Visit MikeHolt.com
New UL GFCI Standard  

 

Underwriters Laboratories (UL) has announced a revision to standard UL 943 that became effective on June 29, 2015. Because testing a GFCI is a good way to verify that it is providing protection, the revision requires that all UL certified Class A residential and commercial grade wallbox mounted GFCIs have: Image

 

a) An auto-monitoring function that will allow for periodic automatic testing (self-test) of the GFCI device and its ability to respond to a ground fault. If a problem is detected one or more of the following will happen:

- Power will be denied (trip with the inability to reset)

- Trip with the ability to reset, subject to the next auto-monitoring test cycle or repeatedly trip

- Visual and/or audible indication

b) Provisions to ensure that receptacle type GFCIs that contain separate line and load terminals, and that is powered through its load terminals, shall not reset and supply power to its receptacle face or line terminals if miswired. This applies both during its initial installation and after reinstallation following a correctly wired installation. If the device is provided with special instructions for removal and reinstallation, the instructions shall be followed during testing.

 

Leviton Responds with New Self-Test Models

In response to the revised standard, GFCI manufacturers must stop producing their current GFCIs and only manufacture the new self-test models as of the end of June. What this means is that you will notice a gradual transition in the market to self-test models by all manufacturers of GFCIs after that date. It is important to note that you can continue to sell and install any GFCI products manufactured prior to the effective date of the revised standard with no restrictions on phase out.

Click here to read the Self-Test GFCI Flyer from Leviton outlining which products are affected along with information on the new self-test products.

 

 

Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 
Image
 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
Mike Holt Enterprises of Leesburg, Inc. 3604 Parkway Blvd. Suite 3 Leesburg, FL 34748
"... as for me and my house, we will serve the Lord" [Joshua 24:15]
Comments
  • the correct way to fasten fire alarm mc cable 0n a main beam of a house. Staples or clips.

    ed bonollo  January 16 2016, 2:48 pm EST
    Reply to this comment

  • Will this change extend to panel mount gfci breakers? If so it will cause more homeowners to get electrocuted because they will r and r a breaker as well as a receptacle but in a live panel instead of a dead branch circuit. Probably standing on a concrete floor as well. It's called E.N.S. Excelerated Natural Selection.

    Jim  September 8 2015, 11:52 am EDT
    Reply to this comment

  • will this UL change also affect chord and plug connected GFCI's used in construction as well?

    Rick  August 28 2015, 5:30 pm EDT
    Reply to this comment

  • Going to be interesting when Johnny home owner comes home in the middle of winter after vacation and finds that his garage door opener doesn't and that his freezer and fridge are all defrosted. Not sure they thought this one out.

    Paul Matthews  August 27 2015, 4:42 pm EDT
    Reply to this comment

  • This may lead to homeowners removing and replacing them with non-GFCI outlets. When you make a safety change you have to consider intangible effects and human behavior as well.

    Matt Egloff  August 27 2015, 10:06 am EDT
    Reply to this comment

  • this will be real nice when the GFI on the freezer or fridge fails

    darwin  August 27 2015, 9:46 am EDT
    Reply to this comment

  • Clarification: it's not just all "UL certified" GFCIs. There are many ETL Listed GFCIs to UL-943 as well (including Leviton). The change will affect all Class A residential and commercial grade wallbox mounted GFCIs listed to UL-943 regardless of the certifying company.

    Derek Silva  August 27 2015, 9:17 am EDT
    Reply to this comment

  • Seems that the new requirement will eventually phase out GFCI receptacles in new construction if the DUAL FUNCTION branch circuit disconnect is acceptable in dwellings. Consideration of using DUAL FUNCTION technology would at least eliminate multiple GFCI receptacle usage and testing potential flaws if the source GFCI protection is more stable.

    Ben Jacks  August 27 2015, 4:30 am EDT
    Reply to this comment

  • Is DUAL FUNCTION breakers affected?

    Ben Jacks  August 27 2015, 4:11 am EDT
    Reply to this comment

  • GFCIs have had a less that start history. The Question what took them so long to develop this most current fix? I bet the legal cost were becoming excessive.

    L.W. Brittian  August 26 2015, 10:58 pm EDT
    Reply to this comment

  • Do they really think a homeowner will put up with testing an outlet ? I hate to say it but when it becomes a headache the owners will be taking them out and now all the protection is gone.

    tom  August 26 2015, 10:50 pm EDT
    Reply to this comment

  • Mike, Thanks for the notification about New UL GFCI Standards.

    glene77is  August 26 2015, 8:24 pm EDT
    Reply to this comment

  • What is the justification for this change. I can't help but think this is going to be expensive and much like the AFCI's, not very dependable. Is this justified by statistics to show the need for a self test?.

    Bill Clapp  August 26 2015, 8:05 pm EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter