Visit MikeHolt.com
Class 2 and 3 Circuits - Article 725 based on the 2014 NEC  

 
Image

By Mike Holt, NEC Consultant


Modern buildings make extensive use of Class 2 and Class 3 circuits. Do you know the Code requirements?

If the power source is a listed Class 2 transformer or listed Class 2 power supply, or it’s in listed equipment marked to identify the Class 2 power source, you’ve got a Class 2 circuit between the power source and the connected Class 2 equipment [725.2]. Take that sentence, change the 2 to 3, and you define a Class 3 circuit.

Class 2 circuits are rendered safe by limiting the power supply to 100 VA for circuits that operate at 30V or less, and the current to 5 mA for circuits over 30V [Chapter 9, Table 11(A)]. Class 2 circuits typically include wiring for low-energy, low-voltage loads such as thermostats, programmable controllers, and security systems. Class 2 also includes twisted-pair or coaxial cable that interconnects computers for Local Area Networks (LANs) and programmable controller I/O circuits [725.121(A)(3) and 725.121(A)(4)].

Class 3 circuits are used when the power demand exceeds 0.50 VA, but not more than 100 VA, for circuits over 30V [Chapter 9, Table 11(A)].

Power source
The power source for a Class 2 or a Class 3 circuit must be [725.121(A)]:

(1) A listed Class 2 or Class 3 transformer.

(2) A listed Class 2 or Class 3 power supply.

(3) Equipment listed as a Class 2 or Class 3 power source.

Exception 2 to 725.121(A)(3). Where each circuit has an energy level at or below the limits established in Chapter 9, Table 11(A) and Table 11(B), the equipment doesn’t need to be listed as a Class 2 or Class 3 power transformer, power supply, or power source.

(4) Listed information technology equipment.

(5) A dry cell battery rated 30V or less (for a Class 2 circuit).

Equipment supplying Class 2 or Class 3 circuits must be marked to indicate each circuit that’s a Class 2 or Class 3 circuit [725.124]. This requirement means that the power source must be marked but not the raceways, cables, or fittings containing the Class 2 or 3 circuits.

Wiring methods
Of the Article 300 sections, only those specifically referenced in Article 725 apply to Class 1, 2, and 3 circuits [725.3].

Conductors and equipment on the supply side of the Class 2 or Class 3 power source must be installed per Chapters 1 through 4 [725.127]. On the load side, Class 2 or Class 3 circuits can also use a Chapter 3 wiring method [725.130(A)].

Class 2 and Class 3 circuits can be reclassified as a Class 1 circuit if the Class 2 and Class 3 equipment markings required by 725.124 are eliminated and the entire circuit is installed using a Chapter 3 wiring method per Part II of Article 725 for Class 1 circuits. But then they are no longer Class 2 or Class 3 circuits, regardless of their continued connection to a Class 2 or Class 3 power source [725.130(A) Ex 2].

Class 2 and Class 3 circuit conductors must be of the type listed and marked per 725.179. Install them per 725.133 and 725.154 [725.130(B)].

Installation of Class 2, Class 3, and PLTC cables must comply with 725.135(A) through (M). Some highlights:

(A) Class 2, Class 3, and PLTC cables installed in buildings must be listed.

(C) Plenum rated Class 2 or Class 3 cables are permitted in plenum spaces as described in 300.22(C)(1) through (6).

(H) Cables installed in cable trays outdoors must be Type PLTC. There are several other types for cable trays indoors.

Separation from power conductors
Class 2 and Class 3 circuit conductors [725.136]:

  • Must not be placed in any enclosure, raceway, or cable with conductors of electric light, power, and Class 1 circuits, except as permitted in 725.136(B) through (J). [725.136(A)]
  • Must not be installed with conductors of electric light, power or Class 1 conductors unless separated by a barrier [725.136(B)].
  • Can be mixed with electric light, power, and Class 1 conductors in enclosures if these other conductors are introduced solely for connection to the same equipment as the Class 2 or Class 3 circuits, and a minimum ¼ in. separation is maintained from the Class 2 or Class 3 conductors [725.136(D)].
  • Must be separated by at least 2 in. from insulated conductors of electric light, power, and Class 1 circuits, unless electrical power and Class 1 circuit conductors are in a raceway or metal-sheathed or nonmetallic-sheathed cable, or the Class 2 and Class 3 circuit conductors are in a raceway or metal-sheathed or nonmetallic-sheathed cable [725.136.(I)].

Different circuits
You can mix some of these circuits in cables, raceway, etc. [725.139]:

(A) Class 2 circuit conductors can be in the same cable, cable routing assembly, enclosure, or raceway as other Class 2 circuit conductors. Same thing for Class 3 conductors with other Class 3 conductors.

(C) Class 2 conductors can be within the same cable, cable routing assembly, enclosure, or raceway as Class 3 circuit conductors, if insulation of the Class 2 circuit conductors is at least that required for Class 3 circuits.

(D)(1) Class 2 and Class 3 circuit conductors can be within the same cables as communications circuits in listed communications cables in which case they’re classified as communications circuits and must be installed per Article 800. A common application of this requirement is when a single communications cable is used for both voice communications and data. Note that listed Class 2 cables have an insulation rating of at least 150V insulation [725.179(G)], whereas listed communications cables have a voltage rating of at least 300V [800.179].

(E) Class 2 or Class 3 jacketed cables can be in the same enclosure, cable tray, raceway, or cable routing assembly as jacketed cables of any of the following:
(1) Power-limited fire alarm circuits in compliance with Parts I and III of Article 760.
(2) Nonconductive and conductive optical fiber cables in compliance with Parts I and IV of Article 770.
(3) Communications circuits in compliance with Parts I and IV of Article 800.
(4) Coaxial cables in compliance with Parts I and IV of Article 820.

(F) Audio output circuits [640.9(C)] using Class 2 or Class 3 wiring methods in compliance with 725.136 and 725.154 aren’t permitted in any cable routing assembly, raceway, or cable with Class 2 or Class 3 conductors or cables. But why? The concern is that a fault from audio amplifier circuits to a Class 2 and Class 3 circuit has the potential of creating a hazard by disrupting the operation of alarm systems and remote-control circuits for safety-control equipment.

Support
Class 2 control cables can be supported by the raceway that supplies power to the equipment controlled by the Class 2 cable [300.11(B)(2)]. That’s the only case in which raceway can be used to support Class 2 or Class 3 cables; it’s otherwise forbidden [725.143].

Exposed cables must be supported by the structural components of the building such that the cable won’t be damaged by normal building use. Cables must be secured by straps, staples, hangers, or similar fittings designed and installed in a manner that won’t damage the cable [725.24].

Listing and marking
Class 2, Class 3 cables, nonmetallic signaling raceways, and cable routing assemblies installed within buildings must be listed as being resistant to the spread of fire. Other criteria per 725.179(A) through (J) also apply, and the cable shall be marked per 725.179(K).

(A) Types CL2P and CL3P. Types CL2P and CL3P plenum cable are listed as being suitable for use in plenum space and listed as having adequate fire-resistance and low-smoke producing characteristics.

(G) Class 2 cables must have a voltage rating not less than 150V, and Class 3 cables must have a voltage rating not less than 300V.

(K) Voltage ratings can’t be marked on the cable. Why? Because voltage markings on cables may suggest the cables are suitable for Class 1 or electric power and light applications, but they aren’t.

Avoiding problems
The biggest threat to Class 2 and Class 3 circuits is voltage induced from wiring such as that supplying conductors of electric light, power, and Class 1 circuits. You need to keep these separate.



Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 
Image
 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
Mike Holt Enterprises of Leesburg, Inc. 3604 Parkway Blvd. Suite 3 Leesburg, FL 34748
"... as for me and my house, we will serve the Lord." [Joshua 24:15]
Comments
  • Great informational note I'm in the process of my level A EI exam Oregon this one of the notes I have seen on my exam. Thank you

    Michael Gatt  September 3 2016, 2:35 am EDT
    Reply to this comment

  • Mike, What cable do I use for a thermostat that the engineer wants to use non plenum cable that the controller is in a plenum?

    TJ Fay  September 1 2016, 9:51 am EDT
    Reply to this comment

  • What about the new type of cable that has both low voltage & 120 volt wire together

    Glenn  September 1 2016, 8:55 am EDT
    Reply to this comment

  • Thank you to all at Mike Holt who contributed to this article. If nothing else soaks in I hope that the reference to NEC 725.143 relative to supporting Class 2 & 3 cables from other conduit sticks with all those who read the article.

    Please keep such good reference material articles coming!

    Rick M.  August 31 2016, 12:30 pm EDT
    Reply to this comment

  • Would appreciate more discussion of the implications of this for new high amperage Power over Ethernet (PoE) applications, using PoE network switches to provide 90W of power to lighting and other devices, over Cat-6, and even powering up the ceiling grid itself.

    Richard Sanders  August 31 2016, 11:19 am EDT
    Reply to this comment

  • Mike,

    Thank you for the comprehensive review on class 2 & 3 cables and allowable support with regard to line voltage devices. I have this discussion with electrical contractors and low voltage systems providers regularly during design and observation reporting.

    Chris Daniels  August 31 2016, 7:23 am EDT
    Reply to this comment

  • One thing that seems obvious when you look at it closely but was not explicitly stated in the text: If you reclassify a Class 2 circuit as Class 1 to allow it to share a cable or raceway with power circuits, you can no longer use loads which are restricted for use with a Class 2 supply only, even though the supply itself is still Class 2. For this reclassification to work the loads must all be listed for Class 1 operation as well as Class 2.

    Dave Uggla  August 31 2016, 3:13 am EDT
    Reply to this comment

  • Mike,

    Didn't see this in your post, but a lot of new networking components now use POE or power over Ethernet. This voltage is about 54VDC, and changes a class 3 network cable to class 2, since over the 30V threshold. The biggest issue is that there is CCA network cable in the marketplace due to the Chinese. This becomes an extreme fire hazard as the copper clad aluminum is not rated for the voltages or currents that is commonly used by most POE devices. Users tend to complain of problems with the devices, and don't realize it's due to the wire as its looks like copper when exposed.

    Don't know if you remember, I'm one of the EE's that attended your class in Indianapolis on bonding and grounding, and that we investigate fires as part of our forensic services to our clients. I have only personally seen one case where this has occurred, but one fire is too many in my book.

    So I ask that we make our fellow electrical contractors know that CCA network wire is a very bad idea, as you never know if the customer is going to attach a POE device to the wire.

    Kevin H.

    Kevin Hecksher  August 31 2016, 1:54 am EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter