Visit MikeHolt.com
GFCIs and AFCIs - Based on the 2014 NEC  

 

By Mike Holt, NEC Consultant

Protecting against ground faults and arc faults in branch circuits.

Two different technologies protect against two different types of hazard. Ground Fault Circuit Interrupter (GFCI) devices protect people from shock by opening a circuit at a low threshold of leakage current (typically 6 mA). Arc Fault Circuit Interrupter (AFCI) devices protect buildings and occupants by opening a circuit upon detecting an arc fault.

The threshold current for an AFCI is too high to protect individuals against shock. Both must be installed in readily accessible locations.

 

GFCI

A GFCI device must be installed in the places named in 210.8(A) through (D). The last two ((C) and (D)) are boat hoists and dwelling unit dishwashers, respectively. Note that 210.8(A) is for dwelling units and 210.8(B) is for everything else.

(A) Dwelling Units. GFCI protection is required for all 15A and 20A, 125V receptacles installed in:

(1) Bathroom Areas.

(2) Garages and Accessory Buildings. Includes grade-level portions of accessory buildings used for storage or work areas of a dwelling unit. If you install a 15A or 20A, 125V receptacle in an accessory building, it must be GFCI protected.

(3) Outdoors. Includes all receptacles outside a dwelling unit. Each unit of a multifamily dwelling with individual entrances at grade level must have at least one GFCI-protected receptacle accessible from grade level and not more than 6½ ft above grade [210.52(E)(2)]. Attached balconies, decks, and porches accessible from inside the unit must each have at least one GFCI-protected receptacle [210.52(E)(3)].

(4) Crawl Spaces. The NEC requires a receptacle in a crawl space only if it contains heating, air-conditioning, and refrigeration equipment [210.63].

(5) Unfinished Basements. These are the unfinished portion(s) not intended as a habitable room and limited to storage and work areas. Excluded are receptacles supplying only permanently installed fire alarm or burglar alarm systems [760.41(B) and 760.121(B)].

(6) Kitchen Countertop Surfaces.

(7) Sinks. Includes only receptacles within an arc measurement of 6 ft from the outside edge of a sink.

(8) Boathouses. If you install a 15A or 20A, 125V receptacle in a boathouse, it must be GFCI protected.

(9) Bathtubs or Shower Stalls. Includes only receptacles within 6 ft of the outside edge of a bathtub or shower stall.

(10) Laundry Areas.

 

(B) Other than Dwelling Units. GFCI protection is required for all 15A and 20A, 125V receptacles installed in these commercial/industrial locations:

(1) Bathrooms. If you install a 15A or 20A, 125V receptacle in a commercial or industrial bathroom, it must be GFCI protected.

(2) Kitchens. Includes even those receptacles that don’t supply the countertop surface (but not those rated other than 15A and 20A, 125V).

(3) Rooftops.

(4) Outdoors.

Exception 2 to (3) and (4): GFCI protection isn’t required for a receptacle supplied by a branch circuit dedicated to fixed electric snow-melting or deicing or pipeline and vessel heating equipment, if the receptacle isn’t readily accessible and the equipment or receptacle has ground-fault protection of equipment (GFPE) [426.28 and 427.22].

(5) Sinks. Includes only receptacles installed within 6 ft of the outside edge of a sink. Excluded are receptacles in patient bed locations of general care or critical care areas of health care facilities. Also excluded are, in industrial laboratories, receptacles used to supply equipment where removal of power would introduce a greater hazard.

(6) Indoor Wet Locations.

(7) Locker Rooms. If they have associated showering facilities.

(8) Garages. Includes service bays and similar areas, unless in show rooms or exhibition halls.

 

AFCI

AFCI protection must be provided per 210.12(A), (B) and (C).

(A) Where Required. All 15A or 20A, 120V branch circuits in dwelling units supplying outlets or devices in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar places must be protected by one of the following (all listed):

(1) Combination type AFCI, installed to protect the entire branch circuit.

(2) Branch/feeder type AFCI at the origin of the branch circuit, plus a listed outlet branch-circuit AFCI installed at the first outlet box of the branch circuit. The outlet box must be marked to indicate that it’s the first outlet box of the circuit.

(3) Supplemental arc protection circuit breaker installed at the origin of the branch circuit, plus a listed outlet branch-circuit type AFCI installed at the first outlet box on the branch circuit. When using this option:

(a) The branch-circuit wiring must be continuous from the branch circuit overcurrent protection device (OCPD) to the AFCI device.

(b) The maximum length of the branch circuit to the AFCI is 50 ft for 14 AWG conductors or 70 ft for 12 AWG conductors.

(c) The first outlet box in the circuit must be marked to indicate that it's the first outlet box of the circuit.

(4) A regular fuse or circuit breaker, plus a listed outlet branch-circuit type AFCI installed at the first outlet of the branch circuit. When using this option, the same conditions apply as for (3) above but also the combination of the branch-circuit OCPD and the AFCI must be listed and identified as meeting the requirements for a “System Combination” type AFCI.

(5) You can use a listed outlet branch-circuit type AFCI at the first outlet, if the wiring between the OCPD and the AFCI contains all metal boxes and is installed using any (or a combination) of the following: RMC, IMC, EMT, Type MC, Type AC cables meeting the requirements of 250.118, metal wireways, or metal auxiliary gutters.

(6) You can use a listed outlet branch-circuit type AFCI at the first outlet, if the wiring between the OCPD and the AFCI is in a raceway with 2 in. of concrete encasement.

 

(C) Dormitory Units. All 120V, single phase, 15A and 20A branch circuits supplying outlets in dormitory unit bedrooms, living rooms, hallways, closets, and similar rooms must be AFCI protected.

 

Combo AFCI

The combination AFCI is a circuit breaker that protects downstream branch-circuit wiring plus cord sets and power-supply cords; an outlet branch-circuit AFCI (receptacle) is installed as the first outlet in a branch circuit to protect downstream branch-circuit wiring, cord sets, and power-supply cords.

Where branch-circuit wiring is modified, replaced, or extended in any of the areas specified in 210.12(A), the branch circuit must be protected by a listed [210.12(B)]:

(1) Combination AFCI located at the origin of the branch circuit; or

(2) Outlet branch circuit AFCI located at the first receptacle of the existing branch circuit.

Exception: AFCI protection isn’t required for extensions less than 6 ft long, if there are no outlets or devices added.

 

Omissions

The 120V circuit limitation means AFCI protection isn’t required for equipment rated 230V, such as a baseboard heater or room air conditioner.

You can omit AFCI protection for an individual branch circuit to a fire alarm system in accordance with 760.41(B) and 760.121(B), if the circuit conductors are installed in metal wireways, metal auxiliary gutters, RMC, IMC, EMT, or steel sheath Type AC or MC cable that qualifies as an equipment grounding conductor in accordance with 250.118, with metal outlet and junction boxes.

Smoke alarms connected to a 15A or 20A circuit in a dwelling unit must be AFCI protected if the smoke alarm is in one of the areas specified in 210.12(A). The exemption from AFCI protection for the “fire alarm circuit” contained in 760.41(B) and 760.121(B) doesn’t apply to the single- or multiple-station smoke alarm circuit typically installed in dwelling unit bedroom areas.

This is because a smoke alarm circuit isn’t a fire alarm circuit as defined in NFPA 72, National Fire Alarm Code. Unlike single- or multiple-station smoke alarms, fire alarm systems are managed by a fire alarm control panel.

 

Exercise judgment

It’s important to remember that, despite how detailed 210.8 and 210.12 are, the people serving on the Code Making Panel for Article 210 can’t think of every possible scenario. In applications where GFCI or AFCI isn’t required, this does not mean they are prohibited. It means they are optional.

Optional means you should exercise your judgment. Think about the application and whether there’s a reasonable chance of a hazard that an optional GFCI and/or AFCI would protect against, given the intended use of the occupancy. Yes, these do cost a little more but the owner may gladly pay for the added protection if you explain your reasoning and the possible consequences of going without.

 

Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 
Image
 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
Mike Holt Enterprises of Leesburg, Inc. 3604 Parkway Blvd. Suite 3 Leesburg, FL 34748
"... as for me and my house, we will serve the Lord" [Joshua 24:15]
Comments
  • In your example on 210.8 a6 you have dishwasher as example as exclusion from gfci protection but in 210.8D it says otherwise please clarify.

    Brett Williams  September 15 2015, 8:43 pm EDT
    Reply to this comment

  • What about hard wired dishwashers?Do they have to be on GFCI?

    Bezo  September 13 2015, 9:50 am EDT
    Reply to this comment

  • Just a matter of time until GFI protection is required on anything that has (possible) contact with water, moisture, or other liquids, e.g. Disposal, water heater, refrigerator, pump for (water) well, outdoor (pad mounted) air conditioner units [including 230-volt units], clothes washers, etc. You name it !

    Jim Green   September 12 2015, 6:31 pm EDT
    Reply to this comment

  • What about arc fault protection for lighting,is it required?

    Eddie  September 12 2015, 9:45 am EDT
    Reply to this comment

  • The following in your newsletter is miss leading: (6) Kitchen Countertop Surfaces. Excluded are receptacles supplying built-in appliances (e.g., dishwashers).

    as further down (D) requires dishwashers to be GFCI protected. However do have a question as to dedicated Microwave outlets: If it is more than 6'-0" from a sink is it still required to be GFCI. My interpretation is that it is not.

    Christina  September 11 2015, 10:38 am EDT
    Reply to this comment

  • 210.8 (D) Kitchen Dishwasher Branch Circuit. GFCI protection shall be installed for outlets that supply dishwashers installed in dwelling units.

    David Fjeran  September 11 2015, 7:23 am EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter