This article was posted 03/31/2006 and is most likely outdated.

Grounding vs Bonding Online Training
 

 
Grounding vs Bonding: 250.92 Service Bonding

March 31, 2006  

  View Comments | Add Comments | Notify Me When Comments Are Added  

 


PART V. BONDING   Hi Res - Cable/DSL [11639Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
 
Sections

250.92 Service Bonding.

(A) Equipment and Raceways. The following metal parts must be service bonded to an effective ground-fault current path in accordance with 250.92(B): Figure 250–125

(1) Metal raceways containing service conductors.
(2) Enclosures containing service conductors.

Author’s Comment: Metal raceways and enclosures containing service conductors must be effectively bonded in accordance with 250.92(B).
(3) A metal raceway containing the grounding electrode conductor.

Author’s Comments:
• The metal raceway containing the grounding electrode conductor must be effectively bonded in accordance with 250.64(E).
• Raceways or enclosures containing feeder and branch-circuit conductors are not required to be service bonded in accordance with 250.92(B). Figure 250–126
(B) Methods of Bonding. Enclosures and raceways containing service conductors must be bonded to an effective ground-fault current path by one of the following methods:

(1) Grounded Neutral Conductor. Enclosures and raceways containing service conductors are considered bonded to an effective ground-fault current path by bonding to the grounded neutral service conductor via the main bonding jumper. Figure 250–127
The bonding must be by exothermic welding, listed pressure connectors, listed clamps, or other listed
fittings [250.8].

Author’s Comments:
• A main bonding jumper is required to bond the service disconnect to the grounded neutral service conductor [250.24(B) and 250.28].
• At service equipment, the grounded neutral service conductor is used to provide the effective ground-fault current path to the power source [250.24(C)]. Therefore, an equipment grounding (bonding) conductor isn’t required to be installed within a nonmetallic raceway containing service-entrance conductors [250.142(A)(1) and 352.60 Ex. 2]. Figure 250–128



Figure 250–125
(Click on image to enlarge)


Figure 250–126
(Click on image to enlarge)


Figure 250–127
(Click on image to enlarge)


Figure 250–128
(Click on image to enlarge)

 

Copyright © 2005 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments
  • I replaced a new service panel from 100 to a 200 amp. Why do you have to seperate the grounds and neutrals in sub panel inside and not outside. Also when you have first installtion you can combine the grounds and neutrals and it would pass. Can anyone explain this to me. Grounding question. lol volk

    Edward Webb
    Reply to this comment
  • Reply from: Mike Holt   
    The following is an extract from my Grounding versus Bonding book.

    A neutral-to-ground connection at other than a separately derived system (e.g., transformer or generator) creates a condition where neutral current and ground-fault current will flow through conductive metal parts of a building or electrical system. This current flow can cause death from electric shock, property damage from fires, as well as power quality issues.

    Electric Shock. Death from electric shock occurs in a matter of minutes when electric current passes through the heart causing it to stop pumping blood to the brain (ventricular fibrillation). Ventricular fibrillation occurs when current (30 milliampere, +-10 mA) flows through the heart for approximately 1/6th of a heartbeat.

    When the service grounded (neutral) conductor is opened (wind storm, ice, etc.) all metal parts of the electrical system will become energized* and the system loses the ability to clear ground-faults. This dangerous voltage condition is of particular concern in building with pools, spas and hot tubs (personal experience), Figure 1-2.

    *To determine the actual voltage on the metal parts you need do some fancy math calculations and a spreadsheet should be used to accommodate the variable conditions. An Excel spreadsheet is available at www.MikeHolt.com, go to the Free Stuff link, and download the touch voltage calculator.

    Electric Shock - Electric shock can occur if the service grounded (neutral) conductor is open because the required neutral-to-ground connection at the service equipment permits neutral current to flow onto the metal parts of the electrical system.

    Example: If the service neutral is open, and a person is in series to a lamp (touches any grounded metal part of the electrical system), the voltage across the lamp (144 ohms) and the human body (2,400 ohms) will equal the voltage drop of the circuit (voltage source), Figure 1-3.

    The following steps explain how to calculate the voltage distribution (resistors in series). Step 1. Calculate the circuit resistance total: Rt = R1 + R2 R1 = Lamp 144 ohms (R = E2/P), R2 = Person 2400 ohms Rt = 144 ohms (lamp) + 2400 ohms (person) Rt = 2544 ohms

    Step 2. Calculate the circuit current: I = E/Rt E = Voltage source 120 volts, Rt = 2544 ohms I = 120 volts/2544 ohms I = 0.0472 amperes, or 47.2 milliamperes

    Step 3. Calculate the voltage across each of the loads: E = I x R I = 0.0472 ampere, R = 144 ohms and 240 ohms Lamp Voltage = .0472 amperes x 144 ohms, = 7 volts Person Voltage = .0472 amperes x 2400 ohms, = 113 volts

    Electric Shock from No Safety Ground - If the service grounded (neutral) conductor is open, the low-impedance path used to clear ground-fault current is lost. Under this condition (open service neutral), a ground-fault will not be cleared and all metal parts of the electrical system will be energized to line-voltage, Figure 1-4.

    Fire. A fire is created when heat is sufficient to cause ignition. In electrical systems, heat is generated whenever current flows. The temperature rise is dependent on the square of the current flow (I) and the resistance of the material (R), as well as the duration of the current flow (I2R). A neutral-to-ground connection (even if it meets the NEC requirements) can cause a fire, and sometimes an explosion, due to an electric arc if the grounded service (neutral) conductor is open.

    When the service (neutral) conductor is open, neutral current flows onto the metal parts of the electrical system because a neutral-to-ground connection (main bonding jumper) is required within the service disconnect enclosure. When the service grounded (neutral) conductor is opened in wood frame construction, neutral current seeking a return path to the power supply travels into the moist wood members. After many years the wood is converted into charcoal (wood with no moisture) because of the heat generated from the current flow. The ignition temperature of the wood is decreased and the temperature of the wood is increased because of neutral current. A fire caused by this condition is called pyroforic-carbonization, Figure 1-5.

    Author’s Comment: I can’t create an acceptable graphic to demonstrate how pyroforic-carbonization causes a fire by an open service neutral. However, if you would like to order a video (it’s fascinating) showing actual fires caused by pyroforic-carbonization, call my office 1-888 NEC CODE.
    Reply to Mike Holt


  • In Figure 250-125 there appears to be an uninsulated split-bolt connector on each of the 3 service wires feeding the meter on the right. What is the reason for this? It would make for a less problematic installation if each of the 3 wires were run unbroken from the distribution terminal block in the raceway to the respective terminal on the meter socket.

    Denny M
    Reply to this comment
  • Reply from: Mike Culbreath   
    Denny, I agree with your opinion that it would be a "better" installation without the splices althought it does comply with the NEC [230.46]. The only reason the splices are in this graphic is because I used this service in another location where they were revelent to the point being made. Since the splices do not add any specific value to this graphic in this location, I will remove them. Thanks for your input.

    Mike Culbreath Technical Illustrator Mike Holt Enterprises, Inc.
    Reply to Mike Culbreath


  • Can you tell me what grounding is required for a mobile lift that will be placed in psoition or wekks or months at a time, and runs off of 12 VDC power? The lift raises a camera in the sky, and stands 40 feet high. Are there requirements for a non-conductive section of the structure?

    Phil Buckley
    Reply to this comment
  • Reply from: Tara Moffitt   
    Phil, Questions of a technical nature should be posted on our code forum. You can post this question under the Grounding and Bonding topic and I'm sure you'll get some feedback. Here is the link to the code forum: http://www.mikeholt.com/codeForum/ Thank you
    Reply to Tara Moffitt



Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter