightning arrester’s resistance to
earth by installing additional ground rods or other methods, at
additional costs to the utilities, the utilities elected to save the
additional cost by using the customers’ connections to earth.
This practice placed the industrial facility, the homeowners
and the farmers in danger from excessive lightning current
flow over the neutral conductor and the ground conductor in
their facilities and the potential of high voltages during the
lightning arresters’ operations.
This connection permitted the hazardous electrical current
from the operation of the lightning arrester to flow into the
customers’ homes, into the homeowner’s ground rod, through
the metallic water piping without their knowledge or consent
which benefited the utility without proper approval or
compensation of the owner of the secondary wiring system.
B. Primary Neutral to Secondary Neutral Connection
The extension of this invasion of the customers’ wiring
systems was when the utilities connected the primary neutral
to the secondary neutral at the transformer and allowed
primary neutral current to flow unimpeded into and over the
customers’ homes, into the homeowner’s ground rod, through
the metallic water piping into their showers, hot tubs and
bathtubs and into the industrial facility without the owners’
knowledge or consent. To comprehend this situation we need
to start with what is a transformer.
H1
H2
Primary Secondary
X1
X2
Figure 11. Transformer Electrically Isolated
Figure 11 shows what is considered by the majority of
electrical engineers as a standard electrical transformer
connection or wiring. Note that on the left side is the primary
winding with two terminals, H1 and H2. For the purposes of
this report, only a step down transformer will be discussed.
The lower voltage windings are referred to as the
secondary. In the case at hand, a primary voltage of 14,400
volts is applied to the primary winding and the secondary
voltage for sake of discussion will be 120 volts. Note that
Figure 11 shows a dividing dashed line separating the primary
windings from the secondary windings.
There are no solid electrical connections between the
primary windings and the secondary windings. The vast
Phase
Neutral
Primary
Winding
Line 2
Line 1
Neutral
Secondary
Winding 120 Volts
120 Volts
Connection to earth
240 Volts
Figure 12. Phase to Neutral Primary Connection with
Secondary winding Center Tapped – Primary and Secondary
Electrically Isolated
9
majorities of electrical engineers are aware of and consider
this the correct wiring for a transformer configuration.
A poll of electrical engineers NOT associated with utilities
were asked if Figure 12 was the electrical wiring diagram for
the transformer located on the pole outside their home, or the
wiring diagram for the pad mounted transformer located on
the ground near their home or if they had an underground
electric transformer vault, the correct representation for the
transformer?
Eighty-five percent of the electrical engineers working in
industrial and commercial facilities, answered yes. The
correct answer is Figure 13 with the solid electrical connection
from the primary neutral to the secondary neutral. Such a
connection is unthinkable and unheard of in the industrial,
commercial and residential electrical engineering fields. Only
electrical engineers working in the utility distribution area are
aware of such a non-standard transformer connection and the
disastrous results of allowing hazardous, stray electrical
Phase
Neutral
Primary
Winding
Line 2
Line 1
Neutral
Secondary
Winding 120 Volts
120 Volts
Connection to earth
240 Volts
Jumper from
Primary Neutral
to Secondary
Neutral
Figure 13. Phase to Neutral Primary Connection with
Secondary winding Center Tapped and the Primary Neutral
Solidly Connected to the Secondary Neutral.
current to flow continuously uncontrolled over the earth,
metallic piping, building steel, into industrial, commercial
facilities, homes and farms.
This is verified by the Institute of Electrical and Electronic
Engineers’ Standard 141, titled, “IEEE Recommended
Practice for Electrical Power Distribution for Industrial Plants”
and IEEE Standard 241, titled, “Recommended Practice for
Electric Power Systems in Commercial Buildings” [17].
Why should one industry, the utility industry, be allowed to
use transformers with such a non-standard transformer
connection considered unsafe and/or unknown of by the vast
majority of electrical engineers just because it saves money?
VII. UNDERSTANDING THE CONTINUOUS FLOW
STRAY CURRENT
To completely understand the flow of stray current a person
needs to 1) understand the definition of stray current and 2)
realize how the current flows over the primary to secondary
neutral connection and into industrial and commercial
facilities, residences or farms and 3) the multigrounded
neutral distribution system with uncontrolled flow of
continuous electric current over the earth and into and through
industrial and commercial facilities, residences or farms.
A. Stray Current
It has been shown previously that it is the current that is
dangerous to the human animal and to the animal kingdom.
Voltage is only the pressure that pushes the current. Voltage
does not burn the body. It is the current that burns the body,
sets the heart into fibrillation, halting the pumping action of the
heart, resulting in death of both.
As long as we know that the mighty Mississippi River is
contained within its banks, everyone is comfortable, satisfied
and content. Likewise, the flow of all electric current must be
contained within an insulated conductor just like the banks of
the Mississippi. When the mighty Mississippi overflows its
banks there is a problem and we become concerned. Just
because we cannot see the flow of electric current over the
earth is no reason that we should not be concerned when the
electric current over flows its “banks”.
Any continuous flow of electric current and the key word is
continuous flow, must be contained within a conductor
insulated from earth and not permitted to flow uncontrolled
over and through the earth, metallic water pipes, building
steel, etc.
When an electric fault occurs it is normal and acceptable
for the fault current to flow over the ground path, whether that
be a green or bare ground conductor or the earth, only for so
long as it takes to open the circuit protective device (circuit
breaker, fuse, recloser or other device). If the wiring system
has been correctly installed, that period of time is very short;
normally less than a second before the protective device,
opens and halts the flow of fault current.
Thus we can now define “stray current” as the
continuous flow of any current, other than momentary
fault current, over the earth, metallic piping, building
steel, into houses and farms, etc. which is thus
objectionable and undesirable to the continued good
health of humans and animals.
B. Parallel Current Paths
A lineman was asked to place an ammeter on the primary
phase conductor of the conductor shown in Figure 13. He
yelled down the reading, “42 amps”. “Would you read the
neutral conductor current please?” he was asked. “22 amps”
he called down. “What happened to the other 20 amperes?”
“Oh! That is normal” he replied. This exchange actually took
place. [18]
Let us look closely at Figure 12, the primary winding of the
transformer. The current enters the conductor on the
conductor labeled “phase”. Now the current flows just like
water in a coil of hose, around and comes out the end marked
“Neutral”. All of the electric current that went into the
transformer on the primary phase conductor, all of it came out
on the primary neutral terminal of the transformer. See Figure
12.
The same is not true of the Figure 13. The current coming
out of the transformer at the primary neutral terminal now has
two paths that the “return current” can take. Some of the
current will flow back on the neutral primary conductor and
some will flow onto the neutral connection to earth on the
10
secondary side of the transformer. In the example above with
the lineman, 20 amperes flowed out the connections to earth
and was uncontrolled and flowed continuously over the earth,
through metallic pipelines, into industrial facilities’ metallic
piping, building steel, commercial buildings’ steel and metallic
piping, residences, metallic piping and over the earth, etc
resulting in hazardous conditions to humans and animals.
One of the methods used to “eliminate” “stray voltage” is to
increase the size of the neutral conductor in utilities
distribution circuits. It is assumed by some that increasing the
neutral size will “prevent” current from flowing over the earth
since the larger neutral has less resistance.
Confusion may also exist over harmonics and their
associated problems. One low voltage distribution system
solution for 3rd harmonics is to increase the neutral.
Harmonics are not applicable in this discussion of stray
current. The following will clarify the fallacy of increasing the
neutral size.
Using Figure 14, let us assume that leaving the transformer
at the neutral is 10 amperes of electrical current. There is a
path using the neutral conductor, path A to B and another
path A to C through the earth to another earth connection D to
B. Since the resistance through the conductor path is 1 Ohm
and equal to the resistance through the earth, 1 Ohm also, the
current will divide equally. There will be 5 amperes through
each path. This is based on Ohm’s Law.
If we keep the resistance of the conductor constant, path A
to B and change the resistance of the path A, C, D to B
through the earth the current flow through the earth values will
change. Using Figure 15, we will keep the resistance of the
conductor from A to B constant at 1 Ohm. The resistance
through the earth, “Z” will change. This change will affect the
amount of current through both the paths A to B through the
conductor and the path through the earth, A to C to D to B.
10 Amps
Resistance 1 Ohm
through the conductor
Resistance 1 Ohm
through the earth
10 Amps
A B
C D
5 Amps
5 Amps
Figure 14. Parallel Path Through A Conductor And Flow Of
Current Through The Earth with Fixed Resistance Values
The point that Table 2 and Figure 15 make is no matter what
the ratio of resistance of path A to B if it is kept at a low value
as compared to path A, C, D, B which is increasing, there will
be some amount of current through the earth. Another way of
saying it is no matter how great the differences in the
resistance of two parallel paths, there will always be some
value of electric current flowing through both parallel paths.
Just because the earth may have a high resistance does not
mean that there will be no current flow over and through the
earth.
10 Amps
Resistance 1 Ohm
through the conductor
Resistance X Ohm
through the earth
10 Amps A B
C D
Y Amps
Z Amps
Figure 15. Parallel Path Through A Conductor And Flow Of
Current Through The Earth with Variable Resistance Values
Current through Current through
Resistance Conductor the Earth
X Ohms Path A to B Path A, C, D, B
1 W 5.00 A 5.000 A
10 W 9.09 A 0.910 A
100 W 9.90 A 0.100 A
1000 W 9.99 A 0.010 A
Table 2. Current through a Parallel Path Using Figure 15.
Just to put into perspective for a male 1.1 mA is the level of
perception “let go” threshold median.
When there exists more than one electrical connection
to earth, no matter what the resistance of the earth is,
there will always be some amount of hazardous electric
current flowing continuously over and through the earth
uncontrolled. Referring to Table 1, it can be seen that any
current exceeding 9 milliamperes (0.009 A) can be
hazardous to humans.
VIII. DANGEROUS PRACTICE OF COMBINING THE
EQUIPMENT GROUNDING CONDUCTOR AND
THE NEUTRAL CONDUCTOR INTO ONE
CONDUCTOR SERVING TWO FUNCTIONS
The next step in the evolution of electrical distribution
would have been Figure 16. Figure 16 shows a substation
symbolized by the secondary wye transformer configuration
with the neutral connected to earth. In addition to having the
neutral connected to earth the neutral is carried on the poles
along with the three phase conductors.
Somewhere along the distribution line, the three phases
are dropped in favor of just one phase conductor. This is
changing from three-phase distribution to single-phase
distribution circuit. A typical load is shown in the form of a
transformer connected from a phase conductor to the neutral
conductor.
In figure 16, the current flow is shown originating at the
substation transformer starting at the neutral connection in the
center of the wye, labeled “N”. The current flow continues to
11
Phase A
Phase B
Phase C
25,000 V
25,000 V
25,000 V
Neutral
Primary
Secondary
Winding
3 Phase Service Single Phase Service
14,400 V
Neutral
Ground Conductor
N
A
B
D
C
Voltage
E
F
Figure 16. Wye Connected Electrical System Grounded at the source, Uni-Grounded With Transformer Connection To Earth At
Only One Location With Both A Neutral And Ground Conductor Carried With The Phase Conductors With Phase-To-Neutral
Loads (Which Generate A Hazardous Neutral Voltage –To–Earth, Point C to E) And A Ground Conductor
point A to point B through the transformer to point C onto the
neutral and continuing on the neutral to point D and back to
the beginning point, the center of the substation transformer
N.
The neutral conductor has resistance. With current flowing
through the neutral conductor, which has resistance, a voltage
will be developed between point “C” and point “D”. The
voltage on the neutral at point “C” to earth point “E” can be
high enough, depending on resistance and amount of current,
to cause harm to a person, especially a lineman. Even
though this wiring configuration contains all the continuous
current flow within a conductor insulated from earth, there is a
problem with a voltage build up from the neutral to earth along
the length of the neutral conductor especially if it is on a pole
and bare.
Since there is a voltage developed between the neutral
conductor and the ground conductor, the neutral conductor
should be treated as an energized conductor and installed on
insulators, which add additional costs to the electrical
distribution system and result in additional costs for the
utilities. This type of electrical system allows the use of the
less costly phase-to-neutral transformer.
Figure 16 is referred to as a 5-wire electrical distribution
system consisting of one, two or three phase conductors, an
insulated (from earth) neutral and an “equipment grounding
conductor”. This is exactly like what has been used in low
voltage electrical distribution system in industrial and
commercial facilities since approximately the 1950s.
Again, costs were the determining factor in resolving the
problem with the difference in voltage between the neutral and
the earth. Instead of installing, the neutral insulated from
earth and treating the neutral as an energized conductor, the
utilities took the least costly way and multigrounded the
neutral thus reducing the build up of harmful potential to the
linemen to less than approximately 25 volts at the mid-location
between grounding points.
IX. MULTIGROUNDED NEUTRAL
The least costly solution to the problem with a voltage build
up between the neutral and the ground conductor as shown in
Figure 16 was to combine the function of the neutral and the
ground conductors into one conductor. This combination of
the neutral conductor and the ground conductor is called
“multigrounded neutral”.
When a fault of a primary conductor to earth occurred it
was necessary to have low impedance paths back to the
substation transformer in order that sufficient electrical current
would flow to operate the protective device, the fuse, circuit
breaker or recloser. In order to insure a low resistance,
impedance path back to the source it was necessary to earth
the multigrounded neutral conductor just like when there were
two separate conductors, the neutral and the ground as
shown in Figure 16.
Figure 17 shows the multigrounded neutral system. In
Figure 16 all the current is contained within an insulated
conductor; See path “N” to “A” to “B” through the service
transformer to “C” to “D” and back to the starting point “N”.
With a multigrounded neutral distribution system it is
necessary to have an electrical connection to earth at least 4
times per mile to keep the voltage on the multigrounded
neutral from exceeding approximately 25 volts making it safe
for the linemen should they come into contact with the neutral
and the earth. See NESC Rule 096 C in the section on the
National Electrical Safety Code.
With the multigrounded neutral conductor connected to
earth at least 4 times per mile and at each transformer and
lightning arrester there are now multiple paths over and
through the earth that the hazardous electric current can flow
over continuously, uncontrolled. The solid arrows in Figure 17
indicate this hazardous current flow. This flow of hazardous
electric current, which is shown with the solid arrows, is
created as primary current only. Additional primary current
may be produced by unbalanced electrical loads.
12
Phase A
Phase B
Phase C
25,000 V
25,000 V
25,000 V
Mulitgrounded Neutral
Primary
Secondary
Winding
3 Phase Service Single Phase Service
14,400 V
N
A
B
D
C
Voltage = 0
Figure 17. Wye connected at the source primary electrical system multigrounded neutral showing the continuous current flow
through the earth when utilizing phase-to-neutral loads
Phase
Neutral
Line 2
Line 1
120 Volts
120 Volts
240 Volts
Secondary
Winding Grounding
Conductor
Earth Connection
from Service
Entrance Panel
Equipment Grounding Conductor
Line 1
Primary Winding
Neutral
Jumper from
Primary Neutral
to Secondary
Neutral
Service
Entrance
Panel
Well Casing
Indicates
Hazardous
Uncontrolled
Stray Primary
Current Flow
Utility Mr. Allen's Property
Connection to earth
Figure 18. Wiring diagram showing the hazardous uncontrolled stray primary current flow over the customer’s property.
A. Hazardous Electrical Current Flow
Figure 17 shows just part of the primary current flow into
the earth. The path that this current flow takes through the
earth cannot be determined. We cannot put an isotope on
each electron and trace its path as it flows uncontrolled
through the earth.
Public Service Commissions and Utilities are obligated to
provide adequate electrical service without any adverse
effects. It is irresponsible to permit stray uncontrolled electric
current to flow into and over private property. This act is
hidden from view, as the public is very unaware of what is
being done by the utilities. It is not advertised on TV nor is
information included in the bill sent to the utility customers.
Customer
13
B. Primary Neutral Current Entering through the Service
Transformer (S)
As was explained previously in the section titled, “Lightning
Arrester Primary to Secondary Wiring Connection” in 1932,
The Utilities Research Commission of Chicago and the
Engineering Experimental Station at the University of Purdue
conducted an investigation of surge protection of distribution
circuits. The conclusions reached were, “Measurements of
the voltage between primary phase c lead and secondary
neutral have shown that the interconnection of the
secondary neutral with the lightning arrester ground is,
in general, beneficial to the transformer.”
This connection and the adverse effects are shown in
Figure 18. The primary current leaves the transformer
winding and has a fork in the path. One path is back to the
substation over the multigrounded neutral conductor. In many
cases, the neutral conductor is of a smaller size than the
phase conductor supplying the current and the multigrounded
neutral conductor has many high resistance twist connections
which increases the impedance of the line forcing more and
more current into the earth uncontrolled.
In addition, the neutral current can now flow over the
jumper between the primary neutral conductor and the
secondary neutral conductor as is shown in Figure 18. The
NESC requires the transformer’s neutral to be connected to
earth at the transformer. This is the first connection to earth in
Figure 18. Just because the NESC has a Rule that requires
something to be accomplished does not make it safe or
correct as will be covered later. In fact, a judge made such a
ruling in a case.
The distribution line and the product, electrical energy, are
inseparable and thus, become one. A Court has concluded
that electricity is a product by holding as follows: “It is no
answer for a company engaged in the public sale of such a
highly destructive agency as electricity to say that
precautionary measures which may have been adequate to
meet the test of due care 50 years ago when the lines were
installed, must be regarded as sufficient in modern industrial
society.“1
The National Electrical Code (NEC) requires the neutral in
the service disconnect and overcurrent panelboard to be
connected to the earth also. Now the secondary neutral is
connected to earth a second time. A parallel connection of
the neutral to earth now exists permitting hazardous electric
current to flow continuously uncontrolled over the earth.
The equipment-grounding conductor has to be connected
to everything that is metal and contains an electric conductor
as per the NEC. The well casing offers another path to earth,
the third parallel path contributing to the flow of hazardous
uncontrolled electric current over the earth.
The discussion thus far has been about the hazardous
stray continuous flowing primary neutral current from the
electrical system owned and operated by the utility. This
hazardous stray primary neutral current flowing continuously
over the earth is the major contributor to the flow of
uncontrolled stray current.
1 Black v. Public Service Electric & Gas Co.
In addition to the primary electrical stray current, there are
additional stray current sources flowing from the secondary
side of the service transformer.
C. Fee for Using the Utilities Poles by Other Utilities
The communication and cable companies when mounting
their conductors on utility companies’ electric power poles
compensate the utility company for their use.
Assume that Mr. Utility Customer wanted to communicate
with his brother’s house located on an adjacent street by
utilizing an electronic communication device and the existing
power conductors of surreptitiously. There would be no
interference with the normal electric power distribution
system. Such action would no doubt be considered by the
utility company as utilization of their electric lines without
adequately compensating. Alternatively, consider a person
hanging his own conductors on the utility company’s poles,
the utility company would want compensation for the use of
their poles.
The original wiring installed in and on Mr. Customer’s
property after the electric service meter was paid for and
owned by Mr. Customer. That wiring consists of the neutral
conductor being connected per the National Electrical Code to
a driven ground rod supplied and owned by Mr. Customer.
The internal electrical wiring on Mr. Customer’s property has
the neutral connected to the metallic water piping system and
is owned by Mr. Customer.
The utility has usurped Mr. Customer’s internal wiring
system for the enhancement of their electrical system in order
to reduce the utility’s costs for the benefit of the transformer.
The National Electrical Code (NEC) requires the neutral in the
service disconnect and overcurrent panelboard to be
connected to the earth through the grounding conductor. Now
there is a second connection to earth. A parallel connection
of the neutral to earth now exists permitting current to flow
continuously uncontrolled over the earth.
The equipment-grounding conductor has to be connected
to everything that is metal and contains an electric conductor
as per the NEC. The well casing offers another path to earth.
The discussion thus far has been about the stray
continuous flowing primary neutral current from the electrical
distribution system. This stray primary neutral current flowing
continuously over the earth is the major contributor. There
are additional stray current flows from the secondary side of
the service transformer.
D. Total Primary and Secondary Hazardous Uncontrolled
Continuous Stray Current Flows
Figure 19 shows the magnitude of the points where the
hazardous uncontrolled continuous flow of primary and
secondary current can originate. The single phase-to-neutral
transformer electrical circuit originates at the “N” in the center
of the transformer winding. The current flows to point “A” to
point “B” and through the primary winding of the service
transformer.
As the current exits the transformer winding there is a fork
in the circuit and one branch continues to “C to “D” and back
to the beginning. However, the other path is the primary
neutral to secondary neutral, point “K”. From point, “K” the
14
Phase A
Phase B
Phase C
25,000 V
25,000 V
25,000 V
Mulitgrounded Neutral
Primary
3 Phase Service Single Phase Service
14,400 V
N
A
B
D
C
Secondary
Winding
Voltage = 0
Neutral
Line 2
Line 1
Equipment Grounding
Conductor
Well Casing
E
F
G
H
J K
Wisconsin Public Service Corporation
Customer
Figure 19. Wye Connected Electrical System Multigrounded Neutral with Primary Neutral to Secondary Neutral Electrical
Service Connection Showing the Hazardous Stray Uncontrolled Primary Current Flow.
current can flow to the ground rod at the base of the pole,
point “E” and into the earth, uncontrolled.
The other path is to point “J” down to another junction point
where the stray current can flow into the earth at point “F” or
into the earth at the well casing, point “G”. There is another
branch allowing the stray current to flow onto the “equipment
grounding conductor and into the earth at every point where
the equipment grounding conductor touches earth.
Figure 19 also shows the secondary electrical system
where the primary and secondary continuous flowing stray
uncontrolled current entered the earth at points E, F, G and H,
but not limited to these points.
X. A RECOMMENDED SAFE METHOD FOR
ELECTRICAL DISTRIBUTION
Figure 20 shows the source transformer at the substation
as a wye connected transformer, uni-grounded. The phase
conductors are insulated from earth just as the present day
phase conductors are. The ground conductor is earthed at
multiple places. This multiple earthing of the ground
conductor allows any fault current that enters the earth,
should a phase conductor fall to earth, to flow over the lower
impedance path of the ground conductor and over the earth
back to the neutral point of the transformer. This improves the
safety of the electrical distribution system.
The load transformers are electrically connected phase-tophase
not in the present method of phase-to-neutral. This
requires a two bushing transformer and fully rated insulation in
the transformer.
The lightning arresters are connected to the grounding
conductor, which has a low impedance connection to earth
because of the four connections to earth plus the connection
at each transformer can and lightning arrestor.
To accomplish this improved electrical distribution system
requires the installation of another insulated phase conductor,
which should have been installed in the beginning. The
present “multigrounded neutral” conductor becomes the
ground conductor.
Since the lightning arrester now has a low impedance earth
connection due to the multiple earthing connections of the
ground conductor, it is no longer necessary to use the
earthing systems of the customers to obtain a low impedance
connection to earth for the lightning arrestor successful
operation. With the now required two bushing, full phase-tophase
voltage across the service transformer there will be no
primary neutral current or primary neutral terminal on the
service transformer.
Since there is no primary neutral the non-standard,
transformer electrical connection of the primary neutral to
secondary neutral cannot be made. Thus, the flow of primary
current into the secondary side and into the customer’s
property will not exist. With this electrical distribution system,
that does not have any primary neutral connections to earth,
the customer will no longer have hazardous stray continuous
electrical current from the primary distribution system flowing
over his property or nearby earth.
XI. TRANSFORMER CONNECTED 3
PHASE, 5-WIRE GROUNDED WYE WITH LOADS
PHASE-TO-PHASE OR PHASE-TO-NEUTRAL
CONNECTIONS
Figure 16 shows an alternate method that is also safe for
the public and animals. It is known as the 5-wire system.
This system has been shown to reduce stray currents. [19]
This second type of system that is safer than a
multigrounded neutral distribution system is a 3 phase, 5-wire
grounded wye with all loads either phase-to-phase or phase-
Utility
15
Phase A
Phase B
Phase C
25,000 V
25,000 V
Primary
3 Phase Service Single Phase Service
Ground Conductor
N
A
B
D
F
Secondary
Winding
Neutral
Line 2
Line 1
Equipment Grounding
Conductor
Well Casing
H
K
J K
(1)
(2)
(3)
(4)
Service
Entrance
Utility Customer
120 V
120 V
240 V
G
C
25,000 V
Figure 20. 4-Wire, Wye Connected Electrical System Grounded at the Substation Only and at the Service Transformer
Secondary Side Only with Complete Electrical Isolation from Earth and All Continuous Electric Current Contained in Conductors
Insulated from Earth.
.
to-neutral connections. The fourth conductor is a neutral
insulated from earth. This type of electrical distribution has
been in existence within industrial and commercial facilities for
over 50 years. In the case of utilities, the neutral is treated as
an energized conductor
This electrical configuration is considered one of the most
desirable and safest type of electrical distribution systems for
the simple reasons that whenever a phase comes into contact
with the earth or the ground conductor, the fifth wire, the
ground conductor, which is connected to earth at frequent
intervals and is directly connected back to the transformer
allows the placement of protective devices that can detect low
levels of fault current to trip immediately.
Depending on the configuration of the circuit the fault
current detection could be as low as approximately 25 to 50
amperes or lower and can be made to open the circuit
removing the voltage from the circuit as compared to the 100,
150, 200 amperes or more current required to operate the
protective device.
The utilities saved billion and billion of dollars over the
years by utilizing the multigrounded neutral distribution
system. The cost to fix or solve the problem is much less
since the transformers can be re-used. The cost to add a
single bare neutral is all that is required. The existing
multigrounded neutral conductor would be converted to the
ground conductor and the required NESC four ground rods
per mile already exist. The costs to correctly wire the circuit
or circuits system wide would be minimal, considering only
one additional conductor would have been required. It has
been estimated that the costs would be approximately
$ 10 000.00 per mile and could be accomplished in the same
fashion that the three wire receptacle was phased in – over a
period of years.
It is reported by Mr. Lawrence C. Neubauer, Master
Electrician who has tested many dairy farms in California that
the utilities in the dairy areas of California do not use
multigrounded neutral distribution system. There are no
reports of stray current from the primary system.
There are no prohibitions in the NESC against such an
electrical installation. Electric Power Research Institute
(EPRI), an organization of the electric utilities, conducted
extensive testing of the 5-wire electrical distribution system.
The experimental facilities of the utilities have installed and
tested such a safe electrical distribution system in New York
State and have made the report available to their EPRI
members.
B. Make the Secondary Service Conductors Safe
Initially, if utility companies had used four (4) service drop
conductors, Figure 20, conductors (1), (2), (3) and (4), the
secondary neutral earthed at the transformer as it should be,
and the secondary neutral an insulated conductor, this would
have resulted in a very safe electrical service drop without any
continuously flowing stray electric current over the earth.
By bringing the insulated phase and insulated neutral
conductors plus the equipment-grounding conductor to the
customer there will be no need to re-earth the neutral in the
service disconnect and overcurrent panelboard. The reearthing
of the neutral a second time in the service panel
results, as has been shown, in parallel continuous stray
electrical current paths.
XII. ARGUMENTS TO CONFUSE
There will be presented arguments that will try to show the
system as shown in Figure 20 cannot work because of various
excuses. One such argument will state lightning strikes will
destroy the transformer unless the transformer is connected to
the secondary circuit. Or that the primary neutral must be
16
connected to the secondary neutral in order to “stabilize the
system”. This is pure poppycock, a new technical term.
In the intervening years since 1932, the utility industry has
forgotten the reason for the resultant connecting of the
primary neutral to the secondary neutral. The intermediate
step was the adoption of the multigrounded neutral distribution
system, which connected the lightning down connection to
earth to and through the multigrounded neutral conductor,
which was connected to earth multiple times, and the
multigrounded neutral conductor was connected to the
secondary neutral since it was “beneficial to the
transformer”. In the industrial world of electrical distribution,
Figure 20 is the method used to install electrical distribution
systems every day for over 50 years or more.
It will be granted that transformers were not as well
constructed in the 1920s as they are today. Failures were
common due in some part to poor lightning arrester design
and insulation methods as cited above. Transformers today
rarely fail and when they do the fail, the mode of failure is not
one where the primary voltage is applied to the secondary
winding causing the users to have high voltage on their
electrical circuits.
In fact, in a recent Virginia Division of Energy Regulation,
State Corporate Commission action concerning VEPCO
where VEPCO dropped a 25,000-volt line onto a 12,470-volt
distribution line the voltage at the service entrance was
calculated to have risen only to 334 volts maximum. The
point is even with the primary connected to the secondary
there was still a voltage rise at the customer services. Not
everyone suffered electrical damage even after this happened
four times. There were no transformer failures reported.
Like many things in the past, the utilities were aware of the
cost savings and may not initially been aware of the safety
concerns. It can be argued that once a practice is begun, it is
often difficult to undo what has been done. However, it can
and has been undone.
Proof that this non-multigrounded neutral electrical
distribution system functioning safely can be found in
California’s Public Utilities Commission’s General Orders –
95.
A. California’s Public Utilities Commission’s General Orders –
95
On January 19, 1994 the California’s Public Utilities
Commission in their General Orders – 95 generated a
resolution SU-25 resulting in Rule 33.2.
33.2 Ground or Earth as a Conductor
Ground or earth shall not be used as a normal return or
circuit conductor. In direct current supply systems or in
single phase or polyphase supply systems, a neutral or any
other conductor shall be used under normal use as a return
or circuit conductor; however, the grounding of the neutral
or any other conductor is not permitted as a normal return
or circuit conductor. The neutral or any other conductor is
permitted to be grounded only for the purposes of
stabilization and protection.
In California, there is another term “messenger” that is
used that has a different meaning and application elsewhere
in the rest of the utility companies. California applies the term
messenger correctly.
21.11 Messenger
means stranded wires in a group and which generally is not
a part of the conducting system, its primary function being
to support wires or cables of the conducting system;
sometimes called "suspension strand".
The messenger has been corrupted into serving as not only
a messenger, but as a combined neutral and ground
conductor as will be discussed in detail later.
B. Transformers – Two Bushing Type – Two Phase
Conductors
Two bushing transformers are required in California. Two
bushing phase-to-phase transformers have full voltage
Figure 21. Left – Single Bushing Transformer With Ground
Strap Connecting Secondary Neutral To Metal Can Of
Transformer (Shown just above the “10”), Which Is the
Primary Connection. Right – Two Bushing Transformer.
insulation rating where as a phase-to-neutral transformer has
only 58 percent insulating rating, resulting in a savings in
material cost in insulation and bushings.
A two bushing transformer eliminates any neutral current,
thus there are no hazardous uncontrolled stray continuous
flowing current over the multigrounded neutral conductor to
earth since there is no need for any multigrounded neutral
conductors
17
XIII. CONFLICT BETWEEN NATIONAL
ELECTRICAL SAFETY CODE AND THE
NATIONAL ELECTRICAL CODE
The National Electrical Safety Code Rules govern the
electrical installation up to the service point, which include the
service transformer. The service point is usually the electric
meter or the line of demarcation between the utility and the
customer.
“NESC Rule 011.Scope
B. The NESC covers utility facilities and functions up to
the service point.
NOTE: The National Electrical Code. (NEC.), NFPA 70-
1999 covers utilization wiring requirements beyond the
service point.”
There is lack of trust between the two code making bodies,
the NESC and the NEC. Both bodies want the neutral to be
connected to earth, ground. The most logical place to make
this electrical connection to earth is at the transformer. The
IEEE industrial and commercial electrical engineers state this
in the IEEE Standard 141 [17].
The NEC fearing the utility companies will not ground the
neutral at the transformer and the utilities supplying only a 3-
wire service using the messenger for triple duty, requires the
neutral to be grounded a second time at the service
disconnect and overcurrent panelboard. This second
grounding of the neutral on the secondary side of the
transformer results in a parallel path condition and the
problem of hazardous stray secondary neutral currents.
In addition, the utilities insist saving money by combining
the neutral conductor with the ground conductor and the
messenger support wire; three functions into one conductor.
It would be acceptable to combine the ground conductor
and the messenger, but not include the neutral conductor.
The neutral conductor must be insulated like the phase
conductors, from earth except at the transformer. In the
service disconnect and overcurrent panelboard the neutral is
connected again to the earth using the grounding conductor.
See Figure 22.
A. Joint NESC and NEC Meeting Rejected
To resolve the conflict between the NESC and the NEC
over the neutral being grounded by both code-making bodies
at different locations a letter was sent to the Chair of both
organizations requesting a joint meeting. This suggestion was
based on the joint meeting of the NEC with the Canadian
Electrical Making Code body to have uniform adoption by both
codes of the European method of hazardous location
installation, the IEC’s Zones method. Both bodies rejected
the suggestion for the NEC and the NESC meeting.
The members to the National Electrical Safety Code
making body have their way paid by their utility employers.
This is a clear conflict of interest. When one considers that
utility employees have lived with the errors that were made in
the distant past it should be no surprise to a person that utility
employees would hesitate to try and change something
management would be opposed to if it would cost additional
funds.
Phase
Neutral
Line 2
Line 1
Secondary
Winding
Primary Winding
Indicates
Hazardous
Uncontrolled
Stray Secondary
Current Flow
Connection to earth
120 Volts
120 Volts
240 Volts
Grounding
Conductor
Earth Connection
from Service
Entrance Panel
Equipment Grounding Conductor
Line 1
Neutral
Service
Entrance
Panel
Well Casing
Mr. Allen's Property Utility
The Neutral conductor
is combined with the
Ground Conductor and
All conductors are supported
by the messenger
Figure 22. Conflict between the NESC and the NEC over the Grounding of the Neutral.
Customer
18
B. Proposals to the NESC to Fix the Service Drop
Conductors Rejected
Contributing to the conflict is the fact that the conductors
that run from the utilities’ pole to the house consists of only
two-phases, also known as hot or energized conductors and a
messenger to support the two-phase conductors.
A neutral must be delivered to the house. The utilities have
saved millions and millions of dollars by combining the neutral
with the messenger when the neutral should be, for safety
purposes, an insulated conductor.
In addition, the grounding of the transformer generates an
equipment-grounding conductor that must also be carried into
the house. In summary, the utilities should have supplied the
following conductors in the service to any residence:
· Insulated either two or three phase conductors. (Line 1
and Line 2 in Figure 22.)
· Insulated neutral.
· A bare wire connected to the grounding conductor at
the transformer and used as a messenger to support
the above-insulated conductors.
Figure 23 shows the correct number of conductors installed
between the transformer and the home. A proposal was
submitted to both code making bodies, NEC and the NESC
that would permit the correct number of service drop
conductors if the homeowner paid the difference. In other
words, there would be no additional cost to the utility, for the
correct installation of service conductors that would prevent
the flow of continuous electric current over the earth and/or
home. This proposal was soundly rejected by the NESC,
receiving only one vote, that of this writer.
No doubt, it was surmised that if such an admittance of
incorrect electrical installation were acknowledged by the
adoption of such a Rule change, the utilities would be
inundated with legal action by homeowners. No such legal
action to this writer’s knowledge has occurred in California.
C. Proposals to the NEC to Fix the Service Drop Conductors
Rejected
Proposals and comments have been made to the National
Fire Protection Association’s National Electrical Code Making
Panel to change the service entrance conductors as
described above. The proposals and comments were soundly
rejected by the NEC with the excuse that it is the domain of
the NESC.
Phase
Neutral
Line 2
Line 1
Secondary
Winding
Primary Winding
120 Volts
120 Volts
240 Volts
Grounding
Conductor
Line 1
Service
Entrance
Panel
Indicates
Hazardous
Uncontrolled
Stray Secondary
Current Flow
(There is none)
Connection to earth
Earth Connection
from Service
Entrance Panel
Well Casing
Customers Utility
Neutral N
EG
Each Function, Phase Conductor(s),
Neutral Conductor, and Equipment
Grounding Conductor have their own
conductor and none are combined with
any other function/conductor.
Equipment Grounding Conductor
Figure 23. The Correct Number of Conductors for the Utilities Service Entrance
However, the NEC does require and has specifications for
the conductors that connect with the utility’s service drop
conductors. Each, the NESC and the NEC say that they
would consider making the change if the other code making
19
body would do so first. Yet, both bodies refuse to meet in a
joint meeting to iron out the conflicts.
D. Proposals to the NEC to Prevent adoption of
Multigrounded Neutral Rejected
Before the NEC’s 2002 code edition, Section 250.184 read
as follows:
Section 250-184. Solidly Grounded Neutral Systems
(a) Neutral Conductor. The minimum insulation level
for neutral conductors of solidly grounded systems shall be
600 volts.
Exception No. 1: Bare copper conductors shall be
permitted to be used for the neutral of service entrances
and the neutral of direct-buried portions of feeders
Exception No. 2: Bare conductors shall be permitted for
the neutral of overhead portions installed outdoors.
FPN: See Section 225-4 for conductor covering where
within 10 ft (3.05 m) of any building or other structure.
(b) Multiple Grounding. The neutral of a solidly
grounded neutral system shall be permitted to be grounded
at more than one point for the following:
1. Services
2. Direct-buried portions of feeders employing a bare
copper neutral
3. Overhead portion installed outdoors
(c) Neutral Grounding Conductor. The neutral
grounding conductor shall be permitted to be a bare
conductor if isolated from phase conductors and protected
from physical damage.
During the NEC 2002, cycle there was proposed expansion
of NEC Section 250.184.
(D) Multigrounded Neutral Conductor. Where a
multigrounded neutral system is used, the following shall
apply:
(1) The multigrounded neutral conductor shall be of
sufficient ampacity for the load imposed on the
conductor but not less than 331/3 percent of the
ampacity of the phase conductors.
Exception: In industrial and commercial premises
under engineering supervision, it shall be permissible to
size the ampacity of the neutral conductor to not less
than 20 percent of the ampacity of the phase conductor.
(2) The multigrounded neutral conductor shall be
grounded at each transformer and at other additional
locations by connection to a made or existing electrode.
(3) At least one grounding electrode shall be installed
and connected to the multigrounded neutral circuit
conductor every 400 m (1300 ft).
(4) The maximum distance between any two adjacent
electrodes shall not be more than 400 m (1300 ft).
(5) In a multigrounded shielded cable system, the
shielding shall be grounded at each cable joint that is
exposed to personnel contact.
This writer made a presentation to the NEC Making Panel #
5 at the beginning of the 2002 cycle proposal stage explaining
the fallacies of such action. Since a subcommittee made the
proposal and the proposal was taken from the NESC, it is
believed the committee’s proposal was received with validity
where as an individual opposing the NESC was not.
In addition, one must realize that the NEC Making Panel #
5 is extremely slow in making correct decisions. This was
evident in the adoption of the same four wire as described
above for electric ranges and dryers. Beginning in 1944
because of the war effort electric ranges and dryers were
allowed to combine the neutral and the equipment grounding
conductors to save copper “for the duration”. There was
never a definition of the term, “for the duration” and the
duration lasted 50 years.
In 1950s, the NEC adopted the safety policy of the threewire
grounding system prevalent in homes, commercial and
industrial facilities. House trailers were wired using the
incorrect method of combining the equipment-grounding
conductor with the neutral. This action resulted in many
electrical deaths and electrical shocks when someone
touched the metal sides of the trailer and was standing on wet
ground.
The NEC Making Panel handling Articles 550 and 551,
trailers and mobile homes about 1968 made mandatory wiring
that had insulated phase conductors (2) and a separate
insulated neutral conductor and a bare or insulated
equipment-grounding conductor. This separation of the
neutral and the equipment-grounding conductor eliminated
electrocutions and electrical shocks from the metal siding of
trailers and mobile homes of persons standing on wet earth or
in water and touching the metallic siding.
The very next NEC cycle, 3 years later, the panel
responsible for marinas made the very same change.
However, NEC Making Panel # 5 resisted making the same
change for electric ranges and dryers for over 21 years. The
author was told that NEC Panel # 5 had not heard of anyone
being electrocuted thus there was no need to make any
change in the wiring for ranges and dryers and continued to
allow the combining of the neutral and the equipment
grounding conductors. However, persons were receiving
electric shocks from electric dryers. Finally, after over 21
years, in 1996, NEC Making Pane # 5 made the change and
now the NEC requires that all new electric ranges and dryers
be wired with insulated phase conductors (2), a separate
insulated neutral conductor and an equipment-grounding
conductor. Safety at last prevails with trailer homes, marinas,
ranges and dryers. However, the service conductors still pose
a problem.
There are several points to be made from the above
discussion.
The logical progression from trailers to marinas to ranges
and dryers has been accomplished. The next step is the
service entrance conductors.
The majorities of the members of the National Electrical
Safety Code Making Panels are employed by or sell services
to the utilities, and thus are reluctant to make code changes
that will cost their employers or clients’ additional funds.
The majorities of the members of the National Electrical
Safety Code Making Panels have probably been employed
only by utilities and thus are very comfortable with the existing
multigrounded neutral electrical distribution system since it is
the only electrical distribution system with which they have
worked and with which they are familiar.
20
XIV. LEGISLATION AND REGULATION
It is interesting to note the courts thinking on code and
legislature enactments. Wisconsin legislation states:
“Sec. 288C. Compliance With Legislation or
Regulation.
“Compliance with a legislative enactment or an
administrative regulation does not prevent a finding of
negligence where a reasonable man would take additional
precautions.” 2
A New Jersey court has stated:
“An uninsulated high voltage power line carrying a
deadly current must be considered one of the most
dangerous contrivances known to man. In the pursuit of its
business, by installing and maintaining such a line, a utility
company must use care commensurate with the risk of
harm, i.e. a high degree of care, to others who in the
course of their ordinary and lawful activities might suffer
injury, death or damage therefrom. In the utilization of such
deadly wires along, adjacent to, across or over public
highways, streets or ways, or private property, the (utility)
company must be aware not only of the killing quality of its
high-voltage lines, but also need to adjust the degree of
care exercised in its control and maintenance of such
wires.” 3
It was not until the period of 1942 to 1950 that the ability to
determine the amount of current humans are sensitive to
began. Excluding the EKG studies, which began about 1921,
it was in the 1950 to 1974 period that the amount of electric
current controlling the heart became known. These studies
resulted in the defibrillator being developed.
Unfortunately, the use of the earth as a partial return path
was permitted in the April 15, 1927 Edition of the National
Electrical Safety Code although the wording is vague.
NESC Rule 012 C General Rules - 1927
C. For all particulars not specified in these rules,
construction and maintenance should be done in accordance
with accepted good practice for the given local conditions
known at the time by those responsible for the construction or
maintenance of the communication or supply lines and
equipment.
“NEC Rule 215 C Use of Ground as Part of Circuit -
1927
In urban districts, supply circuits shall not be designed to
use the ground normally as the sole conductor for any part of
the circuit.
Recommendation. --- It is recommended that such use be
avoided in rural districts.”
“NESC Rule 215. C. Use of Ground as Part of Circuit -
1927
“The use of the ground for the return portion of telegraph
circuits and other communications and signaling circuits has
long been customary and is for many purposes satisfactory, . .
. For supply purposes a similar arrangement has been
sometimes used, but it has objections from both the service
and the accident standpoints, and its use is considered
undesirable.”
2 Kemp v. Wisconsin Electric Power Co., 44 Wis.2d 571, 579
(1969), quoting Restatement, 2 Torts 2d, p. 39.
3 Black v. Public Service Electric & Gas Co.
At that time, the NESC also lacked the understanding of
hazardous levels of current as is evident from the following:
“(c) Current in grounding conductor. - Where multiple
grounds are used there is a possibility of circulating currents
between the different ground connections, arising from
unbalanced loads, improper connection of grounding wires,
and for other reasons. It is advisable to ascertain the
amount of this current flow when the grounds are made in
order to make certain that it is not great enough to be
objectionable. A fraction of an ampere, or even several
amperes on circuits of large capacity, may not be a serious
matter, but cases can easily arise where the flow would be
sufficient to be disturbing to the service.”
As we see from above the amount of electric current to
cause harm to humans and animals is extremely small, not
“even several amperes on circuits of large capacity”. We
know today that that statement is false. Nevertheless, the
warning was there.
A. Failure of the National Electrical Safety Code to Protect
the Public
The National Electrical Safety Code states in the beginning
of the Code the purpose.
NESC Rule 010.Purpose - 1997
“The purpose of these rules is the practical safeguarding of
persons during the installation, operation or maintenance of
electric supply and communication lines and associated
equipment.
“These rules contain the basic provisions that are
considered necessary for the safety of employees and the
public under the specified conditions.”
B. Removal of or Disconnection of Grounding Down
Connections
In order to protect from the objectionable hazardous stray
continuous flow of electrical current the NESC allows removal
of or disconnection of grounds.
“NESC Rule 092 - 1997
“D. Current in Grounding Conductor
“Ground connection points shall be so arranged that under
normal circumstances there will be no objectionable flow of
current over the grounding conductor. If an objectionable flow
of current occurs over a grounding conductor due to the use
of multi-grounds, one or more of the following should be used:
1. Abandon one or more grounds.
2. Change location of grounds.
3. Interrupt the continuity of the conductor between ground
connections.
“Subject to the approval of the administrative authority, take
other effective means to limit the current. The system ground
of the source transformer shall not be removed. The
temporary currents set up under abnormal conditions while
the grounding conductors are per-forming their intended
protective functions are not considered objectionable. The
conductor shall have the capability of conducting anticipated
fault current without thermal overloading or excessive voltage
buildup.”
Thus, it is acceptable to remove the parallel connections
once it has been shown that irreparable damage has been
inflected.
21
Section 250-6(b) and (c), NEC – 1999, also states:
“(b) Alterations to Stop Objectionable Current. If the
use of multiple grounding connections results in an
objectionable flow of current, one or more of the following
alterations shall be permitted to be made, provided that the
requirements of Section 250-2(d) are met.
“Discontinue one or more but not all of such grounding
connections.
“Change the locations of the grounding connections.
“Interrupt the continuity of the conductor or conductive path
interconnecting the grounding connections.
“Take other suitable remedial action satisfactory to the
authority having jurisdiction.
(c) Temporary Currents Not Classified as Objectionable
Currents. Temporary currents resulting from accidental
conditions, such as ground-fault currents, that occur only
while the grounding conductors are performing their intended
protective functions shall not be classified as objectionable
current for the purposes specified in (a) and (b).”
The currents that are continuously flowing currents over the
earth, are objectionable. On the other hand, nonobjectionable
currents are those that flow over the earth
momentarily until a protective device such as a fuse, circuit
breaker or recloser operates to stop the current flow.
XV. UNGROUNDED ELECTRICAL DISTRIBUTION
SYSTEMS
Another very dangerous to the public and to utility linemen
is the ungrounded electrical distribution system. With only the
capacitance connection to earth there is less likelihood that
the normal ungrounded electrical distribution system will
operate the protective devices at a low value of current, when
a person comes into contact with the energized lines.
An example is a case where a 12 year old boy riding his
bicycle on the payment after a storm when an energized
conductor snapped and wrapped around his neck. He laid on
the ground with the energized conductor around his neck
smoking while his parents watched helplessly for between 20
and 45 minutes. The utility linemen had to cut the line before
it was safe to attend to his lifeless body. [20]
Another case involved a lineman who was accustomed to
multigrounded neutral distribution system and during storm
duty was sent to another utility where the distribution system
was ungrounded. He fuzzed the line and getting no response
somehow touched the line and was electrocuted.
XVI. GFCI – PROTECTION AGAINST ON SITE
STRAY CURRENT
The GFCI contains two electronic circuits. One circuit
measures the amount of current flowing on the phase
conductor and the amount of current on the neutral conductor.
If the amount differs by 0.005 to 0.006 amperes, the GFCI
trips, stopping the flow of current. It is assumed the
unaccounted for current could be flowing through a person
and thus protection from electrical injury is provided.
The second circuit in a GFCI detects when a neutral to
ground fault occurs. The designers of the GFCI with pressure
from Europe where whole house ground fault detection is
required installed in 1986 the second neutral fault detection
circuit.
Since any current flowing over the earth would be
objectionable, unwanted and harmful the GFCI trips and
opens the electrical circuit stopping the flow of harmful neutral
current over the earth. A proposal has been submitted to the
2005 NEC to have dairy and pig farms install GFCIs on all
120-volt circuits.
XVII. CONCLUSIONS
It appears that whenever the utilities were faced with the
choice of public safety or saving costs they chose saving
costs over the safety of the public with respect to the
multigrounded neutral distribution system and the
modifications that were made that were “beneficial to the
transformer”.
In order to have an electrical distribution system that is safe
from the great and continuous risks of harm from stray current
flowing uncontrolled over the earth in unrestrained amounts
the following must be accomplished:
i. The multigrounded neutral distribution system must be
eliminated and replaced by the 4-wire, see figure 20
with phase-to-phase loads or the 5-wire, see figure 16
with either phase-to-phase or phase-to-neutral loads
type distribution system, which will eliminate using the
earth for a return current path and will contain all the
return current on an insulated conductor as specified
by Zipse’s Law.
ii. The hazardous connection of the primary neutral to the
secondary neutral is no longer needed to allow
previously poorly earthed lightning arrestors to function
since the ground conductor is earthed at four times per
mile providing adequate earth connection for the
lightning arrestors.
iii. No longer will the messenger be allowed to functioning
as a messenger, a neutral and a ground conductor.
The service drop conductors will consist of one, two or
three phase conductors, an insulated neutral, and the
messenger that can also serve as the earthing
conductor only.
iv. No longer will the neutral be connected to the earth at
the service disconnect and overcurrent panelboard.
With a separate insulated neutral, which will be
connected to earth at the transformer and a ground
conductor from the transformer coming into the service
disconnect and overcurrent panelboard at the
residence, it will not be required to connect the neutral
to the earth again at the service disconnect and
overcurrent panelboard.
v. Consideration should be given to the installation of
GFCIs on all 120-volt circuits that could become or
could develop a neutral-to-ground fault.
If the public wants to be able to enter a swimming pool or a
hot tub or to take a shower without the fear of receiving an
unwanted electric shock or to be a victim of an electrocution,
then the public must rise up in letter writing to their Public
Service Commissions and their legislators both local and
federal and demand an electrical distribution system free from
to flow of uncontrolled hazardous stray current.
22
XVIII. REFERENCES
[1] Institute of Electrical and Electronic Engineers’ National
Electrical Safety Code, ANSI C-2, Piscataway, NJ,
Edition 2002.
[2] IEEE Std 100-1996, “ The IEEE Standard Dictionary of
Electrical and Electronics Terms”, Piscataway, NJ
[3] ANSI/IEEE Std. 80, IEEE Guide for Safety in Substation
Grounding, New York, NY
[4] ANSI/IEEE Standard 142, “Recommended Practice for
Grounding of Industrial and Commercial Power Systems”
(Green Book), Piscataway, NJ.
[5] NFPA Standard 70, “National Electrical Code” Quincy
MA.
[6] D. W. Zipse, “Electrical Shock Hazard Due to Stray
Current”, (Subtitled, “The Shocking Shower”) in IEEE
I&CPS Conference Record, May 1999.
[7] D. W. Zipse, “Are The National Electrical Code and the
National Electrical Safety Code Hazardous to Your
Health?”, (Subtitled, “The Shocking Swimming Pool”) in
IEEE I&CPS Conference Record , May 1999.
[8] State of Wisconsin, Circuit Court, Brown County, Case
No. 00-CV-1441, Russell Allen –v– WPSC
[9] http://www.ag.state.mi.us/speclit_div/speclit_hm.htm,
select “Dave Stetzer” exhibits for a short list of site
investigations, Michigan Attorney General case against
Consumers Power in the PSC.
[10] Charles F. Dalziel, “Dangerous Electric Currents”, AIEE
Transactions, August – September 1946, Vol. 65, pp. 579
– 585.
[11] J. Ma, F. P. Dawalibi and W. K. Daily, “Analysis of
Grounding Systems in Soils with Hemispherical
Layering”, PES Transactions.
[12] Tom Shaughnessy, PowerCet Corporation, 3350 Scott
Boulevard, Building 55, Unit 1, Santa Clara, CA 95054,
Vol. No. 3, Summer 1997.
[13] H. H. Dewey, General Considerations in Grounding the
Neutral of Power Systems, AIEE, April 1923, pp. 405-
416.
[14] G. G. Post, Important Features of a Successful Plan for
Rural Electrification, AIEE Transactions, May 1926, pp.
515-521.
[15] Electricity On The Farm, Feb. to Aug. 1930, G. E. History,
Schenectady Museum, Schenectady, NY.
[16] C. Francis Harding and C. S. Sprague, Interconnection of
Primary Lightning Arrester Ground and the Grounded
Neutral of the Secondary Main”, Transaction AIEE, 1932,
pp.234-238
[17] IEEE Standard 141, “IEEE Recommended Practice for
Electrical Power Distribution for Industrial Plants”,
Piscataway, NJ,
and
IEEE Standard , 241, titled, “Recommended Practice for
Electric Power Systems in Commercial Buildings,
Piscataway, NJ,
[18] Present-Day Grounding Practices on Power Systems –
third AIEE Report on System Grounding, AIEE 1947, Vol.
66, pp. 15251551.
[19] Short, et al, Five Wire Distribution System Demonstration
Project, IEEE Transactions on Power Delivery, Vol. 17,
No. 2, April 2002.
[20] Edie Buchanan Administrator of the Estate of Michael C
Yandek, Deceased v. FirstEnergy Corporation, et al.,
Case No.: 408609, Judge: TIMOTHY McCORMICK.
Cleveland, OH
XII. BIBLIOGRAPHY
ANSI/IEEE Std. 100, IEEE Standard Dictionary of Electrical
and Electronic Terms, New York, NY
AIEE Committee Report, “Application of Ground Fault
Neutralizers, Electrical Engineering, vol. 72, July 1953, p. 606
IEEE Standard 81, “IEEE Guide for Measuring Earth
Resistivity, Ground Impedance and Earth Surface Potentials
of a Ground System in Part 1: Normal Measurements.”
John P. Nelson. “High Resistance Grounding Of Low Voltage
Systems” IEEE – IAS – PCIC 96-3 Conference Record, Sept.
1996.
John P. Nelson. “The Grounding of Power Systems Above
600 Volts: A Practical Viewpoint”, IEEE – IAS – PCIC 03-X
Conference Record, Sept. 2003
VITA
Donald W. Zipse (S'58-M'62-SM'89-F’94-LF’97) was
graduated from the Williamson Free School of Mechanical
Trades with honors where he gained practical experience in
electrical construction and in power plant operation. He
received his electrical engineering degree from the University
of Delaware and went to work for Cutler-Hammer as an area
sales engineer. He spent 16 years with ICI America, Inc in
their Central Engineering Department as a company wide
electrical specialist.
For the next 14 years, he was with the FMC Corporation
in their Engineering Service organization, functioning as an
Electrical Engineering Consultant, responsible for providing
electrical design of new facilities and consulting service to the
total corporation, both chemical and mechanical groups.
23
He is a registered Professional Engineer. He represents
the IEEE on the National Electrical Code Making Panel #14,
Hazardous Locations as well as the Lightning Standard NFPA
780 and is a member of the International Association of
Electrical Inspectors. He serves on the National Electrical
Safety Code Grounding Subcommittee.
He has served on many IEEE committees, participated in
the color books (IEEE Recommended Practice), and standards
groups, including the Standards Board and the
Standards Board’s Review Committee. He is a member of the
IEEE COMAR, Committee On Man And Radiation and
Standards Correlating Committee #28, Non-Ionization Radiation.
Mr. Zipse received the Standards Medallion for his work
in and promoting standards.
He has published countless technical papers on such
diverse and controversial subjects as Unity Plus Motors,
Computers, Neutral to Ground Faults, NEC Wire Tables,
Health Effects of Electrical and Magnetic Fields, Measuring
Electrical and Magnetic Fields, Lightning Protection Systems:
Advantages and Disadvantages, the NESC and the NEC: Are
Dangerous to Your Health? Electrical Shock Hazard Due To
Stray Current and has participated on National Electrical Code
panels and in teaching the Code.
For the last ten years, he has been President of Zipse
Electrical Engineering, Inc., an electrical forensic engineering
consulting firm. For the past seven years, he has been
primarily involved as a forensic engineer and expert witness in
cases resulting from electrical accidents and electrocutions
and for the last two years he has been involved in legal cases
concerning stray current and dairy cows. Jose Pomares Reply to this comment |
The article referenced some figures that were not in my newsletter.
Were figures attached? Brian Purvis Reply to this comment |
The reason for the popularity of 4-wire multigrounded neutral primary distribution in the United States has very little to do with cost but rather that the 4-wire multigrounded neutral system has superior resistance to LIGHTNING, particularly the low energy kind. What phase to neutral connected distribution transformers do is that they provide a path that prevents buildup of excessive static charge on the ungrounded conductors from a phenomenon known as Saint Elmo's Fire. During just about any rainstorm there is a more is less steady trickle of static electricity from the sky in addition to the usual lighting bolts. Wires that are up in the air collect this static charge very easily and if there is no path for it it builds up to astounding levels.
Multiple grounding of the neutral where the pole spacing is frequent such as in urban arease also hepls with the higher energy lightning too.
A multigrounded neutral ( TNC grounding ) on the supply side of an electrical service also provides protection against unbalanced voltages if the neutral should go open circuit. One of my customers had his underground service neutral go bad on Super Bowl Sunday in 2002 with the result that a lot more than 120 volts was applied to some appliances with resulting damage. This was because the electrician who built the original electrical service fogot to hook up the copper water pipe that was connected to the metal well casing. A temporary connection of the well casing and copper pipe using automotive jumper cables ( until I got the real deal from the supply house ) produced good voltage stability until Ohio Edison hooked up a temporary neutral that I ran from the padmount transformer to the meter socket.
In actuality, most dairy farms need full fledged 3-phase power and it is possible to buy single phase transformers for phase-to-phase connection on 7,200Y12,470 volts or any other wye voltage to reduce to nearly zero the primary neutral current that is added by a farm. Also, connection of some single phase distribution transformers phase-to-phase improves voltage regulation for single phase motors particularly far away from the substation.
There are also other ways to beat that neutral current gremlin. Dr. Jesse Aronstein ran some experiments for the Consumer Product Safety Commission that showed that a wire brush is 100% INEFFECTIVE at removing aluminum oxide and the best agent for removing aluminum oxide is #220 silicon carbide abrasive paper. Yet, most utilities continue to wire brush aluminum wire and Rural Utilies Service still requires the use of a wire brush.
You can also get terminals that you tungsten inert gas weld to 3/0 and larger alumin wire.
Mike Cole, mc5w at earthlink dot net
Michael R. Cole Reply to this comment |
Are the figures referenced in this document availiable, or have I missed seeing them?
I heartaly agree with the concern when regulations are generated by indiniduals (our esteemed governmental officials) who have no knowledge of what they are regulating and do not appear to have enough native intelligence to make a reasonable decision on anything other than poll results and political spin. Howard Smay Reply to this comment |
|
| |
|